Quantcast

Motor Breaker GV4L Magnetic 115A 100kA Everlink Terminal

Motor Breaker GV4L Magnetic 115A 100kA Everlink Terminal

Motor Breaker GV4L Magnetic 115A 100kA Everlink Terminal

Item Number: GV4L115S

Retail
$1,267.50
RRP (Inc. GST)

Product Dimensions

Width icon

Width81 mm

Height icon

Height155 mm

Depth icon

Depth165 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Protection type

short-circuit

[In] rated current

115 A

Control type

rotary handle

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mounting mode

  • by screws
  • by clips
    • Mounting support

    • plate
    • 75 mm symmetrical DIN rail
    • 35 mm symmetrical DIN rail
      • Mechanical durability

        40000 cycles

        Electrical durability

      • 10000 cycles for AC-3 at 440 V In/2
      • 5000 cycles for AC-3 at 440 V In
        • Local signalling

          green indicatorpresence of auxiliary contacts:

          Connections - terminals

        • top 1 EverLink BTR screw connectors wire size 1.5-70 mm², solid
        • top 1 EverLink BTR screw connectors wire size 1.5-50 mm², flexible
        • bottom 1 EverLink BTR screw connectors wire size 2.5-95 mm², solid
        • bottom 1 EverLink BTR screw connectors wire size 2.5-70 mm², flexible
          • Wire stripping length

            20 mm

            Standards

          • EN/IEC 60947-4-1
          • EN/IEC 60947-2
            • Height

              155 mm

              Width

              81 mm

              Depth

              165 mm

              Net weight

              1.65 kg

              Product certifications

            • IEC
            • CCC
            • EAC
            • EU-RO MR
              • IP degree of protection

                IP40 front face conforming to IEC 60529

                IK degree of protection

                IK07 conforming to IEC 62262

                Ambient air temperature for operation

                -25-70 °C

                Ambient air temperature for storage

                -50-85 °C

                EU RoHS Directive

                Compliant

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                Product out of China RoHS scope. Substance declaration for your information

                Environmental Disclosure

                ENVPEP1704004EN

                Circularity Profile

                ENVEOLI1704004EN

                Others

                Product name

                TeSys GV4

                Device short name

                GV4L

                Poles description

                3P

                Utilisation category

                category A

                Trip unit technology

              • magnetic
              • electronic
                • Breaking capacity

                • Icu 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                • Icu 10 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                  • [Ics] rated service breaking capacity

                  • 120 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
                  • 100 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
                  • 70 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
                  • 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
                  • 18 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
                  • 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
                    • Trip unit rating

                      690-1610 A

                      Motor power kW

                    • 37-37 kW at 400...415 V AC 50/60 Hz
                    • 45-45 kW at 400...415 V AC 50/60 Hz
                    • 55-55 kW at 400...415 V AC 50/60 Hz
                    • 45-45 kW at 500 V AC 50/60 Hz
                    • 55-55 kW at 500 V AC 50/60 Hz
                    • 75-75 kW at 500 V AC 50/60 Hz
                    • 75-75 kW at 660...690 V AC 50/60 Hz
                    • 90-90 kW at 660...690 V AC 50/60 Hz
                    • 110-110 kW at 660...690 V AC 50/60 Hz
                      • [Uimp] rated impulse withstand voltage

                        [Ui] rated insulation voltage

                        800 V conforming to IEC 60947-2

                        Suitability for isolation

                        yes conforming to IEC 60947-1

                        Number of slots

                      • 1 slot(s) for alarm switch for fault signalling contact, plug-in
                      • 1 slot(s) for voltage release for electrical remote tripping, plug-in
                      • 1 slot(s) for auxiliary switch for open/close contact, plug-in
                        • Rotary handle padlocking

                          padlock in OFF or ON position

                          Connection pitch

                          27 mm

                          Tightening torque

                        • 9-9 N.m for 16-95 mm²
                        • 5-5 N.m for 1.5-10 mm²
                          • Quality labels

                            CE

                            Tropicalisation

                            2 conforming to IEC 68-2

                            Pollution degree

                            3 conforming to IEC 60947-1

                            Mechanical robustness

                          • vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6
                          • vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6
                          • shocks: 15 gn 11 ms conforming to IEC 60068-2-27
                            • Operating altitude

                            • 0...2000 m without derating
                            • 2000...5000 m with derating
                              • Unit Type of Package 1

                                PCE

                                Number of Units in Package 1

                                1

                                Package 1 Weight

                                1.45 kg

                                Package 1 Height

                                12.5 cm

                                Package 1 width

                                9 cm

                                Package 1 Length

                                22 cm

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

                                PVC free

                                Yes

                                Halogen content performance

                                Halogen free plastic parts product
                                Show all specifications

                                Frequently Asked Questions

                                hide show

                                Will the Compact NSX breaker be for sale in the USA or Canada?

                                Issue:
                                Where can I buy a Compact NSX breaker?

                                Product Line:
                                Circuit Breakers

                                Cause:
                                This breaker is popular overseas and there is interest in the US

                                Resolution:
                                There are no plans for a general release of the Compact NSX breaker line in North America, since the NSX is not UL Listed to UL489. (UL 489 is the standard commonly required in the US.) In the US, the Powerpact Circuit Breakers should be used (Powerpact breakers are UL, CSA and IEC-rated).

                                If an existing piece of equipment has an NSX breaker which needs replacing, we have made a few catalog numbers available for sale in the US. The list of numbers will vary based upon need. Contact your local authorized Schneider Electric distributor for assistance on your specific NSX catalog number.

                                For support on these breakers, Please see the following link to Global Operations where you can select other Countries:
                                https://www2.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page