MASTER YOUR CASTLE with your new build or reno project
Enter competition
Thermal-magnetic circuit-breaker TeSys GV2RT, with screw clamp terminals, 0.25A to 23A

Catalogue Number: GV2RT14

Gv2 MotOR CB High Inrush 6-10A Toggle Sw

Thermal-magnetic circuit-breaker TeSys GV2RT, with screw clamp terminals, 0.25A to 23A
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2RT
Product or component type
circuit breaker
Device application
  • transformer
  • motor
    • Trip unit technology
      thermal-magnetic
      Poles description
      3P
      Network type
      AC
      Utilisation category
    • AC-3 conforming to IEC 60947-4-1
    • category A conforming to IEC 60947-2
      • Network frequency
        50/60 Hz conforming to IEC 60947-4-1
        Fixing mode
      • 35 mm symmetrical DIN rail: clipped
      • panel: screwed (with adaptor plate)
        • Operating position
          any position
          Motor power kW
        • 1.5-1.5 kW at 220/230 V AC 50/60 Hz motor protection high peak current
        • 2.2-2.2 kW at 220/230 V AC 50/60 Hz motor protection high peak current
        • 3-3 kW at 400/415 V AC 50/60 Hz motor protection high peak current
        • 4-4 kW at 400/415 V AC 50/60 Hz motor protection high peak current
        • 4-4 kW at 440 V AC 50/60 Hz motor protection high peak current
        • 4-4 kW at 500 V AC 50/60 Hz motor protection high peak current
        • 5.5-5.5 kW at 500 V AC 50/60 Hz motor protection high peak current
        • 5.5-5.5 kW at 690 V AC 50/60 Hz motor protection high peak current
        • 7.5-7.5 kW at 690 V AC 50/60 Hz motor protection high peak current
        • 2.5-2.5 kW at 230/240 V AC 50/60 Hz transformer protection
        • 4-4 kW at 400/415 V AC 50/60 Hz transformer protection
        • 5-5 kW at 400/415 V AC 50/60 Hz transformer protection
        • 5-5 kW at 440 V AC 50/60 Hz transformer protection
        • 5-5 kW at 500 V AC 50/60 Hz transformer protection
        • 6.3-6.3 kW at 500 V AC 50/60 Hz transformer protection
          • Breaking capacity
          • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
          • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
          • 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 15 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
            • Control type
              toggle
              [In] rated current
              10 A
              Trip unit rating
              6-10 A
              Magnetic tripping current
              200-200 A
              [Ue] rated operational voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ui] rated insulation voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ith] conventional free air thermal current
              10 A conforming to IEC 60947-4-1
              [Uimp] rated impulse withstand voltage
              Power dissipation per pole
              2.5 W
              Mechanical durability
              100000 cycles
              Electrical durability
              100000 cycles for AC-3 at 440 V
              Maximum operating rate
              25 cyc/h
              Rated duty
              continuous conforming to IEC 60947-4-1
              Direct connector
              without
              Connections - terminals
            • screw clamp terminals 2 cable(s) 1-6 mm² solid
            • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
              • Tightening torque
                1.7 N.m on screw clamp terminals
                Suitability for isolation
                yes conforming to IEC 60947-1
                Height
                89 mm
                Width
                45 mm
                Depth
                78.5 mm
                Compatibility code
                GV2RT
                Standards
              • EN/IEC 60947-2
              • EN/IEC 60947-4-1
              • UL 60947-4-1
              • CSA C22.2 No 60947-4-1
                • Product certifications
                • IECEE CB Scheme
                • UL
                • CSA
                • CCC
                • EAC
                • BV
                • LROS (Lloyds register of shipping)
                  • Protective treatment
                    TH
                    IP degree of protection
                    IP20 conforming to IEC 60529
                    IK degree of protection
                    IK04
                    Ambient air temperature for operation
                    -20-60 °C
                    Ambient air temperature for storage
                    -40-80 °C
                    Fire resistance
                    960 °C conforming to IEC 60695-2-1
                    Operating altitude
                    2000 m
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Reference contains Substances of Very High Concern above the threshold
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP121004EN
                    Circularity Profile
                    N/A
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    California proposition 65
                    WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Movies

                    • Technical Data Catalogues

                    • Catalog Page

                    • Technical Leaflet

                    • Data Bulletin

                    • Installation Instruction

                    • Product Environmental

                    • Handout

                    • Operating Manuals

                    • Specification for Tender

                    • eTechPub

                    • White Paper

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    • Software - Released