Gv2 Motor CB High Inrush 0.63-1A Toggle

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth78.5 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

TeSys

Product or component type

circuit breaker

Device application

  • motor
  • transformer
    • Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Fixing mode

    • 35 mm symmetrical DIN rail: clipped
    • panel: screwed (with adaptor plate)
      • Control type

        toggle

        [In] rated current

        1 A

        [Ue] rated operational voltage

        690 V AC 50/60 Hz conforming to IEC 60947-2

        Mechanical durability

        100000 cycles

        Electrical durability

        100000 cycles for AC-3 at 440 V

        Connections - terminals

      • screw clamp terminals 2 cable(s) 1-6 mm² solid
      • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
      • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
        • Height

          89 mm

          Width

          45 mm

          Depth

          78.5 mm

          Standards

        • EN/IEC 60947-2
        • EN/IEC 60947-4-1
        • UL 60947-4-1
        • CSA C22.2 No 60947-4-1
          • Product certifications

          • IECEE CB Scheme
          • UL
          • CSA
          • CCC
          • EAC
          • BV
          • LROS (Lloyds register of shipping)
            • IP degree of protection

              IP20 conforming to IEC 60529

              IK degree of protection

              IK04

              Ambient air temperature for operation

              -20-60 °C

              Ambient air temperature for storage

              -40-80 °C

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP121004EN

              California proposition 65

              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov

              Others

              Product name

              TeSys GV2

              Device short name

              GV2RT

              Trip unit technology

              thermal-magnetic

              Poles description

              3P

              Network type

              AC

              Utilisation category

            • AC-3 conforming to IEC 60947-4-1
            • category A conforming to IEC 60947-2
              • Network frequency

                50/60 Hz conforming to IEC 60947-4-1

                Operating position

                any position

                Motor power kW

              • 0.09-0.09 kW at 220/230 V AC 50/60 Hz motor protection high peak current
              • 0.12-0.12 kW at 220/230 V AC 50/60 Hz motor protection high peak current
              • 0.25-0.25 kW at 400/415 V AC 50/60 Hz motor protection high peak current
              • 0.37-0.37 kW at 400/415 V AC 50/60 Hz motor protection high peak current
              • 0.25-0.25 kW at 440 V AC 50/60 Hz motor protection high peak current
              • 0.37-0.37 kW at 440 V AC 50/60 Hz motor protection high peak current
              • 0.37-0.37 kW at 500 V AC 50/60 Hz motor protection high peak current
              • 0.55-0.55 kW at 690 V AC 50/60 Hz motor protection high peak current
              • 0.63-0.63 kW at 440 V AC 50/60 Hz transformer protection
              • 0.63-0.63 kW at 500 V AC 50/60 Hz transformer protection
              • 1-1 kW at 690 V AC 50/60 Hz transformer protection
                • Breaking capacity

                • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
                • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
                • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
                • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
                • 100 kA Icu at 220/230 V AC 50/60 Hz conforming to IEC 60947-2
                  • Trip unit rating

                    0.63-1 A

                    Magnetic tripping current

                    22-22 A

                    [Ui] rated insulation voltage

                    690 V AC 50/60 Hz conforming to IEC 60947-2

                    [Ith] conventional free air thermal current

                    1 A conforming to IEC 60947-4-1

                    [Uimp] rated impulse withstand voltage

                    Power dissipation per pole

                    2.5 W

                    Maximum operating rate

                    25 cyc/h

                    Rated duty

                    continuous conforming to IEC 60947-4-1

                    Direct connector

                    without

                    Tightening torque

                    1.7 N.m on screw clamp terminals

                    Suitability for isolation

                    yes conforming to IEC 60947-1

                    Compatibility code

                    GV2RT

                    Protective treatment

                    TH

                    Fire resistance

                    960 °C conforming to IEC 60695-2-1

                    Operating altitude

                    2000 m

                    Unit Type of Package 1

                    PCE

                    Number of Units in Package 1

                    1

                    Package 1 Weight

                    226 g

                    Package 1 Height

                    4.8 cm

                    Package 1 width

                    8.7 cm

                    Package 1 Length

                    9.3 cm

                    Unit Type of Package 2

                    S02

                    Number of Units in Package 2

                    24

                    Package 2 Weight

                    5.762 kg

                    Package 2 Height

                    15 cm

                    Package 2 width

                    30 cm

                    Package 2 Length

                    40 cm

                    Unit Type of Package 3

                    P06

                    Number of Units in Package 3

                    384

                    Package 3 Weight

                    102.564 kg

                    Package 3 Height

                    80 cm

                    Package 3 width

                    80 cm

                    Package 3 Length

                    60 cm

                    WEEE

                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Show all specifications

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Product Environmental

                    • Installation Instruction

                    • Data Bulletin

                    • eTechPub

                    Frequently Asked Questions

                    hide show

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    Is a padlocking device available for the GV2MC** type enclosures?

                    Issue:
                    Padlocking device for GV2MC Enclosures

                    Product Line:
                    TeSys GV2 Manual Starters and Protectors

                    Environment:
                    n/a

                    Resolution:
                    Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                    Issue:
                    Mounting adaptor for GV2 and LC1D contactor

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    TeSys GV Manual Starter and Protectors
                    Tesys D Contactors
                     
                    Resolution:
                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                    Issue:
                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                    Product Line:
                    Contactors and Starters IEC

                    Environment:
                    Tesys D contactors and GV manual starters

                    Cause:
                    Spacer required

                    Resolution:
                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                    Are explosion proof enclosures available for GV manual motor starters.

                    Issue:
                    NEMA 7/9 rated enclosure for GV manual motor starters

                    Product Line:
                    Tesys GV Motor Starters and Protectors

                    Environment:
                    TeSys™ GV Manual Starters and Protectors

                    Resolution:
                    No hazardous duty enclosures are available for the GV product line.
                    For explosion proof applications consider the Class 2510 Type M or Type T offering.

                    GV2P disconnect options

                    Issue:
                    What is the product number for a complete through-the-door disconnect device for a GV2P

                    Product Line:
                    GV2P Manual Starters and Protectors

                    Environment:
                    US product

                    Cause:
                    Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                    Resolution:
                    There are three devices which include mechanism, shaft and handle:
                    GV2APN01 has a NEMA 1, 12 rating and is black
                    GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                    GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                    What is the equivalent of GV2AP01 and GV2AP02 rotary handle

                    The equivalent of GV2AP01 and GV2AP02 rotary handles are GV2APN01          
                     and GV2APN02 respectively.Refer attached file for more details

                    Protection Rating for GV2E01

                    Issue:
                    What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                    Product Line:
                    GV2 Enclosure Accessories

                    Environment:
                    US Product

                    Cause:
                    The IP rating is not specified in the Digest 176

                    Resolution:
                    When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                    What is the difference between the GV2MC01 and the GV2MC02 enclosures?

                    Product Line:
                     
                    GV Manual Motor Starters and Protectors
                     
                    Resolution:
                    The GV2MC01 has an IP41 rating ( similar to Nema Type 1 ), whereas the GV2MC02 has an IP55 rating (similar to the Nema Type 12 ).

                     

                    What does Pitch refer to in regards to the GV2G busbar system?

                    Issue: 
                    Need to know what 45mm, 54mm, and 72mm pitch means

                    Product Line:
                    GV2 Manual Starters

                    Environment:
                    n/a

                    Resolution:
                    The pitch is the spacing between slots.  In order to select the correct pitch, total up the width of the device, plus any side mounted auxiliaries.  Use the total width for selecting the proper pitch. The busbar pitch selection must be the same or greater than the sum of device and auxiliaries.

                    What is the tripping class of the GV2 ME, GV2 P and GV2 RT?

                    The tripping class for GV2MExx, GV2Pxx, GV2RTxx circuit-breakers is class 10. Class 10 corresponds to a direct on-line motor starting time between 4 and 10 sec. Example of a tripping curve:




                     

                    Which enclosures can the GV2E01 sealing kit be used on?

                    Issue:
                    Which enclosures can the GV2E01 sealing kit be used on?

                    Product Line:
                    IEC Manual Starters/Protectors - GIC Product

                    Environment:
                    US Product

                    Cause:
                    Product Application

                    Resolution:
                    GV2MC01 and GV2MP01.
                    Show More