Quantcast

TeSys GV2 Motor Circuit Breaker Thermal Magnetic, 20¦25 A

TeSys GV2 Motor Circuit Breaker Thermal Magnetic, 20¦25 A

TeSys GV2 Motor Circuit Breaker Thermal Magnetic, 20¦25 A

Item Number: GV2P22

Retail
$826.07
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth97 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

TeSys

Product or component type

circuit breaker

Device application

motor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Fixing mode

  • 35 mm symmetrical DIN rail: clipped
  • panel: screwed (with 2 x M4 screws)
    • Control type

      rotary knob

      [In] rated current

      25 A

      [Ue] rated operational voltage

      690 V AC 50/60 Hz conforming to IEC 60947-2

      Mechanical durability

      100000 cycles

      Electrical durability

      100000 cycles for AC-3 at 440 V

      Connections - terminals

    • screw clamp terminals 2 cable(s) 1-6 mm² solid
    • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
      • Height

        89 mm

        Width

        45 mm

        Depth

        97 mm

        Standards

      • EN/IEC 60947-2
      • EN/IEC 60947-4-1
      • UL 60947-4-1
      • CSA C22.2 No 60947-4-1
        • Product certifications

        • IECEE CB Scheme
        • UL
        • CSA
        • CCC
        • EAC
        • ATEX
        • BV
        • LROS (Lloyds register of shipping)
        • DNV-GL
        • RINA
          • IP degree of protection

            IP20 conforming to IEC 60529

            IK degree of protection

            IK04

            Ambient air temperature for operation

            -20-60 °C

            Ambient air temperature for storage

            -40-80 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            EU RoHS Directive

            Compliant

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            Product out of China RoHS scope. Substance declaration for your information

            Environmental Disclosure

            ENVPEP121004EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

            Others

            Number of Units in Package 1

            1

            Number of Units in Package 2

            20

            Number of Units in Package 3

            320

            Package 1 Height

            4.6 cm

            Package 1 Length

            10 cm

            Package 1 width

            9.3 cm

            Package 2 Height

            15 cm

            Package 2 Length

            40 cm

            Package 2 width

            30 cm

            Package 3 Height

            80 cm

            Package 3 Length

            60 cm

            Package 3 width

            80 cm

            Unit Type of Package 1

            PCE

            Unit Type of Package 2

            S02

            Unit Type of Package 3

            P06

            Product name

            TeSys GV2

            Device short name

            GV2P

            Trip unit technology

            thermal-magnetic

            Poles description

            3P

            Network type

            AC

            Utilisation category

          • AC-3 conforming to IEC 60947-4-1
          • category A conforming to IEC 60947-2
            • Network frequency

              50/60 Hz conforming to IEC 60947-4-1

              Operating position

              any position

              Motor power kW

            • 11-11 kW at 400/415 V AC 50/60 Hz
            • 15-15 kW at 500 V AC 50/60 Hz
              • Breaking capacity

              • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
              • 10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
              • 4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
              • 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
              • 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
                • [Ics] rated service short-circuit breaking capacity

                • 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
                • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
                • 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
                • 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
                • 75 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
                  • Trip unit rating

                    20-25 A

                    Magnetic tripping current

                    327-327 A

                    [Ui] rated insulation voltage

                    690 V AC 50/60 Hz conforming to IEC 60947-2

                    [Ith] conventional free air thermal current

                    25 A conforming to IEC 60947-4-1

                    [Uimp] rated impulse withstand voltage

                    Power dissipation per pole

                    2.5 W

                    Maximum operating rate

                    25 cyc/h

                    Rated duty

                    continuous conforming to IEC 60947-4-1

                    Direct connector

                    without

                    Tightening torque

                    1.7 N.m on screw clamp terminals

                    Suitability for isolation

                    yes conforming to IEC 60947-1

                    Phase failure sensitivity

                    yes conforming to IEC 60947-4-1

                    Compatibility code

                    GV2P

                    Protective treatment

                    TH

                    Fire resistance

                    960 °C conforming to IEC 60695-2-1

                    Operating altitude

                    2000 m

                    Package 1 Weight

                    339 g

                    Package 2 Weight

                    7.106 kg

                    Package 3 Weight

                    124.26 kg

                    WEEE

                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Show all specifications

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Technical Data Catalogues

                    • Installation Instruction

                    • Product Environmental

                    • Data Bulletin

                    • Certificates (MSDS)

                    • Declaration of Conformity

                    • eTechPub

                    Frequently Asked Questions

                    hide show

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                    Issue:
                    Mounting adaptor for GV2 and LC1D contactor

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    TeSys GV Manual Starter and Protectors
                    Tesys D Contactors
                     
                    Resolution:
                    The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                    Are explosion proof enclosures available for GV manual motor starters.

                    Issue:
                    NEMA 7/9 rated enclosure for GV manual motor starters

                    Product Line:
                    Tesys GV Motor Starters and Protectors

                    Environment:
                    TeSys™ GV Manual Starters and Protectors

                    Resolution:
                    No hazardous duty enclosures are available for the GV product line.
                    For explosion proof applications consider the Class 2510 Type M or Type T offering.

                    Does the GV2P22 have a rotary handle

                     Yes it does.

                    What options can I use if the LS1D32 is not available

                    You can use GV2P32 & GV3P32

                    What items does the GV2PC02 enclosure suit?

                    The GV2PC02 is for GV2P and GV2L, 0.55 to 15kW.

                    Show More