Quantcast

TeSys GV2 Circuit Breaker Thermal Magnetic, 20...25 A, Screw Clamp Terminals

TeSys GV2 Circuit Breaker Thermal Magnetic, 20...25 A, Screw Clamp Terminals

TeSys GV2 Circuit Breaker Thermal Magnetic, 20...25 A, Screw Clamp Terminals

Item Number: GV2ME22

Datasheet

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth78.5 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys Deca

Range of product

TeSys GV2

Product or component type

motor circuit breaker

Device application

motor protection

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Fixing mode

  • 35 mm symmetrical DIN rail: clipped
  • panel: screwed (with adaptor plate)

Control type

push-button

[In] rated current

25 A

[Ue] rated operational voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability

100000 cycles

Electrical durability

  • 100000 cycles for AC-3 at 415 V
  • at 415 V

Height

89 mm

Width

45 mm

Depth

78.5 mm

Net weight

0.26 kg

Standards

  • EN/IEC 60947-2
  • EN/IEC 60947-4-1

Product certifications

  • CCC
  • UL
  • CSA
  • EAC
  • ATEX
  • BV
  • LROS (Lloyds register of shipping)
  • UKCA
  • DNV-GL
  • RINA

Climatic withstand

conforming to IACS E10

IK degree of protection

IK04

IP degree of protection

IP20 conforming to IEC 60529

Ambient air temperature for storage

-40...80 °C

Ambient air temperature for operation

-20...60 °C

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive

Compliant

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Environmental Disclosure

ENVPEP121004EN

Circularity Profile

ENVEOLI121004EN

California proposition 65

WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

Others

Device short name

GV2ME

Product name

  • TeSys GV2
  • TeSys Deca

Trip unit technology

thermal-magnetic

Poles description

3P

Network type

AC

Utilisation category

  • AC-3 conforming to IEC 60947-4-1
  • category A conforming to IEC 60947-2

Network frequency

50/60 Hz conforming to IEC 60947-4-1

Operating position

any position

Motor power kW

  • 11 kW at 400/415 V AC 50/60 Hz
  • 15 kW at 500 V AC 50/60 Hz

Breaking capacity

  • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 6 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 4 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service short-circuit breaking capacity

  • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
  • 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 40 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

Trip unit rating

20...25 A

Magnetic tripping current

327 A

[Ui] rated insulation voltage

690 V AC 50/60 Hz conforming to IEC 60947-2

[Ith] conventional free air thermal current

25 A conforming to IEC 60947-4-1

[Uimp] rated impulse withstand voltage

6 kV conforming to IEC 60947-2

Power dissipation per pole

2.5 W

Maximum operating rate

25 cyc/h

Rated duty

continuous conforming to IEC 60947-4-1

Direct connector

without

Tightening torque

1.7 N.m on screw clamp terminals

Mechanical robustness

  • shocks: 30 Gn conforming to IEC 60068-2-27
  • vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6

Phase failure sensitivity

yes conforming to IEC 60947-4-1

Compatibility code

GV2ME

Suitability for isolation

yes conforming to IEC 60947-1 § 7-1-6

Fire resistance

960 °C conforming to IEC 60695-2-11

Operating altitude

2000 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

287.0 g

Package 1 Height

4.5 cm

Package 1 width

8.5 cm

Package 1 Length

9.5 cm

Unit Type of Package 2

S02

Number of Units in Package 2

24

Package 2 Weight

7.129 kg

Package 2 Height

15.0 cm

Package 2 width

30.0 cm

Package 2 Length

40.0 cm

Unit Type of Package 3

P06

Number of Units in Package 3

384

Package 3 Weight

122.064 kg

Package 3 Height

75.0 cm

Package 3 width

80.0 cm

Package 3 Length

60.0 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Data Bulletin

  • Installation Instruction

  • Product Environmental

  • Operating Manuals

  • Technical Drawing

  • Declaration of Conformity

  • eTechPub

  • Certificates (MSDS)

Frequently Asked Questions

hide show

Can the GV* starters be used on 50 hertz applications?

Issue:
GV* Starter for 50/60hz application

Product Line:
Motor Starters and Protectors

Environment:
PowerPact™ Manual Starters

Resolution:
Yes, these starters are rated for 50/60 hertz.

This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.