MASTER YOUR CASTLE with your new build or reno project
Enter competition
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys motor circuit breaker GV2-ME
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys motor circuit breaker GV2-ME

GV2ME08

TeSys GV2 Circuit Breaker Thermal Magnetic, 2.5...4 A, Screw Clamp Terminals

Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys motor circuit breaker GV2-ME
Thermal-magnetic motor circuit-breakers TeSys GV2ME  screw clamp terminals or lugs
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys GV2-Circuit breaker-thermal-magnetic - 2.5...4 A - screw clamp terminals
TeSys motor circuit breaker GV2-ME
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
TeSys GV2
Range
TeSys
Product name
TeSys GV2
Device short name
GV2ME
Product or component type
circuit breaker
Device application
motor
Trip unit technology
thermal-magnetic
Poles description
3P
Network type
AC
Utilisation category
  • AC-3 conforming to IEC 60947-4-1
  • category A conforming to IEC 60947-2
    • Network frequency
      50/60 Hz conforming to IEC 60947-4-1
      Fixing mode
    • 35 mm symmetrical DIN rail: clipped
    • panel: screwed (with adaptor plate)
      • Operating position
        any position
        Motor power kW
      • 1.1-1.1 kW at 400/415 V AC 50/60 Hz
      • 1.5-1.5 kW at 400/415 V AC 50/60 Hz
      • 1.5-1.5 kW at 500 V AC 50/60 Hz
      • 3-3 kW at 690 V AC 50/60 Hz
      • 2.2-2.2 kW at 500 V AC 50/60 Hz
      • 2.2-2.2 kW at 690 V AC 50/60 Hz
        • Breaking capacity
        • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
        • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
        • 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
          • [Ics] rated service short-circuit breaking capacity
          • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
          • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
          • 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
            • Control type
              push-button
              [In] rated current
              4 A
              Trip unit rating
              2.5-4 A
              Magnetic tripping current
              51-51 A
              [Ue] rated operational voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ui] rated insulation voltage
              690 V AC 50/60 Hz conforming to IEC 60947-2
              [Ith] conventional free air thermal current
              4 A conforming to IEC 60947-4-1
              [Uimp] rated impulse withstand voltage
              N/A
              Power dissipation per pole
              2.5 W
              Mechanical durability
              100000 cycles
              Electrical durability
              100000 cycles for AC-3 at 440 V
              Maximum operating rate
              25 cyc/h
              Rated duty
              continuous conforming to IEC 60947-4-1
              Direct connector
              without
              Connections - terminals
            • screw clamp terminals 2 cable(s) 1-6 mm² solid
            • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
              • Tightening torque
                1.7 N.m on screw clamp terminals
                Suitability for isolation
                yes conforming to IEC 60947-1
                Phase failure sensitivity
                yes conforming to IEC 60947-4-1
                Height
                89 mm
                Width
                45 mm
                Depth
                78.5 mm
                Net weight
                0.26 kg
                Compatibility code
                GV2ME
                Standards
              • EN/IEC 60947-2
              • EN/IEC 60947-4-1
              • CSA C22.2 No 60947-4-1
              • UL 60947-4-1
                • Product certifications
                • IECEE CB Scheme
                • UL
                • CSA
                • CCC
                • EAC
                • ATEX
                • BV
                • LROS (Lloyds register of shipping)
                • DNV-GL
                • RINA
                  • Protective treatment
                    TH
                    IP degree of protection
                    IP20 conforming to IEC 60529
                    IK degree of protection
                    IK04
                    Ambient air temperature for operation
                    -20-60 °C
                    Ambient air temperature for storage
                    -40-80 °C
                    Fire resistance
                    960 °C conforming to IEC 60695-2-1
                    Operating altitude
                    2000 m
                    Sustainable offer status
                    Green Premium product
                    REACh Regulation
                    Reference contains Substances of Very High Concern above the threshold
                    EU RoHS Directive
                    Compliant
                    Mercury free
                    Yes
                    RoHS exemption information
                    Yes
                    China RoHS Regulation
                    Product out of China RoHS scope. Substance declaration for your information
                    Environmental Disclosure
                    ENVPEP121004EN
                    Circularity Profile
                    N/A
                    WEEE
                    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                    Warranty
                    18 months

                    Documents & downloads

                    hide show
                    Filter items
                    • All

                    • CAD Files and Packs

                    • Product Brochures

                    • Movies

                    • Technical Data Catalogues

                    • Catalog Page

                    • Technical Leaflet

                    • Installation Instruction

                    • Data Bulletin

                    • Product Environmental

                    • Handout

                    • Operating Manuals

                    • Specification for Tender

                    • Certificates (MSDS)

                    • eTechPub

                    • White Paper

                    • Declaration of Conformity

                    • Software - Released

                    Frequently Asked Questions

                    hide show

                    What is the part number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B ,GV2ME08?

                    The part  number for a left side mount contact block with 1 N/C & 1 N/O contacts to go with motor start C/B , GV2ME08 is - GVAN11
                    For further information , visit link below:-
                    https://www.schneider-electric.com.au/en/search/GVAN11
                    User-added image

                    Can the GV* starters be used on 50 hertz applications?

                    Issue:
                    GV* Starter for 50/60hz application

                    Product Line:
                    Motor Starters and Protectors

                    Environment:
                    PowerPact™ Manual Starters

                    Resolution:
                    Yes, these starters are rated for 50/60 hertz.

                    This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                    What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                    Issue:
                    Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                    Product Line:
                    Digest 177 Section 18 : Contactors and Starters IEC

                    Environment:
                    Products sold and used in the United States

                    Cause:
                    Spacer required

                    Resolution:
                    Compensation plate catalog number GV1F03, requires 2 pieces snap together.