Range of product
TeSys GV2
Product or component type
circuit breaker
Utilisation category
category A conforming to IEC 60947-2AC-3 conforming to IEC 60947-4-1
Network frequency
50/60 Hz conforming to IEC 60947-2
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity
100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit technology
magnetic
Magnetic tripping current
22.5-22.5 A
Fixing mode
35 mm symmetrical DIN rail: clippedpanel: screwed (with adaptor plate)
Operating position
any position
Motor power kW
0.55-0.55 kW at 400/415 V AC 50/60 Hz0.55-0.55 kW at 500 V AC 50/60 Hz0.75-0.75 kW at 500 V AC 50/60 Hz1.1-1.1 kW at 690 V AC 50/60 Hz
[Ue] rated operational voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] rated insulation voltage
690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage
Power dissipation per pole
1.8 W
Mechanical durability
100000 cycles
Electrical durability
100000 cycles for AC-3 at 415 V
Maximum operating rate
40 cyc/h
Rated duty
continuous conforming to IEC 60947-4-1
Connections - terminals
screw clamp terminals 2 cable(s) 1-6 mm² solidscrew clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable endscrew clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
Tightening torque
1.7 N.m on screw clamp terminals
Mechanical robustness
shocks: 30 Gn conforming to IEC 60068-2-27vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
Suitability for isolation
yes conforming to IEC 60947-1
Standards
EN/IEC 60947-2EN/IEC 60947-4-1CSA C22.2 No 60947-4-1UL 60947-4-1
Product certifications
IECEE CB SchemeULCSACCCEACRINALROS (Lloyds register of shipping)DNV-GLBV
IP degree of protection
IP20 conforming to IEC 60529
IK degree of protection
IK04
Ambient air temperature for operation
-20-60 °C
Ambient air temperature for storage
-40-80 °C
Fire resistance
960 °C conforming to IEC 60695-2-1
Operating altitude
0...2000 m
Sustainable offer status
Green Premium product
REACh Regulation
Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive
Compliant
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP121004EN
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
California proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov