Quantcast

Magnetic Circuit Breaker

Product Dimensions

Width icon

Width45 mm

Height icon

Height89 mm

Depth icon

Depth97 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

TeSys

Product or component type

circuit breaker

Device application

motor

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Fixing mode

  • 35 mm symmetrical DIN rail: clipped
  • panel: screwed (with 2 x M4 screws)
    • Control type

      rotary knob

      [In] rated current

      0.63 A

      [Ue] rated operational voltage

      690 V AC 50/60 Hz conforming to IEC 60947-2

      Mechanical durability

      100000 cycles

      Electrical durability

      100000 cycles for AC-3 at 415 V

      Connections - terminals

    • screw clamp terminals 2 cable(s) 1-6 mm² solid
    • screw clamp terminals 2 cable(s) 1.5-6 mm² flexible without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm² flexible with cable end
      • Height

        89 mm

        Width

        45 mm

        Depth

        97 mm

        Net weight

        0.33 kg

        Standards

      • EN/IEC 60947-2
      • EN/IEC 60947-4-1
      • CSA C22.2 No 60947-4-1
      • UL 60947-4-1
        • Product certifications

        • IECEE CB Scheme
        • UL
        • CSA
        • CCC
        • EAC
        • RINA
        • LROS (Lloyds register of shipping)
        • DNV-GL
        • BV
          • IP degree of protection

            IP20 conforming to IEC 60529

            IK degree of protection

            IK04

            Ambient air temperature for operation

            -20-60 °C

            Ambient air temperature for storage

            -40-80 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            EU RoHS Directive

            Compliant

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

            Product out of China RoHS scope. Substance declaration for your information

            Environmental Disclosure

            ENVPEP121004EN

            Others

            Product name

            TeSys GV2

            Device short name

            GV2L

            Poles description

            3P

            Network type

            AC

            Utilisation category

          • category A conforming to IEC 60947-2
          • AC-3 conforming to IEC 60947-4-1
            • Network frequency

              50/60 Hz conforming to IEC 60947-2

              Breaking capacity

            • 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
            • 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
            • 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
            • 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
            • 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
              • [Ics] rated service short-circuit breaking capacity

              • 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
              • 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
              • 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
              • 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
              • 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
                • Trip unit technology

                  magnetic

                  Magnetic tripping current

                  8-8 A

                  Operating position

                  any position

                  Motor power kW

                • 0.12-0.12 kW at 400/415 V AC 50/60 Hz
                • 0.18-0.18 kW at 400/415 V AC 50/60 Hz
                • 0.37-0.37 kW at 690 V AC 50/60 Hz
                  • [Ui] rated insulation voltage

                    690 V AC 50/60 Hz conforming to IEC 60947-2

                    [Uimp] rated impulse withstand voltage

                    Power dissipation per pole

                    1.8 W

                    Maximum operating rate

                    40 cyc/h

                    Rated duty

                    continuous conforming to IEC 60947-4-1

                    Direct connector

                    without

                    Tightening torque

                    1.7 N.m on screw clamp terminals

                    Mechanical robustness

                  • shocks: 30 Gn conforming to IEC 60068-2-27
                  • vibrations: 5 Gn, 5...150 Hz conforming to IEC 60068-2-6
                    • Suitability for isolation

                      yes conforming to IEC 60947-1

                      Compatibility code

                      GV2L

                      Protective treatment

                      TH

                      Fire resistance

                      960 °C conforming to IEC 60695-2-1

                      Operating altitude

                      0...2000 m

                      Unit Type of Package 1

                      PCE

                      Number of Units in Package 1

                      1

                      Package 1 Weight

                      265 g

                      Package 1 Height

                      4.8 cm

                      Package 1 width

                      9.3 cm

                      Package 1 Length

                      10 cm

                      WEEE

                      The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                      Show all specifications

                      Documents & downloads

                      hide show
                      Filter items
                      • All

                      • CAD Files and Packs

                      • Product Brochures

                      • Technical Data Catalogues

                      • Installation Instruction

                      • Product Environmental

                      • Data Bulletin

                      • Certificates (MSDS)

                      • eTechPub

                      Frequently Asked Questions

                      hide show

                      Can the GV* starters be used on 50 hertz applications?

                      Issue:
                      GV* Starter for 50/60hz application

                      Product Line:
                      Motor Starters and Protectors

                      Environment:
                      PowerPact™ Manual Starters

                      Resolution:
                      Yes, these starters are rated for 50/60 hertz.

                      This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                      Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                      Issue:
                      Mounting adaptor for GV2 and LC1D contactor

                      Product Line:
                      Motor Starters and Protectors

                      Environment:
                      TeSys GV Manual Starter and Protectors
                      Tesys D Contactors
                       
                      Resolution:
                      The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                      GV2P disconnect options

                      Issue:
                      What is the product number for a complete through-the-door disconnect device for a GV2P

                      Product Line:
                      GV2P Manual Starters and Protectors

                      Environment:
                      US product

                      Cause:
                      Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                      Resolution:
                      There are three devices which include mechanism, shaft and handle:
                      GV2APN01 has a NEMA 1, 12 rating and is black
                      GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                      GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                      Are explosion proof enclosures available for GV manual motor starters.

                      Issue:
                      NEMA 7/9 rated enclosure for GV manual motor starters

                      Product Line:
                      Tesys GV Motor Starters and Protectors

                      Environment:
                      TeSys™ GV Manual Starters and Protectors

                      Resolution:
                      No hazardous duty enclosures are available for the GV product line.
                      For explosion proof applications consider the Class 2510 Type M or Type T offering.

                      Is a padlocking device available for the GV2MC** type enclosures?

                      Issue:
                      Padlocking device for GV2MC Enclosures

                      Product Line:
                      TeSys GV2 Manual Starters and Protectors

                      Environment:
                      n/a

                      Resolution:
                      Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                      Will the Tesys GV2ME starters install into old style enclosures designed for the GV2M, GV2MC01 and GV2MC02 enclosures?

                      Issue:
                      GV2ME compatibility with old enclosure 

                      Product Line:

                      Motor Starters and Protectors

                      Environment:
                      TeSys™ GV Manual Starters and Protectors
                       
                      Resolution:
                      No, Order new enclosures using the same catalog numbers. The current enclosure has an updated DIN attachement which will accept the Tesys GV2ME starters but will not accept the old GV2M starters.
                      Show More