2 Tap Offs Busbar Gv2 63A 54mm Pitch

2 Tap Offs Busbar Gv2 63A 54mm Pitch

2 Tap Offs Busbar Gv2 63A 54mm Pitch

Item Number: GV2G254

Retail
$127.00
RRP (Inc. GST)

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

  • TeSys U
  • TeSys D
  • TeSys GV2
  • TeSys fuse-disconnector
  • TeSys K
    • Range

      Linergy

      Product or component type

      comb busbar

      Sustainable offer status

      Green Premium product

      Warranty

      18 months

      Physical

      Range compatibility

    • TeSys D
    • TeSys GV2
    • TeSys K
    • TeSys U
      • Length

        98 mm

        Net weight

        0.038 kg

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Compliant

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        X

        Environmental Disclosure

        ENVPEP111252EN

        Others

        Product name

        FT

        Device short name

        GV2G

        Accessory / separate part category

        connection accessory

        Poles description

        3P

        Number of tap-offs

        2

        [Ith] conventional free air thermal current

        63 A

        Connection pitch

        54 mm

        Mounting location

        on terminal

        [Ui] rated insulation voltage

        690 V

        Compatibility code

        GV2G

        Package 1 Weight

        0.04 kg

        Package 1 Height

        0.11 dm

        Package 1 width

        1.05 dm

        Package 1 Length

        0.35 dm
        Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • CAD Files and Packs

        • Product Brochures

        • Technical Data Catalogues

        • Product Environmental

        • Installation Instruction

        • Data Bulletin

        • Declaration of Conformity

        • eTechPub

        Frequently Asked Questions

        hide show

        What does Pitch refer to in regards to the GV2G busbar system?

        Issue: 
        Need to know what 45mm, 54mm, and 72mm pitch means

        Product Line:
        GV2 Manual Starters

        Environment:
        n/a

        Resolution:
        The pitch is the spacing between slots.  In order to select the correct pitch, total up the width of the device, plus any side mounted auxiliaries.  Use the total width for selecting the proper pitch. The busbar pitch selection must be the same or greater than the sum of device and auxiliaries.

        What is the short circuit current rating for TeSys GV2G Comb Busbar.

        The short-circuit current withstand rating (KA) of Tesys Comb Busbar is compatible with the breaking capacity of Motor Protection Circuit Breakers (MPCB) of GV series. The GV Series Comb Busbar does not have a conditional short-circuit current rating.

        The maximum permissible peak current for GV2G*** Series Comb Busbar is 11KA and for GV3G*64 series Comb Busbar is 20KA.

        Example: Use a circuit breaker or fuse in upstream of the Tesys GV2G for a short circuit value up to 11KAmps as the permissible peak current of GV2G354 is 11KA.

        What is the current rating of the GV1G02?

        Issue:
        GV1G02 electrical ratings

        Product Line:
        GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection

        Environment:
        Additional GV2 Wiring Accessories

        Resolution:
        25 amp maximum

        GV2P disconnect options

        Issue:
        What is the product number for a complete through-the-door disconnect device for a GV2P

        Product Line:
        GV2P Manual Starters and Protectors

        Environment:
        US product

        Cause:
        Digest 176 is unclear as to what is a complete mechanism with shaft and handle

        Resolution:
        There are three devices which include mechanism, shaft and handle:
        GV2APN01 has a NEMA 1, 12 rating and is black
        GV2APN02 has a NEMA 1, 12 rating and is red/yellow
        GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

        What is the part number for the 3 tap off comb for the GV3

         The part code is GV3G364

        Protection Rating for GV2E01

        Issue:
        What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

        Product Line:
        GV2 Enclosure Accessories

        Environment:
        US Product

        Cause:
        The IP rating is not specified in the Digest 176

        Resolution:
        When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

        What is the part number for the top mount auxiliary for a GV2L22?

        The part number for the Top mount auxiliary for the GV2 range is the GVAE1....
        This can be a N/O or N/C depending on orientation
        https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=gvae1

        User-added image

        Can the GV* starters be used on 50 hertz applications?

        Issue:
        GV* Starter for 50/60hz application

        Product Line:
        Motor Starters and Protectors

        Environment:
        PowerPact™ Manual Starters

        Resolution:
        Yes, these starters are rated for 50/60 hertz.

        This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

        Issue:
        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

        Product Line:
        Contactors and Starters IEC

        Environment:
        Tesys D contactors and GV manual starters

        Cause:
        Spacer required

        Resolution:
        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

        Is a padlocking device available for the GV2MC** type enclosures?

        Issue:
        Padlocking device for GV2MC Enclosures

        Product Line:
        TeSys GV2 Manual Starters and Protectors

        Environment:
        n/a

        Resolution:
        Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

        Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

        Issue:
        Mounting adaptor for GV2 and LC1D contactor

        Product Line:
        Motor Starters and Protectors

        Environment:
        TeSys GV Manual Starter and Protectors
        Tesys D Contactors
         
        Resolution:
        The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

        Are explosion proof enclosures available for GV manual motor starters.

        Issue:
        NEMA 7/9 rated enclosure for GV manual motor starters

        Product Line:
        Tesys GV Motor Starters and Protectors

        Environment:
        TeSys™ GV Manual Starters and Protectors

        Resolution:
        No hazardous duty enclosures are available for the GV product line.
        For explosion proof applications consider the Class 2510 Type M or Type T offering.
        Show More