TERMINAL BLOCK FOR GV1 L3

Terminal Block For Gv1 L3

Catalogue Number: GV2G05
TERMINAL BLOCK FOR GV1 L3
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
  • TeSys D
  • TeSys U
  • TeSys K
  • TeSys GV2
    • Range
      Linergy
      Product name
      FT
      Device short name
      GV2G
      Product or component type
      terminal block
      Accessory / separate part category
      connection accessory
      Poles description
      3P
      Range compatibility
    • TeSys GV2
    • TeSys D
    • TeSys K
    • TeSys U
      • [Ie] rated operational current
        63 A
        Mounting location
        top
        IP degree of protection
        IP20 conforming to IEC 60529
        [Ui] rated insulation voltage
        690 V conforming to IEC 60947-1
        Connections - terminals
      • screw clamp terminals 1 solid AWG 4
      • screw clamp terminals 1 cable(s) 1.5-16 mm² flexible with cable end
      • screw clamp terminals 1 cable(s) 1.5-16 mm² flexible without cable end
      • screw clamp terminals 1 cable(s) 1.5-25 mm² solid
      • screw clamp terminals 2 cable(s) 1.5-4 mm² flexible with cable end
      • screw clamp terminals 2 cable(s) 1.5-6 mm² solid
      • screw clamp terminals 2 cable(s) 2.5-4 mm² flexible without cable end
      • screw clamp terminals 1 flexible AWG 4
        • Tightening torque
        • 1.7-1.7 N.m - on screw clamp terminals
        • 2.2-2.2 N.m - on connector
          • Net weight
            0.115 kg
            Compatibility code
            GV2G
            Sustainable offer status
            Green Premium product
            REACh Regulation
            Free of Substances of Very High Concern above the threshold
            REACh free of SVHC
            Yes
            EU RoHS Directive
            Compliant
            Toxic heavy metal free
            Yes
            Mercury free
            Yes
            RoHS exemption information
            Yes
            China RoHS Regulation
             Pro-active China RoHS declaration (out of China RoHS legal scope)
            Environmental Disclosure
            ENVPEP111252EN
            Warranty
            18 months

            Documents & downloads

            hide show
            Filter items
            • All

            • CAD Files and Packs

            • Product Brochures

            • Technical Data Catalogues

            • Product Environmental

            • Installation Instruction

            • Data Bulletin

            • eTechPub

            Frequently Asked Questions

            hide show

            Can the GV* starters be used on 50 hertz applications?

            Issue:
            GV* Starter for 50/60hz application

            Product Line:
            Motor Starters and Protectors

            Environment:
            PowerPact™ Manual Starters

            Resolution:
            Yes, these starters are rated for 50/60 hertz.

            This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

            Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

            Issue:
            Mounting adaptor for GV2 and LC1D contactor

            Product Line:
            Motor Starters and Protectors

            Environment:
            TeSys GV Manual Starter and Protectors
            Tesys D Contactors
             
            Resolution:
            The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

            GV2P disconnect options

            Issue:
            What is the product number for a complete through-the-door disconnect device for a GV2P

            Product Line:
            GV2P Manual Starters and Protectors

            Environment:
            US product

            Cause:
            Digest 176 is unclear as to what is a complete mechanism with shaft and handle

            Resolution:
            There are three devices which include mechanism, shaft and handle:
            GV2APN01 has a NEMA 1, 12 rating and is black
            GV2APN02 has a NEMA 1, 12 rating and is red/yellow
            GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

            What does Pitch refer to in regards to the GV2G busbar system?

            Issue: 
            Need to know what 45mm, 54mm, and 72mm pitch means

            Product Line:
            GV2 Manual Starters

            Environment:
            n/a

            Resolution:
            The pitch is the spacing between slots.  In order to select the correct pitch, total up the width of the device, plus any side mounted auxiliaries.  Use the total width for selecting the proper pitch. The busbar pitch selection must be the same or greater than the sum of device and auxiliaries.

            Are explosion proof enclosures available for GV manual motor starters.

            Issue:
            NEMA 7/9 rated enclosure for GV manual motor starters

            Product Line:
            Tesys GV Motor Starters and Protectors

            Environment:
            TeSys™ GV Manual Starters and Protectors

            Resolution:
            No hazardous duty enclosures are available for the GV product line.
            For explosion proof applications consider the Class 2510 Type M or Type T offering.

            Is a padlocking device available for the GV2MC** type enclosures?

            Issue:
            Padlocking device for GV2MC Enclosures

            Product Line:
            TeSys GV2 Manual Starters and Protectors

            Environment:
            n/a

            Resolution:
            Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

            What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

            Issue:
            Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

            Product Line:
            Contactors and Starters IEC

            Environment:
            Tesys D contactors and GV manual starters

            Cause:
            Spacer required

            Resolution:
            Compensation plate catalog number GV1F03, requires 2 pieces snap together.

            Can I get the front membrane for a GV2MC03

             The part code is a GV2E02

            What is the current rating of the GV1G02?

            Issue:
            GV1G02 electrical ratings

            Product Line:
            GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection

            Environment:
            Additional GV2 Wiring Accessories

            Resolution:
            25 amp maximum

            What is the replacement for a GV2M06

            Use a GV2ME06.

            Which enclosures can the GV2E01 sealing kit be used on?

            Issue:
            Which enclosures can the GV2E01 sealing kit be used on?

            Product Line:
            IEC Manual Starters/Protectors - GIC Product

            Environment:
            US Product

            Cause:
            Product Application

            Resolution:
            GV2MC01 and GV2MP01.

            Protection Rating for GV2E01

            Issue:
            What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

            Product Line:
            GV2 Enclosure Accessories

            Environment:
            US Product

            Cause:
            The IP rating is not specified in the Digest 176

            Resolution:
            When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

            Show More