Enclosure Adaptor

Product Dimensions

Width icon

Width35 mm

Height icon

Height39 mm

Depth icon

Depth13 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys GV2

Range

TeSys

Product or component type

compensation plate

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Height

39 mm

Width

35 mm

Depth

13 mm

Net weight

0.003 kg

Quantity per set

set of 10

REACh free of SVHC

Yes

EU RoHS Directive

Compliant

Toxic heavy metal free

Yes

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP111252EN

Others

Device short name

GV1F

Accessory / separate part category

mounting accessory

Compatibility code

GV1F

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Weight

6 g

Package 1 Height

5 cm

Package 1 width

8 cm

Package 1 Length

9 cm

Unit Type of Package 2

BAG

Number of Units in Package 2

10

Package 2 Weight

62 g

Package 2 Height

9 cm

Package 2 width

5 cm

Package 2 Length

8 cm

Unit Type of Package 3

BB1

Number of Units in Package 3

10

Package 3 Weight

60 g

Package 3 Height

5 cm

Package 3 width

6.6 cm

Package 3 Length

12.9 cm

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Technical Data Catalogues

  • Product Environmental

  • eTechPub

Frequently Asked Questions

hide show

What is the replacement for GV1M07 Motor CB?

The replacement for GV1M07 Motor CB is a - GV2ME07
 

What is the current rating of the GV1G02?

Issue:
GV1G02 electrical ratings

Product Line:
GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Selection

Environment:
Additional GV2 Wiring Accessories

Resolution:
25 amp maximum

What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

Issue:
Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

Product Line:
Contactors and Starters IEC

Environment:
Tesys D contactors and GV manual starters

Cause:
Spacer required

Resolution:
Compensation plate catalog number GV1F03, requires 2 pieces snap together.

Can the GV* starters be used on 50 hertz applications?

Issue:
GV* Starter for 50/60hz application

Product Line:
Motor Starters and Protectors

Environment:
PowerPact™ Manual Starters

Resolution:
Yes, these starters are rated for 50/60 hertz.

This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

What is the replacement for the GV1M06?

GV2ME06 is the replacement range.

Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

Issue:
Mounting adaptor for GV2 and LC1D contactor

Product Line:
Motor Starters and Protectors

Environment:
TeSys GV Manual Starter and Protectors
Tesys D Contactors
 
Resolution:
The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

What is the hole size of the padlock provision for a GV2P starter?

ISSUE
What is the hole size of the padlock provision for a GV2P starter?

PRODUCT LINE
Integral starters

ENVIRONMENT
UL508E IEC starter

CAUSE
Fit

RESOLUTION
The padlock hole size is approximately 6mm on the GV2P starter. There are provisions for one padlock only. However, they can add a GV2V03 padlock attachment that will allow up to 6 padlocks for Lock out TAG out applications.

Is it possible to use the current Limiter LA9LB920 or GV1L3 with Tesys GV3 range of MPCB to increase the breaking capacity.

LA9LB920 and GV1L3 current limiter are dedicated to Tesys GV2 Motor Protection Circuit Breaker (MPCB) product range and can be used with MPCB rated up to 32A (maximum current range of Tesys GV2 products).
 
The new Tesys GV3 range does not have current limiter to increase its breaking capacity.
 
If higher breaking capacity for Tesys GV3 is needed, use in association with fuses can increase the breaking capacity of the system up to the fuse performance breaking capacity.

TCSEGDB23F24FA M340 Modbus Plus Proxy Exec v1.03 Release Notes

Release Notice

This Resolution contains the Release Notes for the TCSEGDB23F24FA M340 Modbus Plus Proxy Exec firmware version 1.03.

Goals and Symptoms

The attached document describes the Issues, Results, and Customer Actions of the changes to Exec version 1.03.

Facts and Changes

PRODUCTS Affected:

  • TCSEGDB23F24FA

Causes and Fixes

Refer to the attached document for the complete details.

Attachments

TCSEGDB23F24FA Modbus Plus Proxy Exec v1.03 Release Notes.pdf

(Removed File URL: 202634_F002/TCSEGDB23F24FA_Modbus_Plus_Proxy_Exec_v1.03_Release_Notes.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/69c1186fd0a314b5c12577440052b395/fl_block_5/0.75C?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL202634 V2.0, Originally authored by DaDz on 06/16/2010, Last Edited by DaDz on 06/16/2010
Related ranges: Modicon M340, Modbus Plus

Is a padlocking device available for the GV2MC** type enclosures?

Issue:
Padlocking device for GV2MC Enclosures

Product Line:
TeSys GV2 Manual Starters and Protectors

Environment:
n/a

Resolution:
Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

GV2P disconnect options

Issue:
What is the product number for a complete through-the-door disconnect device for a GV2P

Product Line:
GV2P Manual Starters and Protectors

Environment:
US product

Cause:
Digest 176 is unclear as to what is a complete mechanism with shaft and handle

Resolution:
There are three devices which include mechanism, shaft and handle:
GV2APN01 has a NEMA 1, 12 rating and is black
GV2APN02 has a NEMA 1, 12 rating and is red/yellow
GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

Are explosion proof enclosures available for GV manual motor starters.

Issue:
NEMA 7/9 rated enclosure for GV manual motor starters

Product Line:
Tesys GV Motor Starters and Protectors

Environment:
TeSys™ GV Manual Starters and Protectors

Resolution:
No hazardous duty enclosures are available for the GV product line.
For explosion proof applications consider the Class 2510 Type M or Type T offering.
Show More