Specifications

hide show
Range
TeSys
Product name
TeSys GB2
Device short name
GB2
Product or component type
circuit breaker
Device application
control
Poles description
1P + N
Network type
AC/DC
Utilisation category
  • category A conforming to IEC 60947-2
  • DC-12 conforming to IEC 60947-5-1
  • DC-13 conforming to IEC 60947-5-1
    • Network frequency
      50/60 Hz conforming to IEC 60947-2
      Breaking capacity
    • 2 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-2
    • 1.5 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
    • 1.5 kA Icu at 24 V DC conforming to IEC 60947-2
      • [Ics] rated service short-circuit breaking capacity
      • 75 % at 110 V AC 50/60 Hz conforming to IEC 60947-2
      • 75 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
        • Trip unit technology
          thermal-magnetic
          Magnetic tripping current
          165-165 A
          Mounting mode
          by clips
          Mounting support
        • rail
        • plate
          • Mounting position
          • vertical
          • horizontal
            • Control type
              toggle
              [In] rated current
              12 A
              [Ue] rated operational voltage
            • 250 V AC 50/60 Hz conforming to IEC 60947-2
            • 277 V AC 60 Hz conforming to CSA C22.2 No 235
            • 277 V AC 60 Hz conforming to UL 1077
            • 48 V DC
              • [Uimp] rated impulse withstand voltage
                Power dissipation per pole
                2 W
                Mechanical durability
                8000 cycles
                Electrical durability
                8000 cycles
                Connections - terminals
              • connector 1 cable(s) 0.75-6 mm²solid without cable end
              • connector 2 cable(s) 0.75-4 mm²solid without cable end
              • connector 1 cable(s) 0.75-4 mm²flexible with cable end
              • connector 2 cable(s) 0.75-2.5 mm²flexible with cable end
                • Tightening torque
                  1.2 N.m on connector
                  Mechanical robustness
                • shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27
                • vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6
                  • Quantity per set
                    set of 6
                    9 mm pitches
                    2
                    Height
                    74 mm
                    Width
                    15 mm
                    Depth
                    67 mm
                    Net weight
                    0.07 kg
                    Compatibility code
                    GB2
                    Standards
                  • EN/IEC 60947-1
                  • EN/IEC 60947-2
                  • CSA C22.2 No 235
                  • UL 1077
                    • Product certifications
                    • UL
                    • CSA
                      • Protective treatment
                        TC
                        IP degree of protection
                        IP20 conforming to IEC 60529
                        Ambient air temperature for operation
                        -20-60 °C
                        Ambient air temperature for storage
                        -40-80 °C
                        Fire resistance
                        960 °C conforming to IEC 60695-2-1
                        Operating altitude
                        3000 m
                        Sustainable offer status
                        Green Premium product
                        REACh free of SVHC
                        Yes
                        EU RoHS Directive
                        Compliant
                        Toxic heavy metal free
                        Yes
                        Mercury free
                        Yes
                        RoHS exemption information
                        Yes
                        China RoHS Regulation
                         Pro-active China RoHS declaration (out of China RoHS legal scope)
                        Environmental Disclosure
                        ENVPEP110308EN
                        WEEE
                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                        California proposition 65
                        WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                        Warranty
                        18 months

                        Frequently Asked Questions

                        hide show

                        What would be the part number for an enclosure for the GV2ME20

                        Protection Rating for GV2E01

                        Issue:
                        What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                        Product Line:
                        GV2 Enclosure Accessories

                        Environment:
                        US Product

                        Cause:
                        The IP rating is not specified in the Digest 176

                        Resolution:
                        When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                        Can the GV* starters be used on 50 hertz applications?

                        Issue:
                        GV* Starter for 50/60hz application

                        Product Line:
                        Motor Starters and Protectors

                        Environment:
                        PowerPact™ Manual Starters

                        Resolution:
                        Yes, these starters are rated for 50/60 hertz.

                        This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                        Issue:
                        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                        Product Line:
                        Contactors and Starters IEC

                        Environment:
                        Tesys D contactors and GV manual starters

                        Cause:
                        Spacer required

                        Resolution:
                        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                        Is a padlocking device available for the GV2MC** type enclosures?

                        Issue:
                        Padlocking device for GV2MC Enclosures

                        Product Line:
                        TeSys GV2 Manual Starters and Protectors

                        Environment:
                        n/a

                        Resolution:
                        Yes, use the GV2V01. When this is padlocked, the starter is automatically in and will remain in the OFF position.

                        Can a GV2AF3 or GV2AF4 interconnection block work on a contactor with a DC coil?

                        Issue:
                        Mounting adaptor for GV2 and LC1D contactor

                        Product Line:
                        Motor Starters and Protectors

                        Environment:
                        TeSys GV Manual Starter and Protectors
                        Tesys D Contactors
                         
                        Resolution:
                        The GV2AF3 clip has to be moved to the DC position to accommodate the contactor with a DC coil.

                        Are explosion proof enclosures available for GV manual motor starters.

                        Issue:
                        NEMA 7/9 rated enclosure for GV manual motor starters

                        Product Line:
                        Tesys GV Motor Starters and Protectors

                        Environment:
                        TeSys™ GV Manual Starters and Protectors

                        Resolution:
                        No hazardous duty enclosures are available for the GV product line.
                        For explosion proof applications consider the Class 2510 Type M or Type T offering.