Quantcast

Control Circuit Breaker

Product Dimensions

Width icon

Width15 mm

Height icon

Height74 mm

Depth icon

Depth67 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

TeSys

Product or component type

circuit breaker

Device application

control

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Mounting mode

by clips

Mounting support

  • plate
  • rail
    • Mounting position

    • horizontal
    • vertical
      • Control type

        toggle

        [In] rated current

        8 A

        [Ue] rated operational voltage

      • 250 V AC 50/60 Hz conforming to IEC 60947-2
      • 277 V AC 60 Hz conforming to CSA C22.2 No 235
      • 277 V AC 60 Hz conforming to UL 1077
      • 48 V DC
        • Mechanical durability

          8000 cycles

          Electrical durability

          8000 cycles

          Connections - terminals

        • connector 1 cable(s) 0.75-6 mm²solid without cable end
        • connector 2 cable(s) 0.75-4 mm²solid without cable end
        • connector 1 cable(s) 0.75-4 mm²flexible with cable end
        • connector 2 cable(s) 0.75-2.5 mm²flexible with cable end
          • Quantity per set

            set of 6

            Height

            74 mm

            Width

            15 mm

            Depth

            67 mm

            Net weight

            0.07 kg

            Standards

          • EN/IEC 60947-1
          • EN/IEC 60947-2
          • CSA C22.2 No 235
          • UL 1077
            • Product certifications

            • UL
            • CSA
              • IP degree of protection

                IP20 conforming to IEC 60529

                Ambient air temperature for operation

                -20-60 °C

                Ambient air temperature for storage

                -40-80 °C

                REACh Regulation

                Free of Substances of Very High Concern above the threshold

                REACh free of SVHC

                Yes

                EU RoHS Directive

                Compliant

                Toxic heavy metal free

                Yes

                Mercury free

                Yes

                RoHS exemption information

                Yes

                China RoHS Regulation

                 Pro-active China RoHS declaration (out of China RoHS legal scope)

                Environmental Disclosure

                ENVPEP110308EN

                California proposition 65

                WARNING: Cancer - www.P65Warnings.ca.gov

                Others

                Product name

                TeSys GB2

                Device short name

                GB2

                Poles description

                1P + N

                Network type

                AC/DC

                Utilisation category

              • category A conforming to IEC 60947-2
              • DC-12 conforming to IEC 60947-5-1
              • DC-13 conforming to IEC 60947-5-1
                • Network frequency

                  50/60 Hz conforming to IEC 60947-2

                  Breaking capacity

                • 3 kA Icu at 110 V AC 50/60 Hz conforming to IEC 60947-2
                • 1.5 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
                • 1.5 kA Icu at 24 V DC conforming to IEC 60947-2
                • 1 kA Icu at 48 V DC conforming to IEC 60947-2
                  • [Ics] rated service short-circuit breaking capacity

                  • 75 % at 110 V AC 50/60 Hz conforming to IEC 60947-2
                  • 75 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
                    • Trip unit technology

                      thermal-magnetic

                      Magnetic tripping current

                      108-108 A

                      [Uimp] rated impulse withstand voltage

                      Power dissipation per pole

                      2 W

                      Tightening torque

                      1.2 N.m on connector

                      Mechanical robustness

                    • shocks: 22 Gn for 20 ms conforming to IEC 60068-2-27
                    • vibrations: 5 Gn, 5...110 Hz conforming to IEC 60068-2-6
                      • 9 mm pitches

                        2

                        Compatibility code

                        GB2

                        Protective treatment

                        TC

                        Fire resistance

                        960 °C conforming to IEC 60695-2-1

                        Operating altitude

                        3000 m

                        WEEE

                        The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                        Show all specifications

                        Frequently Asked Questions

                        hide show

                        Protection Rating for GV2E01

                        Issue:
                        What rating does the GV2E01 give when used with the GV2MC01 or GV2MP01 enclosure

                        Product Line:
                        GV2 Enclosure Accessories

                        Environment:
                        US Product

                        Cause:
                        The IP rating is not specified in the Digest 176

                        Resolution:
                        When used with the GV2MC01 or GV2MP01, this kit will give a IP55 rating.

                        What is the replacement lens cap for ZB2BW extended head push button?

                        Issue:
                        What is the replacement lens cap for ZB2BW extended head push button?

                        Product Line:
                        Harmony Pushbuttons

                        Environment:
                        All Products

                        Cause:
                        Product selection

                        Resolution:
                        The ZB2 product line is discontinued.  The replacement heads are no longer available

                        ZB2BW931 - White
                        ZB2BW933 - Green
                        ZB2BW934 - Red
                        ZB2BW935 - Ambler
                        ZB2BW936 - Blue
                        ZB2BW937 - Clear

                        GV2P disconnect options

                        Issue:
                        What is the product number for a complete through-the-door disconnect device for a GV2P

                        Product Line:
                        GV2P Manual Starters and Protectors

                        Environment:
                        US product

                        Cause:
                        Digest 176 is unclear as to what is a complete mechanism with shaft and handle

                        Resolution:
                        There are three devices which include mechanism, shaft and handle:
                        GV2APN01 has a NEMA 1, 12 rating and is black
                        GV2APN02 has a NEMA 1, 12 rating and is red/yellow
                        GV2APN04 has a NEMA 3R, 4, 4X rating and is red/yellow

                        Can the GV* starters be used on 50 hertz applications?

                        Issue:
                        GV* Starter for 50/60hz application

                        Product Line:
                        Motor Starters and Protectors

                        Environment:
                        PowerPact™ Manual Starters

                        Resolution:
                        Yes, these starters are rated for 50/60 hertz.

                        This applies to all GV2M, GV2ME, GV2P, GV3M, GV3ME devices.

                        What is the part number for the spacer used with the LC*D09 through LC*D32 Contactor and the GV2AF3 combination block when the GV2 Motor Circuit Protector is mounted on din rail and the contactor hangs below it?

                        Issue:
                        Identifying the spacer part number for use with a LC*D, GV2AF3, and GV2 device combination

                        Product Line:
                        Contactors and Starters IEC

                        Environment:
                        Tesys D contactors and GV manual starters

                        Cause:
                        Spacer required

                        Resolution:
                        Compensation plate catalog number GV1F03, requires 2 pieces snap together.

                        Will the Tesys GV2ME starters install into old style enclosures designed for the GV2M, GV2MC01 and GV2MC02 enclosures?

                        Issue:
                        GV2ME compatibility with old enclosure 

                        Product Line:

                        Motor Starters and Protectors

                        Environment:
                        TeSys™ GV Manual Starters and Protectors
                         
                        Resolution:
                        No, Order new enclosures using the same catalog numbers. The current enclosure has an updated DIN attachement which will accept the Tesys GV2ME starters but will not accept the old GV2M starters.