Issue:
ATV212 parameter F303 configuration
Product Line:
Altivar 212, Altivar 21
Environment:
All serial numbers
Cause:
N/A
Resolution:
F303 is the number of auto restarts that the VFD will attempt before locking on a fault.
Is there a mounting clip to fit a 30 series mec to a panel?
Yes, the F30Z1, F30Z1.5, or F30Z2 mounting clip suits 1, 1.5, or 2mm thick panels, or the B30GFZ will screw mount onto a surface.
What is the part number for the adapter that lets 30 series mecs fit in a Prestige switch?
The part number for the adapter that lets 30 series mecs fit in a Prestige switch is P30Z.
Why does the ATV212 display a flashing StOP when changing from utility to generator power?
Issue:
ATV212 flashing StOP when changing from utility to generator power
Product Line:
ATV21, ATV212
Environment:
All models and serial numbers.
Cause:
Momentary power loss removes output power to motor.
Resolution:
When F302, supply loss behavior, is enabled, then a brief loss of input power will cause the drive to remove power from the motor and display the flashing StOP alarm. To restart operation, remove and reapply a new run command signal. To disable this function and attempt to ride through the momentary loss of power, set F302 back to the factory default of 0.
What can cause on OC1 fault on the ATV21 and ATV212 drives?
Issue:
OC1 fault on ATV21 and ATV212 drives
Product Line:
Altivar ATV21 and ATV212
Environment:
All
Cause:
Over current during acceleration
Resolution:
Increase the ACC time or the ACC2 time
Try adjusting the PT parameter
Enable catch on the fly F301= 4
Try adjusting the switching frequency F300
Set F316 parameter to 1 or 3