MASTER YOUR CASTLE with your new build or reno project
Enter competition
Link150 Product Image

EGX150

Link 150, Ethernet Gateway, 2 Ethernetport, 24VDC and PoE

Link150 Product Image
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range
Enerlin'X
Product name
Link
Product or component type
gateway
Device short name
Link150
Device application
gateway
[Us] rated supply voltage
external supply: 19.2...26.4 V DC, <500 mA
Supply
power supply device PoE conforming to IEEE 802.3af
Number of port
2
Communication gateway
Ethernet/fieldbus
Current consumption
  • 130 mA at 24 V DC via external supply (20 °C)
  • 65 mA at 48 V DC via PoE (20 °C)
    • Maximum power consumption in W
      15 W via PoE
      Communication network type
    • Ethernet, Ethernet Modbus TCP/IP daisy chain even/odd or none parity, at 10/100 Mbit/s
    • RS485, Modbus RTU, JBUS, PowerLogic (SY/MAX) even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds
    • RS485, Modbus ASCII even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds
    • RS485, Modbus Serial line slave even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds
    • Ethernet, PoE 15W (Power over Ethernet) even/odd or none parity, at 10/100 Mbit/s
    • Ethernet, FTP even/odd or none parity, at 10/100 Mbit/s
    • Ethernet, HTTP even/odd or none parity, at 10/100 Mbit/s
    • Ethernet, SNMP even/odd or none parity, at 10/100 Mbit/s
    • Ethernet, Modbus TCP/IP even/odd or none parity, at 10/100 Mbit/s
    • RS232, Modbus RTU, JBUS, PowerLogic (SY/MAX) even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds
    • RS232, Modbus ASCII even/odd or none parity, at 2400, 4800, 9600, 19200, 38400, 56000 or 57600 bauds
    • RS232, Modbus Serial line slave even/odd or none parity, at 2400, 4800, 9600, 19200 or 38400 bauds
      • Parity
        even/odd or none
        Communication port protocol
      • Ethernet Modbus TCP/IP daisy chain, insulation 6 kV
      • Modbus TCP/IP, insulation 6 kV
      • Modbus RTU, JBUS, PowerLogic (SY/MAX), master - 2 or 4 wires, insulation 2.5 kV
      • Modbus ASCII, master - 2 or 4 wires, insulation 2.5 kV
      • Modbus RTU and ASCII, slave - 2 or 4 wires, insulation 2.5 kV
        • Communication port support
        • RJ45: Ethernet
        • RJ45: RS232
        • RJ45: RS485
          • Number of inputs
            0-0
            Number of outputs
            0
            Connections - terminals
          • power supply: screw terminal block (top) 0.2-1.5 mm² cable(s) rigid
          • power supply: screw terminal block (top) 0.2-1.5 mm² cable(s) flexible with cable end
          • power supply: screw terminal block (top) 0.2-1.5 mm² cable(s) flexible without cable end
            • Tightening torque
              power supply: 0.3-0.3 N.m flat screwdriver 3 mm
              Wire stripping length
              power supply: 7 mm for top connector connection
              Mounting mode
              clip-on
              Mounting support
              35 mm DIN rail
              Product certifications
            • cULus
            • FCC Class A
            • CE
            • RCM
            • UL
            • China RoHS
            • cUL
              • Standards
              • IEC 60950-1
              • UL 61010-2-201
              • UL 61010-1
              • CSA C22.2 No 60950-1
              • AS/NZS 60950-1
              • UL 60950-1
              • IEC 61000-6-2
                • Depth
                  72 mm
                  Height
                  105 mm
                  Width
                  71 mm
                  Net weight
                  175 g
                  Web services
                  web server
                  Local signalling
                • LED: for Ethernet activity (ETH1)
                • LED: for Ethernet activity (ETH2)
                • LED: for module status
                • LED: for network communication status (Net Status)
                • LED: for communication (RS232)
                • LED: for communication (RS485)
                  • Compatibility code
                    EGX150
                    Relative humidity
                    5-95 % at 55-55 °C without condensation
                    IP degree of protection
                  • N/A
                  • N/A
                  • N/A
                    • Mechanical robustness
                    • vibrations in operation: 1 Gn, 5 Hz...150 Hz conforming to IEC 60068-2-6
                    • vibrations de-energized: 1 Gn, 5 Hz...150 Hz conforming to IEC 60068-2-6
                    • shocks in operation: 10 Gn for 11 ms conforming to IEC 60068-2-27
                    • shocks de-energized: 15 Gn for 11 ms conforming to IEC 60068-2-27
                    • jolts de-energized: 100 jolts/axle, 15 Gn for 6 ms conforming to IEC 60068-2-29
                    • free fall resistance: 1.2 m
                      • Electromagnetic compatibility
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                      • N/A
                        • Ambient air temperature for operation
                          -25-70 °C
                          Ambient air temperature for storage
                          -40-85 °C
                          Pollution degree
                          2
                          Sustainable offer status
                          Green Premium product
                          REACh Regulation
                          Reference contains Substances of Very High Concern above the threshold
                          EU RoHS Directive
                          Compliant
                          Mercury free
                          Yes
                          RoHS exemption information
                          Yes
                          China RoHS Regulation
                          Product out of China RoHS scope. Substance declaration for your information
                          Environmental Disclosure
                          ENVPEP090601EN_V0
                          Circularity Profile
                          ENVEOLI100609EN

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • Product Brochures

                          • Technical Data Catalogues

                          • Technical Leaflet

                          • Installation Instruction

                          • Handout

                          • Operating Manuals

                          • Case Studies

                          • Declaration of Conformity

                          • Firmware - Released

                          • Firmware - Updates

                          Frequently Asked Questions

                          hide show

                          What is the maximum number of concurrent Ethernet connections that the Powerlogic EGX150 supports?

                          Issue
                          Need to know the maximum number of concurrent Ethernet connections that the Powerlogic EGX150 supports

                          Product Line
                          EGX150

                          Environment
                          EGX150 Ethernet Gateway

                          Cause
                          Supported TCP/IP concurrent connections supported by the EG150

                          Resolution
                          The Powerlogic EGX150 is a Modbus to Ethernet gateway that can support a maximum of 16 concurrent Ethernet (Modbus TCPIP) connections.


                           

                          Wiring diagram for EGX150 to MGE PMM/PMN

                          Issue:
                          Wiring diagram for EGX150 to PMM/PMN


                          Product line:
                          MGE PMM/PMN


                          Environment:
                          MGE PMM/PMN


                          Cause:
                          Wiring diagram for EGX150 to PMM/PMN



                          Resolution:


                           



                           
                           

                          EGX150 documentation (Brochure, Technical DataSheet, User and Installation Guide, Presentation Overview)

                          Issue
                          Documentation for EGX150 or Link150.
                           
                          Product Line
                          EGX150 / Link150
                           
                          Environment
                          Brochure, Technical DataSheet, Installation and User Guide, Presentation Overview 
                           
                          Cause
                          The Link150 gateway serves as an Ethernet coupler for PowerLogic/Schneider Electric system devices and for other communicating devices that use Modbus protocol.
                           
                          Resolution
                          The documents attached below include the Brochure, Technical DataSheet, Quick Start Guide, User Guide and Presentation Overview.

                          Here is a link to the EGX150/Link150 Schneider Electric product information page
                          https://www.schneider-electric.com/en/product-range/63423-link150?N=884144915

                          Can I use an EGX150 to connect a CM2000 series as a downstream device?

                          Issue
                          EGX150 used as a master device that is connected to downstream devices such as a CM2000

                          Product Line
                          EGX150 (Link150), CM2000 Series

                          Environment
                          Communications, Wiring, Gateway Supported device type

                          Resolution
                          The EGX150 does have the capability of having a CM2000 series as a downstream device. The protocol on the EGX150 must be set to PowerLogic (SY/MAX) in order for a connection to be established. CM2000 series meters are not designed to do 2 wire RS-485 communication. CM2000 series meters can only be wired as 4 wire RS-485 communication. If you would like to use 2 wire communication, a CNV-100 is required to convert from 2 wire to 4 wire. For more information on CNV-100, click on the following article: FA203955

                          EGX150 serial communication cable

                          Issue
                          User is trying to purchase a cable to wire serial communication to EGX150 (Link150) to downstream devices through its RJ45 serial port

                          Product Line
                          EGX150 (Link150)

                          Environment
                          Serial communication

                          Resolution
                          Part# VW3A8306d30

                          This cable is for Modbus serial link 1xRJ45, free wires at the other end. 3m length

                          The correspondence between the wire colors of cable VW3A8306D30 and the pin numbers of the RJ45 socket is as follows:


                          Connecting an EGX150 to a serial RS485

                          Issue
                          The Serial port for the EGX150 uses an RJ45 connector, which is different from the standard RS-485 connector.

                          Product Line
                          Link150, EGX150

                          Environment
                          EGX150 serial connections

                          Cause
                          The EGX150 does not use the standard RS-485 connector. 

                          Resolution
                          Pin Number Colour Signal name Description
                          1 Orange/White striped Rx- Receive Data -
                          2 Orange Rx+ Receive Data +
                          3   NC No Connection
                          4 Blue Tx+ Transmit Data +
                          5 Blue/white striped Tx- Transmit Data -
                          6   NC No Connection
                          7   NC No connection
                          8   GND Ground













                          Connect, using a straight through RJ45 cable to the RS-485 port on your EGX150.
                          Cut the other end (that is to be connected to your slave device) to expose the wires.

                          2-Wire RS-485 connection:
                          Use the Blue wire as the positive (+) and the Blue/White striped wire as the negative (-)


                          4-Wire RS-485 connection:
                          RJ45 Pin Number  Master Slave
                          1 Rx- Tx-
                          2 Rx+ Tx+
                          4 Tx+ Rx+
                          5 Tx- Rx-









                          Kindly refer to the EGX150 User Guide for details on how to wire the RS-485 port.

                          What is the recommended serial port configuration when connecting a Powerlink G3 Controller to an EGX150 (Link150)?

                          Issue
                          During installation, the EGX150 may need to be configured to communicate with the Powerlink controller.

                          Product Line
                          EGX150 (Link 150)
                          Powerlink G3 controller (NF1000, NF3000)

                          Environment
                          Installation and setup

                          Resolution
                          Configuring to communicate via RS-485
                          Wire RS-485 connection as follows:


                          Powerlink Serial Settings
                          Address: <unique identifier>
                          Baud Rate: <consistant with EGX150 device>
                          Parity: Even
                          Mode: 7-bit ASCII

                          EGX150 Serial Port Settings
                          Mode: Master
                          Physical Interface: RS485 2-wire
                          Transmission Mode: Modbus ASCII
                          Baud Rate: <consistant with Powerlink device>
                          Stop bits: 1 bit
                          Response Timeout: 2 seconds


                          Configuring to communicate via RS-232
                          Wire RS-232 connection as follows:


                          Powerlink Serial Settings
                          Address: <unique identifier>
                          Baud Rate: <consistant with EGX150 device>
                          Parity: Even
                          Mode: 7-bit ASCII

                          EGX150 Serial Port Settings
                          Mode: Master
                          Physical Interface: RS232
                          Transmission Mode: Modbus ASCII
                          Baud Rate: <consistant with Powerlink device>
                          Stop bits: 1 bit
                          Response Timeout: 2 seconds


                          Once both of the devices are configured, the Powerlink device needs to be added to the EGX150's device list.
                          To add the Powerlink device to the EGX150:
                          1. Navigate to the Configuration & Settings tab
                          2. Select Device List on the left-hand side of the screen
                          3. Enter a Device Name and then specify the Local ID to be the Address set in the Powerlink device

                          What is the default IP address fo the Link150 Ethernet Gateway?

                          Issue:
                          Need to find the default IP address for the Link150 (EGX15) Ethernet Gateway

                          Product Line:
                          Link150 Ethernet Gateway (EGX150)

                          Environment:
                          Link150 Webpage Connection
                          (EGX150)

                          Cause:
                          Unable to connect to the Link150 Ethernet Gateway (EGX150)

                          Resolution:
                          The default IP address for the Ethernet Gateway Link150 (EGX150) is 169.254.YY.ZZ
                          YY.ZZ are the last 2 bytes of the Link150 MAC address. For example, A Link150 with
                          MAC address 00-B0-D0-86-BB-F7 (hexadecimal) or 0-176-208-134-187-247 (decimal),
                          set the IP address as169.254.187.247



                           

                          Does the EGX150 (Link 150) support Powerlogic and SY/MAX protocols?

                          Issue
                          The user needs to know if the EGX150 supports the Powerlogic and SY/MAX protocols.

                          Product Line
                          EGX150

                          Environment
                          Gateway Protocol Support

                          Cause
                          A user needs to convert legacy device protocols such as Powerlogic and SY/MAX from CM2000 series, CM200 series, CM100 series, etc. to Modbus TCP/IP.

                          Resolution
                          The EGX150 supports the Powerlogic or SY/MAX protocols. When the 'Transmission Mode' within the serial port setting is automatic, the device allows you to communicate to Modbus RTU, Jbus, and PowerLogic™ (SY/MAX) slave devices on the same daisy chain.

                          For Master mode, the usage of the COM port is:

                          • Modbus RTU devices do not have to be defined in the Device List, but it helps you manage your system.
                          • PowerLogic protocol (SY/MAX) devices must be defined in the Device List.


                          EGX150 supported Protocols (Ethernet):
                          IPv4/IPv6 - HTTP
                          FTP
                          Modbus TCP/IP
                          SNMP (MIB II)

                          EGX150 Ethernet Gateway | Manual and Installation Instructions

                          Issue:
                             Where can I find the manual for the Schneider Electric Link150 Ethernet Gateway?

                          Product Line:
                             Link150 Ethernet Gateway (EGX150 / EGX150POE)

                          Environment:
                             EGX150 (all versions)
                             EGX150POE (all verisons)

                          Resolution:

                          The link below contains the most up to date documentation for the Schneider Electric Ethernet Gateway EGX150.
                          https://www.schneider-electric.com/en/product/EGX150/link-150---ethernet-gateway---2-ethernetport---24-v-dc-and-poe/
                           

                          Link150, Comx200/210, Comx510 CAD Files

                          Issue
                          CAD files for the gateway devices:
                          Link150, Comx200/210, Comx510

                          Product Line
                          Link150, Comx200/210, Comx510

                          Resolution
                          Click on the links below for the Comx200/210 and Comx510 CAD files:
                          Comx510 CAD File

                          Comx200/210 CAD File

                          The Link150 CAD file is attached below

                          Does the Device List need to be configured in the EGX / ECC setup page?

                          Product Line
                          EGX300
                          EGX400
                          EGX200
                          EGX100
                          EGX150(Link150)
                          ECC21

                          Environment
                          Device List

                          Resolution
                          The EGX series and ECC series of gateways do not require the user to modify the device list as long as all devices are Modbus and not a mix with Powerlogic and jbus. Port 2 of the EGX200 and EGX400 however must have a device list set.

                          The EGX300 has a Device Auto Discovery mode which will go out and determine which devices are on the chain for the user and auto-populate the device list.

                          Link150 Module status LED is blinking red

                          Issue
                          Link150 Module status LED is blinking red

                          Product Line
                          Link150

                          Environment
                          Status LED

                          Cause
                          The Link150 firmware is in degraded mode, or there is an issue with the power supply going to the Link150

                          Resolution
                          Make sure the Link150 power supply meets the recommended 24 V DC (-20/+10%) or
                          Power over Ethernet (PoE Class 3 IEEE 802.3 af) at 15 W.

                          If the power supply meets the recommended values, then the Link150 should be replaced.
                           

                          Does the Com'X 200/210 or Com'X 510 support the Powerlogic and SY/MAX protocols?

                          Issue
                          A user needs to know if the Com'X 200 / Com'X 210 / Com'X 510 supports the Powerlogic and SY/MAX protocols

                          Product Line
                          Com'X 200/EBX200
                          Com'X 210/EBX210
                          Com'X 510/EBX510

                          Environment
                          Gateway Portocol Support

                          Cause
                          A user needs to convert legacy device protocols such as Powerlogic and SY/MAX from CM2000 series, CM200 series, CM100 series, etc. to Modbus TCP/IP.

                          Resolution
                          The Com'X 200, Com'X 210 and Com'X 510 do not support the Powerlogic or SY/MAX protocols.
                          Use an EGX100 or EGX300 to convert Powerlogic or SY/MAX to Modbus TCP/IP. However, EGX100/300 have been obsoleted and the replacement is EGX150. EGX150 supports the Powerlogic or SY/MAX protocols as well.

                          Com'X 200 supported Protocols:
                          IPv4
                          IPv6 - HTTP
                          HTTPS
                          Modbus TCP/IP

                          Com'X 510 supported Protocols:
                          HTTP
                          HTTPS
                          FTP
                          SMTP
                          Modubs TCP/IP

                          What meters and software support SNMP protocol?

                          Issue
                          Which devices and software support SNMP

                          Product Line
                          ION and Powerlogic Devices
                          ION Enterprise
                          Stuxtureware Power Monitoring
                          Struxureware Power Monitoring Expert

                          Environment
                          Setup and Protocol

                          Cause
                          Not all meters or software support the SMNP protocol

                          Resolution
                          The SNMP protocol is only supported by:

                          • ION7400 series meters
                          • ION7550 and ION7650 series meters with firmware version 350 or greater
                          • PM5500 series meters with firmware v2.0.1 or greater
                          • PM8000 series meters
                          • PM800 series meters with PM8ECC ethernet communication cards
                          • CM4000T with ECC21 ethernet communication card
                          • BCPME
                          • EGX100, EGX150 and EGX300 Ethernet Gateways (MIB II)

                          All other meters do not support this protocol.

                          SNMP Setup Documentation:
                          ION7400 meters: ION7400 User Manual and ION Reference Guide
                          ION7550 and ION7650 meters: ION7550/ION7650 User Guide and ION Reference Guide
                          PM8000 meters: PM8000 User Manual and ION Reference Guide
                          PM800 series meters with the PM8ECC Ethernet Communications card: FA209648
                          CM4000T with ECC21: ECC User Guide
                          BCPME: BCPME User Guide
                          EGX gateways: FA211887

                          ION Enterprise and Struxtureware Power Monitoring do not support the SNMP protocol. To read the SNMP data in ION Enterprise or SPM convert the data to Modbus or ION protocol.

                          What is the part number for the EGX power supply?

                          Issue
                          What is the part number for the EGX power supply?

                          Product Line
                          EGX100, EGX150, EGX200, EGX300, EGX400

                          Environment
                          Installation

                          Resolution

                          Power Supply Offering
                          Schneider Electric sells two 24 Volt power supplies for the EGX gateways:

                          3090PS24 - 7.5 Watt 24 Volt power supply
                          PSSVCSPS24V50W - 50 Watt 24 Volt power supply

                          Additionally, Schneider Electric offers a Power Over Ethernet Injector Kit: TCSEAV0100

                          Gateway Requirements
                          EGX200/400 Gateway - Any 24 Volt power supply with a minimum output of 8 Watts is sufficient
                          EGX100/300 Gateway - Any 24 Volt power supply with a minimum output of 4 Watts is sufficient
                          EGX150 Gateway - Any 24 Volt power supply with a minimum output of 15 Watts is sufficient

                          The EGX100/300/150 gateways are also capable of receiving power over ethernet.

                          The table below indicates the supported power supplies per gateway:

                            EGX200 EGX400 EGX100 EGX300 EGX150
                            24 Volt 24 Volt 24 Volt POE 24 Volt POE 24 Volt POE
                          3090PS24     X   X      
                          PSSVCSPS24V50W X X X   X   X  
                          TCSEAV0100       X   X   X