socket inlet 63a 500v e range

Appliance Inlets - E Range, Multi Phase - 500V, 63A 4 Round pin

Catalogue Number: E463BR
socket inlet 63a 500v e range
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
E Range
Product brand
Clipsal
[In] rated current
63 A
[Ue] rated operational voltage
500 V 50/60 Hz conforming to EN 60309-2
Voltage colour
black
Sustainable offer status
Green Premium product
REACh free of SVHC
Yes
EU RoHS Directive
Compliant
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure
ENVPEP120809EN
Circularity Profile
N/A

Documents & downloads

hide show
Filter items
  • All

  • Product Brochures

  • Product Environmental

  • Installation Instruction

  • Specifications

  • Certificates (MSDS)

  • Declaration of Conformity

  • Corporate Marketing

Frequently Asked Questions

hide show

What is the plug to suit the 63A, 4 pin socket E463PR?

The plug to suit the 63A, 4 pin socket, E463PR is E463P.
Some of its key features are:
  • Multi phase 500 V Plug
  • E range
  • 4 Round pins
  • 63 Amp
  • E-Range
  • Socket to suit plug is E463PR
For further information on this product please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=E463P
 
 

What is the socket extension to suit the E463P?

The socket extension to suit the E463P is the E463SESC.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=E463SESC 

Top Level
Product Category
Buildings & IT
Retail
Wiring devices
ACCESSORIES

What is the part number for the internal of the E463P?

The part name is SP-116273

What is the part number for an ATS46 soft starter keypad?

Issue:
What is the part number for an ATS46 soft starter keypad?

Product Line:
Altistart 46

Environment:
All

Cause:

Need to replace keypad

Resolution:

The part number is VW3G46101U.  It is obsolete and no replacement available.
See attached document for further information


 

When did the ATS46 soft start become obsolete?

Issue:
Customer would like to know when the ATS46 became obsolete.

Product line:
ATS46, Altistart 46

Environment:
All models.

Cause:
Determine age of unit, product obsolescence

Resolution:
ATS46 became obsolete in January of 2004.  The current replacement is the ATS48. 
There are some differences that should be reviewed by the customer such as wiring, dimensions and ratings. Refer to this article for details on the differences: https://www.schneider-electric.us/en/faqs/FA175441/
 

Is there a problem with using the Altistart ATS46 soft starters on open delta and grounded delta distribution systems?

Issue:
Is there a problem with using the Altistart ATS46 soft starters on open delta and grounded delta distribution systems?

Product Line:
Altistart 46

Environment:
All

Cause:
N/A

Resolution:
There are some problems that may occur with corner grounded systems.
The input filter has capacitors from each line to a neutral point and then another capacitor from this neutral point to ground. Using a corner grounded system unbalances this filter and may increase the filter leakage current. Another problem is if there is a fault to ground of the grounded phase, then there is no fault current to detect the fault, but the SCRs on that phase are shorted out by the external short.
Similar problems may occur on ungrounded Delta systems.
One or more phases may have a high voltage with respect to ground. This may cause measurement irregularities that can affect the operation of the soft starter. This is not usually a problem with control board firmware version 3.0 IE07. With older version firmware, this may be a problem.
The open Delta may be problem for the ATS46 because the voltage may not be balanced when loaded. This may cause phase fault problems.
Do not recommend the open delta.

What replaces the obsolete ATS46 soft starter line?

Issue:
What replaces the obsolete ATS46 soft starter line?

Product Line:
Altistart 46

Environment:
All

Cause:
Replacement

Resolution:
The direct replacement is ATS48.

Here are a few things to consider when converting an ATS46 to ATS48 unit.

The ATS46 uses an N at the end of the part number and the ATS48 uses an Y at the end of the part number. 

The dimensions will be different. In most cases the ATS48 is smaller than its equivalent ATS46. 

The ATS48 has a built-in keypad, the ATS46 uses a removable keypad. The VW3G48101 is the remote mountable keypad kit for the ATS48. 

The shorting contactor is connected from A1 to A2, B1 to B2, C1 to C2 on the ATS46. On the ATS48 connect the shorting contactor from L1 to A2, L2 to B2, L3 to C2. Suggest using power distribution block for the input connections of the shorting contactor. 

The ATS46 had 460vac control power (a built -in control transformer is present on ATS46 soft starts). The ATS48 does not have a control transformer built-in. The control power for a ATS48 is 90-270vac and is customer supplied. Customer's typically use 120 vac for the control power for ATS48 soft starts. 

The ATS 46 had a NC (R1B-R1D) or a NO (R1A-R1C) for the fault relay. 
The ATS46 had a NO (R2A-R2C) for the End of start-up relay. 

The ATS48 has a NO (R1A-R1C) for the fault relay. 
The ATS48 has a NO (R2A-R2C) for the End of start-up relay. 
The ATS48 has a NO (R3A-R3C) for a programmable relay. 

The ATS48 does not have a NC relay (R1B-R1D on ATS46), if that contact is being used, you need an interposing relay on the ATS48. Then wire to the NC contact on the relay 
(Recommend ice cube relay w/ N/O-N/C cont. w/ coil voltage to COM) – (i.e. 8501RSD41V53 with base 8501nr41)