E14/48/2

Medilec Isolation Transformers, 240V, 4.8Kva, Encapsulated

Catalogue Number: E14/48/2
E14/48/2
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
  • Medilec
  • ESP Metal Plate Series
  • Series E14
    • Product brand
      Clipsal
      Primary voltage
      240 V AC
      Secondary voltage
      240 V AC
      Rated power in VA
      4800 VA
      [In] rated current
      20 A

      Frequently Asked Questions

      hide show

      Can the Primary and Secondary be run together on the e14/36/3

      - Can the Primary and Secondary be run together?
      Preferably not - but this is impacted by the distance they are run together. If the distance is short, i.e. a few metres then not a problem. If it is more distance then need to segregate. It is difficult to give an exact answer as there are dependencies. If they were separate by 1m then any distance would be ok.

      - Is segregation required, and if so what is the advised segregation distance and type (conduit etc)
      As above - at least 1m would meet all circumstances. Type of conduit does not really matter as the distance provides the segregation rather than any shielding from conduit.
      Please see following link for further information and related products
      https://www.clipsal.com/Trade/search-results?q=e14/36/3

      What replaces the line isolation and overload monitor E05/36/2 and E05/48/2?

      The part number for the line isolation and overload monitor is MLHG6. The MLHG6 line isolation and overload monitor replaces both E05/36/2 and E05/48/2.
      The MLHG6 requires a wall box, the part number for the wall box is MLHG6B-AU.
      Some of the key features are:
      • Programmable for current monitoring up to 100A
      • In-built test / verification module
      • Tracks data history of operational mode and faults
      • Fully approved to AS/NZS4510:1999 Isolated Electrical Supplies for Medical Uses
      • Meets requirements for AS/NZS3003:2011 Electrical Installations – Patient Areas of Hospitals
      • Potential to integrate into BMS
      For further information please visit https://www.clipsal.com/Trade/Products/ProductDetail?catno=MLHG6