Msc Chassis for 6P of 27mm & 30P of 18mm

Msc Chassis for 6P of 27mm & 30P of 18mm

Msc Chassis for 6P of 27mm & 30P of 18mm

Item Number: CH25363

Retail
$912.05
RRP (Inc. GST)

Datasheet

Specifications

Design

Range

Acti 9

Product or component type

chassis

Device application

distribution

Physical

Range compatibility

Acti 9 Isobar B distribution board

[In] rated current

250 A

Number of poles

  • 6 27 mm
  • 30 18 mm
    • Length

      353 mm

      Width

      215 mm

      EU RoHS Directive

      Pro-active compliance (Product out of EU RoHS legal scope)

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Others

      Device short name

      MSC 18/27

      Short-circuit withstand

      25 kA 0.1 s

      [Icw] rated short-time withstand current

      25 kA

      Number of ways

    • 1 way (incomer) - 3P
    • 36 ways (outgoer)
      • Package 1 Weight

        3.12 kg

        Package 1 Height

        100 mm

        Package 1 width

        242 mm

        Package 1 Length

        670 mm
        Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • Technical Data Catalogues

        • Specifications

        Frequently Asked Questions

        hide show

        What distribution board is required for the CH25843 chassis?

        For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

        What is the PAN assembly for C120 MCCB's

         The part code is C125123

        ETSNZ - How do I wire the TSXDEY16A4 discrete IO 100...120 VAC module for a Premium PLC?

        TSXDEY16A4 wiring the 120VAC module as per the diagram:

        Are only Clipsal downrods to be used on ACES48SS fans?

         Yes. Only Clipsal downrods are recommended for ACES48SS fans.

        How many 3 pole C120 breakers can be supplied from the C125123?

        That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

        Is my eco-mind energy monitoring software compatible with windows 8.1?

        The software has been developed for windows 7. You would need to change the compatibility mode to run for windows 7.

        For more information on the Ecomind please visit the Clipsal.com website on the link provided
        https://www.clipsal.com/Trade/search-results?q=ecomind

        PowerChute Business Edition no longer works using JRE 8 Update 91 or greater.

        Issue:
        The PowerChute Business Edition versions listed below are unable to support JRE 8 Update 91 or above due to JRE security changes made which impact how PowerChute Business Edition functions.

        Product line:
        PowerChute Business Edition versions 9.0.3, 9.1.1, 9.2.0

        Environment:
        Windows x64, Windows x86, Linux.
        See attached compatibility list

        Cause:
        The latest release of JRE 8 Update 91 (and greater) contains a security update which breaks PowerChute Business Edition functionality.

        Solution:
        Upgrade to or install the attached PowerChute Business Edition upgrade (v9.2.1) & (9.0.4)which is shipped with JRE 8 Update 102. By upgrading to v9.2.1 or 9.0.4, the functional issues caused by the JRE 8 Update 91 changes are fixed. This upgrade is available for supported Windows and Linux operating systems.

        Note: Once you have upgraded to v9.2.1, or 9.0.4 the software will be fully functional. However, if you then decide to upgrade the JRE to a later version than Update 102 using the JRE Configuration Tool, then the additional manual changes specified in Answer ID #FA264735, FA264736 & FA253763 are still required for communications between the PowerChute Agent and PowerChute Console. 

        If your UPS is a SMT, SMX, SURTD, SRT, SMC PowerChute Agent 9.2.1 will be installed.
        If your UPS is a SU, SC, SUA, SURT, SURTA, Matrix PowerChute Agent 9.0.4 will be installed.

        Upgrade to or download v9.2.1 / 9.0.4 from:
        5 Node for Windows
        5 Node for Linux

        Unable to access PowerChute Business Edition Server from the PowerChute Business Edition Console after upgrading the JRE version with JRE Configuration Tool

        Issue:
        When upgrading the JRE version, the JRE Configuration Tool runs as expected and both APC PBE Agent (if applicable) and APC PBE Server services are started. When the PowerChute Business Edition Console is launched and username and password is entered, an error window is displayed stating that the server is not accessible.


        Product Line: 
        PowerChute Business Edition versions 9.0, 9.0.1, 9.1.0, 9.0.2, 9.1.1, 9.0.3, 9.2.0, 9.0.4, 9.2.1

        Environment:
        OS: Windows x64, x86

        Cause:
        The latest release of Java JRE 8u60 (and greater) contains a security update which prevents communication between the PowerChute Business Edition Console and the PowerChute Business Edition Server.

        Solution:
        After upgrading the Java JRE version to 8u60 (or greater), perform the following steps:

        1.  Stop the PowerChute Business Edition Agent and Server services.
        You can do this from the command line (Run as administrator) with the following command:

        Server:                                
        net stop apcpbeserver

        Agent (if installed):       
        net stop apcpbeagent

        2.  In the PowerChute JRE folder, open the file lib\security\java.security using a text editor.

        Sample JRE locations -
        Windows x86:
        C:\Program Files\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
        Windows x64:
        C:\Program Files (x86)\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
        Linux:
        /usr/java/jre1.8.0_60 (Default Java JRE install directory)
        Go to the line containing the jdk.tls.disabledAlgorithms setting and carry out the following:
        1. Remove RC4 as a disabledAlgorithm
        2. Change DH keysize restriction from 768 to 256
        Original:             
        jdk.tls.disabledAlgorithms=SSLv3, RC4, DH keySize < 768

        New:                    
        jdk.tls.disabledAlgorithms=SSLv3, DH keySize < 256

        3. The following step needs to be carried out for PowerChute Business Edition Agent versions 9.0 and 9.0.1 if it is managed by a PowerChute Business Edition Console/Server.

        In the PowerChute JRE folder, open the file lib\security\java.security using a text editor.

        Sample JRE locations -
        Windows x86:
        C:\Program Files\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
        Windows x64:
        C:\Program Files (x86)\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
        Linux:
        /usr/java/jre1.8.0_60 (Default Java JRE install directory)
        Go to the line (should be at the end of the file) containing the jdk.tls.legacyAlgorithms setting and remove 'RC4_128,' from it:

        Original:
        jdk.tls.legacyAlgorithms= \
                        K_NULL, C_NULL, M_NULL, \
                        DHE_DSS_EXPORT, DHE_RSA_EXPORT, DH_anon_EXPORT, DH_DSS_EXPORT, \
                        DH_RSA_EXPORT, RSA_EXPORT, \
                        DH_anon, ECDH_anon, \
                        RC4_128, RC4_40, DES_CBC, DES40_CBC
         
        New:    
        jdk.tls.legacyAlgorithms= \
                        K_NULL, C_NULL, M_NULL, \
                        DHE_DSS_EXPORT, DHE_RSA_EXPORT, DH_anon_EXPORT, DH_DSS_EXPORT, \
                        DH_RSA_EXPORT, RSA_EXPORT, \
                        DH_anon, ECDH_anon, \
                        RC4_40, DES_CBC, DES40_CBC

        4.  Start the PowerChute Business Edition Agent and Server services
        You can do this from the command line (Run as administrator) with the following command:

        Server:                                
        net start apcpbeserver

        Agent (if installed):
        net start apcpbeagent
         

        Are EasyPact CVS circuit breakers for sale in the USA or Canada?

        Product Line:
        EasyPact CVS circuit breakers

        Cause:
        This breaker is popular overseas and there is interest in the US

        Resolution:
        There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.