Quantcast

Msc Chassis for 6P of 27mm & 12P of 18mm

Msc Chassis for 6P of 27mm & 12P of 18mm

Msc Chassis for 6P of 27mm & 12P of 18mm

Item Number: CH25183

Retail
$641.59
RRP (Inc. GST)

Datasheet

Specifications

Design

Range

Acti 9

Product or component type

chassis

Device application

distribution

Physical

Range compatibility

Acti 9 Isobar B distribution board

[In] rated current

250 A

Number of poles

  • 6 27 mm
  • 12 18 mm
    • Length

      191 mm

      Width

      215 mm

      EU RoHS Directive

      Pro-active compliance (Product out of EU RoHS legal scope)

      China RoHS Regulation

      Product out of China RoHS scope. Substance declaration for your information

      Others

      Device short name

      MSC 18/27

      Short-circuit withstand

      25 kA 0.1 s

      [Icw] rated short-time withstand current

      25 kA

      Number of ways

    • 1 way (incomer) - 3P
    • 18 ways (outgoer)
      • Show all specifications

        Documents & downloads

        hide show
        Filter items
        • All

        • Technical Data Catalogues

        • Specifications

        Frequently Asked Questions

        hide show

        What is the PAN assembly for C120 MCCB's

         The part code is C125123

        How many 3 pole C120 breakers can be supplied from the C125123?

        That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

        What distribution board is required for the CH25843 chassis?

        For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

        Will the 755 base fit the new 755PSMA2 smoke alarm?

        No, the only bases that is compatible with each other is the 755PSMA, 755PSMA2, 755SMA, SD100

        How do you wire the Undervoltage Relay in a PowerPact H circuit breaker?

        Product Line:

        Circuit Breakers

        Environment:
        Electrical Distribution Equipment

        Resolution:

        Connect the control wires of proper voltage to the UVR terminals under the accessory cover. Route the wires out the top of the cover through knock-outs.

        Constant voltage at the correct level for the device (24V, 120V, AC, DC, etc) should be applied to terminals numbered D1 and D4. Designation for UV trip is MN.

        Link to instruction bulletin 48940-22-01

         

        What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

        Issue:
        Coil Voltage suffixes for Tesys D contactors LC*D 09/38

        Product Line:
        IEC Contactors and Starters

        Environment:
        Tesys D contactors

        Cause:
        Selection

        Resolution:
        The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

        AC Volts ___Code     AC Volts ___Code
        12 ___ J7                   208 ___ LE7
        21 ___ Z7                   220 ___ M7
        24 ___ B7                  230 ___ P7
        32 ___ C7                  240 ___ U7
        36 ___ CC7               277 ___ W7
        42 ___ D7                  380 ___ Q7
        48 ___ E7                   400 ___ V7
        60 ___ EE7                415 ___ N7
        100 ___ K7                440 ___ R7
        110 ___ F7                480 ___ T7
        115 ___ FE7              575 ___ SC7
        120 ___ G7                600 ___ X7
        127 ___ FC7              690 ___ Y7
        200 ___ L7                
                       
        Standard Coil                Low Consumption
        DC Volts ___Code          DC Volts ___Code
        12 ___ JD                           5 ___ AL
        24 ___ BD                         12 ___ JL
        36 ___ CD                         20 ___ ZL
        48 ___ ED                         24 ___ BL
        60 ___ ND                         48 ___ EL
        72 ___ SD                         72 ___ SL
        110 ___ FD                       96 ___ DL
        125 ___ GD                     110 ___ FL
        220 ___ MD                    220 ___ ML
        250 ___ UD                     250 ___ UL
        440 ___ RD                
        Show More