Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 with cover
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 without cover
TeSys auxiliary contactor CAD
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 with cover
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 without cover
TeSys auxiliary contactor CAD

TeSys D Control Relay, 5 NO, <= 690V, 500VAC, Standard Coil

Catalogue Number: CAD50S7
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 with cover
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 without cover
TeSys auxiliary contactor CAD
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 with cover
Control relay for connection by screw clamp terminal or lug CAD50 or CAD506 without cover
TeSys auxiliary contactor CAD
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D control relay
Range
TeSys
Product name
TeSys CAD
Product or component type
control relay
Device short name
CAD
Contactor application
control circuit
Utilisation category
  • AC-15
  • AC-14
  • DC-13
    • Pole contact composition
      5 NO
      [Ue] rated operational voltage
      <= 690 V AC 25...400 Hz
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      500 V AC 50/60 Hz
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      [Ith] conventional free air thermal current
      10 A (at 60 °C)
      Irms rated making capacity
    • 140 A AC conforming to IEC 60947-5-1
    • 250 A DC conforming to IEC 60947-5-1
      • [Icw] rated short-time withstand current
      • 100 A - 1 s
      • 120 A - 500 ms
      • 140 A - 100 ms
        • Associated fuse rating
          10 A gG conforming to IEC 60947-5-1
          [Ui] rated insulation voltage
        • 600 V UL certified
        • 600 V CSA certified
        • 690 V conforming to IEC 60947-5-1
          • Mounting support
          • plate
          • rail
            • Connections - terminals
            • screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • Tightening torque
              • 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                • Control circuit voltage limits
                • operational: 0.8...1.1 Uc at 50 Hz
                • operational: 0.85...1.1 Uc at 60 Hz
                • drop-out: 0.3...0.6 Uc
                  • Operating time
                  • 12...22 ms coil energisation and NO closing
                  • 4...12 ms coil de-energisation and NO opening
                    • Mechanical durability
                      30 Mcycles
                      Maximum operating rate
                      180 cyc/mn
                      Inrush power in VA
                      70-70 VA 50 Hz (at 20 °C)
                      Hold-in power consumption in VA
                      8-8 VA 50 Hz (at 20 °C)
                      Minimum switching voltage
                      17 V
                      Minimum switching current
                      5 mA
                      Non-overlap time
                    • 1.5 ms on energisation between NC and NO contact
                    • 1.5 ms on de-energisation between NC and NO contact
                      • Insulation resistance
                        > 10 MOhm
                        Mechanical robustness
                      • shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                      • shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                      • vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                      • vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • Height
                          77 mm
                          Width
                          45 mm
                          Depth
                          84 mm
                          Net weight
                          0.58 kg
                          Compatibility code
                          CAD
                          Standards
                        • BS 4794
                        • EN 60947-5
                        • IEC 60947-5-1
                        • NF C 63-140
                        • VDE 0660
                          • Product certifications
                          • UL
                          • CSA
                            • IP degree of protection
                              IP2x front face conforming to VDE 0106
                              Protective treatment
                              TH conforming to IEC 60068
                              Ambient air temperature for operation
                              -40-70 °C
                              Ambient air temperature for storage
                              -60-80 °C
                              Operating altitude
                              3000 m without
                              Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Compliant
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              Product out of China RoHS scope. Substance declaration for your information
                              Environmental Disclosure
                              ENVPEP110229EN
                              Circularity Profile
                              ENVEOLI1102029EN
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              California proposition 65
                              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                              Warranty
                              18 months

                              Frequently Asked Questions

                              hide show

                              What is the replacement code for CA2DN40U5

                              The replacement part code is CAD50U7

                              What is the rating for a CAD50U7

                               The rating is 10A

                              What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                              Issue:
                              Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                              Product Line:
                              CAD Industrial Relays

                              Environment:
                              Relays and Timers

                              Resolution:
                              Inductive:
                              125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                              250V DC - 0.27 Amps make and break, 2.5 amps cont.
                              600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                               

                              Is the coil on CAD50BL polarity sensitive?

                              Issue:
                              Is the coil on CAD50BL polarity sensitive? 
                              Product Line:
                              Industrial Relays
                              Environment:
                              Tesys D IEC Style Relays
                              Cause:
                              Determine if relay will work for a specific application.                                     
                              Resolution:                                                                 
                              Yes, the DC coil is polarity sensitive - A1 is positive and A2 is negative.
                               

                              What is the power terminal lug data for the LC1D40, LC1D50, LC1D65, LP1D40, LP1D50, and LP1D65 contactor?

                              Issue:
                              Identifying power terminal lug data for the D2 style contactors

                              Product Line:
                              Tesys D line contactors

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Power terminal lug data required

                              Resolution:
                              For contactors with screw clamp terminals:
                              stranded cable w/o cable end : One #10-3 AWG or Two #10-4 AWG per terminal.
                              stranded cable w/cable end: One #10-4 AWG or Two #12-2 AWG per terminal.
                              solid cable: One #10-3 AWG or Two #10-6 AWG per terminal.

                              What is the altitude derating for a TeSys D-Line contactor?

                              Issue:​
                              What is the altitude derating for a TeSys D-Line contactor?

                              Product Line:
                              Digest 177 Section 18 : Contactors and Starters, IEC

                              Environment:
                              North American Products

                              Resolution:
                              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                              Voltage
                              3500m x 0.90
                              4000m x 0.80
                              4500m x 0.70
                              5000m x 0.60

                              Current
                              3500m x 0.92
                              4000m x 0.90
                              4500m x 0.88
                              5000m x 0.86

                              For example, an LC1D80 at 5000 meters:
                              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                               

                              What safety category rating do the CAD TeSys relays meet under IEC EN954-1? Do they have linked contacts?

                              Issue:
                              Safety category listing of CAD TeSys relays

                              Product Line:
                              Relays

                              Environment:
                              TeSys D Relays

                              Resolution:
                              ​The Tesys CAD32** and the CAD50** relays and top mounted adder decks have positively guided or linked contacts.  Therefore the contacts meet IEC EN60947-5-1 and are approved to use in safety systems through category 4.

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              What is the replacement AC coil for CAD32 and CAD50 relay?

                              Issue:
                              AC coil replacement for CAD32 and CAD50

                              Product Line:
                              Relays

                              Environment:
                              Tesys CAD Control Relays

                              Cause:
                              Product selection

                              Resolution:
                              Volt = coil part number
                              12 = LXD1J7
                              21 = LXD1Z7
                              24 = LXD1B7
                              32 = LXD1C7
                              36 = LXD1CC7
                              42 = LXD1D7
                              48 = LXD1E7
                              60 = LXD1EE7
                              100 = LXD1K7
                              110 = LXD1F7
                              115 = LXD1FE7
                              120 = LXD1G7
                              127 = LXD1FC7
                              200 = LXD1L7
                              208 = LXD1LL7
                              220/230 = LXD1M7
                              230 595 21 LXD1P7
                              230/240 = LXD1U7
                              277 781 30 LXD1W7
                              380/400 = LXD1Q7
                              400 = LXD1V7
                              415 = LXD1N7
                              440 = LXD1R7
                              480 = LXD1T7
                              600 = LXD1X7
                              690 = LXD1Y7

                               

                              What is difference between LC1D50U7 and LC1D50AU7?

                              Following are the differences between the LC1D50U7 and the LC1D50AU7:

                              LC1D50AU7 has everlink terminals.
                              LC1D50AU7....is slightly larger case and accommodate LRD3XX overloads
                              Whereas
                              LC1D50U7 contactors accommodate LRD33XX overloads.

                               

                              What reference do I add to the CAD32 or CAD50 to sepcify the coil voltage?

                              Add one of the codes listed in bold below to the end of the code. For example a 24V AC CAD32 would be CAD32B7

                              AC | 24V = B7 | 110V = F7 | 240V = U7 | 415V = N7
                              DC | 24V = BD

                              What is the equivalent for CS722E240 Sprecher & Schuh Relay?

                              The equivalent for CS722E240 Sprecher Schuh Relay is a CAD32U7 or LC1D098U7 can be used.

                               
                              Show More