Frequently Asked Questions
hide
show
What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?
Issue:
Checking on the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay.
Product Line:
CAD Industrial Relays
Environment:
Relays and Timers
Resolution:
Inductive:
125V DC - 0.55 Amps make and break, 2.5 Amps cont.
250V DC - 0.27 Amps make and break, 2.5 amps cont.
600V DC - 0.10 Amps make and break, 2.5 Amps cont.
What is the replacement code for CA2DN40U5
The replacement part code is CAD50U7
What is the rating for a CAD50U7
The rating is 10A
Is the coil on CAD50BL polarity sensitive?
Issue:
What is the hot and neutral on the coil terminals for CAD50BL?
Product Line:
Industrial Relays
Environment:
Tesys D IEC Style Relays
Cause:
Determine if relay will work for a specific application.
Resolution:
Yes, the DC coil is polarity sensitive - A1 is positive and A2 is negative.
What safety category rating do the CAD TeSys relays meet under IEC EN954-1? Do they have linked contacts?
Issue:
Safety category listing of CAD TeSys relays
Product Line:
Relays
Environment:
TeSys D Relays
Resolution:
The Tesys CAD32** and the CAD50** relays and top mounted adder decks have positively guided or linked contacts. Therefore the contacts meet IEC EN60947-5-1 and are approved to use in safety systems through category 4.
What is the replacement AC coil for CAD32 and CAD50 relay?
Issue:
AC coil replacement for CAD32 and CAD50
Product Line:
Relays
Environment:
Tesys CAD Control Relays
Cause:
Product selection
Resolution:
Volt = coil part number
12 = LXD1J7
21 = LXD1Z7
24 = LXD1B7
32 = LXD1C7
36 = LXD1CC7
42 = LXD1D7
48 = LXD1E7
60 = LXD1EE7
100 = LXD1K7
110 = LXD1F7
115 = LXD1FE7
120 = LXD1G7
127 = LXD1FC7
200 = LXD1L7
208 = LXD1LL7
220/230 = LXD1M7
230 595 21 LXD1P7
230/240 = LXD1U7
277 781 30 LXD1W7
380/400 = LXD1Q7
400 = LXD1V7
415 = LXD1N7
440 = LXD1R7
480 = LXD1T7
600 = LXD1X7
690 = LXD1Y7
Show More