Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 with cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 without cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 with cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 without cover

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 415VAC, Standard coil

Catalogue Number: CAD32N7
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 with cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 without cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 with cover
Control relay for connection by screw clamp terminal or lug CAD32 or CAD326 without cover
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys D control relay
Range
TeSys
Product name
TeSys CAD
Product or component type
control relay
Device short name
CAD
Contactor application
control circuit
Utilisation category
  • AC-14
  • DC-13
  • AC-15
    • Pole contact composition
      3 NO + 2 NC
      [Ue] rated operational voltage
      <= 690 V AC 25...400 Hz
      Control circuit type
      AC at 50/60 Hz
      [Uc] control circuit voltage
      415 V AC 50/60 Hz
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947
      [Ith] conventional free air thermal current
      10 A (at 60 °C)
      Irms rated making capacity
    • 140 A AC conforming to IEC 60947-5-1
    • 250 A DC conforming to IEC 60947-5-1
      • [Icw] rated short-time withstand current
      • 100 A - 1 s
      • 120 A - 500 ms
      • 140 A - 100 ms
        • Associated fuse rating
          10 A gG conforming to IEC 60947-5-1
          [Ui] rated insulation voltage
        • 600 V UL certified
        • 600 V CSA certified
        • 690 V conforming to IEC 60947-5-1
          • Mounting support
          • rail
          • plate
            • Connections - terminals
            • screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
            • screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
            • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
            • screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
            • screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
              • Tightening torque
              • 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
              • 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                • Control circuit voltage limits
                • operational: 0.8...1.1 Uc at 50 Hz
                • operational: 0.85...1.1 Uc at 60 Hz
                • drop-out: 0.3...0.6 Uc
                  • Operating time
                  • 12...22 ms coil energisation and NO closing
                  • 4...12 ms coil de-energisation and NO opening
                  • 4...19 ms coil energisation and NC opening
                  • 6...17 ms coil de-energisation and NC closing
                    • Mechanical durability
                      30 Mcycles
                      Maximum operating rate
                      180 cyc/mn
                      Inrush power in VA
                      70-70 VA 50 Hz (at 20 °C)
                      Hold-in power consumption in VA
                      8-8 VA 50 Hz (at 20 °C)
                      Minimum switching voltage
                      17 V
                      Minimum switching current
                      5 mA
                      Non-overlap time
                    • 1.5 ms on energisation between NC and NO contact
                    • 1.5 ms on de-energisation between NC and NO contact
                      • Insulation resistance
                        > 10 MOhm
                        Mechanical robustness
                      • shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                      • shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                      • vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                      • vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • Height
                          77 mm
                          Width
                          45 mm
                          Depth
                          84 mm
                          Net weight
                          0.58 kg
                          Compatibility code
                          CAD
                          Standards
                        • BS 4794
                        • EN 60947-5
                        • IEC 60947-5-1
                        • NF C 63-140
                        • VDE 0660
                          • Product certifications
                          • CSA
                          • UL
                            • IP degree of protection
                              IP2x front face conforming to VDE 0106
                              Protective treatment
                              TH conforming to IEC 60068
                              Ambient air temperature for operation
                              -40-70 °C
                              Ambient air temperature for storage
                              -60-80 °C
                              Operating altitude
                              3000 m without
                              Sustainable offer status
                              Green Premium product
                              REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Compliant
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              Product out of China RoHS scope. Substance declaration for your information
                              Environmental Disclosure
                              ENVPEP110230EN
                              Circularity Profile
                              ENVEOLI1102030EN
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Frequently Asked Questions

                              hide show

                              Are replacement contacts available for a CAD32 relay?

                              Issue:
                              Contacts need to be replaced in a CAD32** relay.

                              Product Line:
                              TeSys D IEC style relays

                              Environment:
                              CAD relays

                              Resolution:
                              The TeSys D IEC style relays do not offer replacement parts.  Replace entire device.

                              What is the replacement coil part number for the LC*D09 through LC*D32 and LC*DT20 through LC*DT40 TeSys contactors?

                              Issue:
                              Identifying replacement coils for tesys D non-reversing and reversing conactors

                              Product Line:
                              IEC Contactors and Starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Replacement coil is needed

                              Resolution:
                              DC replacement coils are not available.
                              AC Coils are 50/60 hertz for voltages as listed below:

                              Volts - Part Number
                              12 ____ LXD1J7
                              21 ____ LXD1Z7
                              24 ____ LXD1B7
                              32 ____ LXD1C7
                              36 ____ LXD1CC7
                              42 ____ LXD1D7
                              48 ____ LXD1E7
                              60 ____ LXD1EE7
                              100 ___ LXD1K7 ( never brought to North America )
                              110 ___ LXD1F7
                              115 ___ LXD1FE7
                              120 ___ LXD1G7
                              127 ___ LXD1FC7
                              200 ___ LXD1L7
                              208 ___ LXD1LE7
                              220 ___ LXD1M7
                              230 ___ LXD1P7
                              240 ___ LXD1U7
                              277 ___ LXD1W7
                              380 ___ LXD1Q7
                              400 ___ LXD1V7
                              415 ___ LXD1N7
                              440 ___ LXD1R7
                              480 ___ LXD1T7
                              575 ___ LXD1SC7
                              600 ___ LXD1X7
                              690 ___ LXD1Y7


                              Note: A contactor with an AC coil can be changed to a different AC voltage coil, IE you can take an LC1D09 with a 120VAC coil and put a 24VAC coil in it instead. An AC device cannot be switched to a DC coil, and a DC device cannot be switches to an AC coil. 

                              Where are the control coil terminals for TeSys LC1D09 to LC1D38 contactor?

                              Issue:
                              Determine the control coil terminal marking and location on LC1D09 to LC1D38 contactor

                              Product Line: 
                              Tesys D Contactors

                              Environment:
                              IEC contactors

                              Resolution:
                              The coil terminals are marked A1 and A2, you can see them on the front of the contactor on the white part (control section).  They are next to the auxiliary contact (13/14, 21/22) terminals.
                               

                              What is the equivalent for CS722E240 Sprecher & Schuh Relay?

                              The equivalent for CS722E240 Sprecher Schuh Relay is a CAD32U7 or LC1D098U7 can be used.

                               

                              What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                              Issue:
                              Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                              Product Line:
                              CAD Industrial Relays

                              Environment:
                              Relays and Timers

                              Resolution:
                              Inductive:
                              125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                              250V DC - 0.27 Amps make and break, 2.5 amps cont.
                              600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                               

                              What is the replacement for a CA3KN313BD needed

                               Use a CAD32BD

                              Will the LA4DC1U work with the new CAD32BD relay?

                              Issue:
                              Will the LA4DC1U work on the CAd32BD relay

                              Product Line:
                              IEC relays and accessories

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying product compatibility

                              Resolution:
                              The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.


                              CTA-ID : 2031917

                              Is the CAD32 Force guided? Are the contacts mechanically linked?

                              Issue:
                              How do the contacts on the CAD32 work

                              Product Line:
                              Relays and Timers

                              Environment:
                              North American Products
                                                                
                              Resolution:                                                                 
                              The CAD32 relays are force guided, and the contacts are mechanically linked.
                               

                              What is the replacement for the CA3DK22BD?

                              Issue:
                              What is the replacement for the CA3DK22BD?

                              Product Line:
                              Relays and Timers

                              Environment:
                              Obsolete Products

                              Cause:
                              Legacy Replacement

                              Resolution:
                              The CA3DK is Obsolete. To electrically replace it, use a CAD32BD & a LAD6K10B
                               

                              What is the altitude derating for a TeSys D-Line contactor?

                              Issue:​
                              What is the altitude derating for a TeSys D-Line contactor?

                              Product Line:
                              Digest 177 Section 18 : Contactors and Starters, IEC

                              Environment:
                              North American Products

                              Resolution:
                              The contactors are fully rated up to 3000 meters. Following are derating multipliers for altitudes above 3000 meters for both voltage and current:

                              Voltage
                              3500m x 0.90
                              4000m x 0.80
                              4500m x 0.70
                              5000m x 0.60

                              Current
                              3500m x 0.92
                              4000m x 0.90
                              4500m x 0.88
                              5000m x 0.86

                              For example, an LC1D80 at 5000 meters:
                              - The maximum rated operational voltage is 1,000V (IEC947-4) and 690V (UL/CSA). At 5000 meters it becomes 1000V x 0.6 = 600V (IEC947-4) and 690V x 0.6 = 414V (UL/CSA).
                              - The maximum rated operational AC3 current is 80A. At 5000 meters it becomes 80A x 0.86 = 68A.



                               

                              What is the part number for a 3 pole 32amp 415VAC coil contactor and overload?

                              The part number for a 3 pole 32amp 415VAC coil contactor and overload is - LC1D32N7 & LRD32

                              For further information , visit links below:-
                              https://www.schneider-electric.com.au/en/search/LC1D32N7
                              https://www.schneider-electric.com.au/en/search/LRD32

                              User-added image

                              What is the 480V coil for a CA2DN31T6 IEC Relay?

                              Issue:
                              What is the 480V coil for a CA2DN31T6 IEC Relay?

                              Product Line:
                              Tesys Relays

                              Environment:
                              Obsolete relays

                              Cause:
                              Product selection

                              Resolution:
                              The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


                              CTA-ID : 2048217

                              What safety category rating do the CAD TeSys relays meet under IEC EN954-1? Do they have linked contacts?

                              Issue:
                              Safety category listing of CAD TeSys relays

                              Product Line:
                              Relays

                              Environment:
                              TeSys D Relays

                              Resolution:
                              ​The Tesys CAD32** and the CAD50** relays and top mounted adder decks have positively guided or linked contacts.  Therefore the contacts meet IEC EN60947-5-1 and are approved to use in safety systems through category 4.

                              What is the part number for LC1D32 contactor with 380V AC Coil?

                              The part number for LC1D32 contactor with 380V AC Coil is LC1D32N7.
                              Even though the LC1D32N7 has a 415V AC coil the coil has + or -  10% rating making the coil range 373.5 - 456.5V AC which is suitable for 380V AC.

                              For more information see:
                              https://www.schneider-electric.com/en/product-range-selector/664-tesys-d/?p_url=http%3A%2F%2Fwww.ops-ecat.schneider-electric.com%2Fecatalogue%2Fbrowse.do%3Fel_typ%3Dproduct%26cat_id%3DBU_POW_664_L3%26prd_id%3DLC1D32N7%26scp_id%3DZ000

                              What is the replacement code for CA2DN40U5

                              The replacement part code is CAD50U7

                              What is the rating for a CAD50U7

                               The rating is 10A

                              Does CAD32 come with Cat 3 certification?

                              No it does not.
                              Please refer the below link
                              https://www.dguv.de/ifa/Praxishilfen/Software/SISTEMA/index-2.jsp

                              What is the maximum UL/CSA AC voltage rating of the LC1D power contacts ?

                              Issue:
                              Identifying maximum voltage of an LC1D contactor

                              Product Line:
                              TeSys D Contactors

                              Environment:
                              IEC contactors and starters used in North America

                              Cause:
                              n/a

                              Resolution:
                              IThe maximum voltage per UL and CSA is 600VAC. 
                               

                              What is the mechanical interlock for an LC1D32U7

                               The LAD9R1V reverser kit contains the mechanical interlock you need for the LC1D32U7

                              What is the Coil control circuit voltage limit for the LC1D32D7 Contactor?

                              The control circuit voltage limit for the 42V AC Coil on the LC1D32D7 Contactor is 0.8...1.1 Uc (0.8...1.1 x 42V AC) operational at 60 °C, AC 50 Hz

                              https://www.schneider-electric.com.au/en/search/LC1D32D7

                              What is the replacement AC coil for CAD32 and CAD50 relay?

                              Issue:
                              AC coil replacement for CAD32 and CAD50

                              Product Line:
                              Relays

                              Environment:
                              Tesys CAD Control Relays

                              Cause:
                              Product selection

                              Resolution:
                              Volt = coil part number
                              12 = LXD1J7
                              21 = LXD1Z7
                              24 = LXD1B7
                              32 = LXD1C7
                              36 = LXD1CC7
                              42 = LXD1D7
                              48 = LXD1E7
                              60 = LXD1EE7
                              100 = LXD1K7
                              110 = LXD1F7
                              115 = LXD1FE7
                              120 = LXD1G7
                              127 = LXD1FC7
                              200 = LXD1L7
                              208 = LXD1LL7
                              220/230 = LXD1M7
                              230 595 21 LXD1P7
                              230/240 = LXD1U7
                              277 781 30 LXD1W7
                              380/400 = LXD1Q7
                              400 = LXD1V7
                              415 = LXD1N7
                              440 = LXD1R7
                              480 = LXD1T7
                              600 = LXD1X7
                              690 = LXD1Y7

                               

                              What reference do I add to the CAD32 or CAD50 to sepcify the coil voltage?

                              Add one of the codes listed in bold below to the end of the code. For example a 24V AC CAD32 would be CAD32B7

                              AC | 24V = B7 | 110V = F7 | 240V = U7 | 415V = N7
                              DC | 24V = BD

                              What does LAD93217 kit come with?

                              Need a LC2D323U7 reversing contactor

                              Use 2 x LC1D32U7 with a LAD9R1V reversing wiring kit

                              What is the code for a spare coil for LC1D32B7

                              LXD1B7

                              What is the code for a 32Amp 24VAC 3 Pole Contactor ?

                              LC1D32B7

                              What is the part number for mechanical interlock for 2 x LC1D32U7 contactors?

                              The part number for a mechanical interlock for 2 x LC1D32U7 contactors is - LAD9V2

                              For further information , visit link below:-
                              https://www.schneider-electric.com.au/en/search/LAD9V2

                              ​Is there an alternative C-Bus Switch for C5032NL-WE?

                              Yes, one off C2032VH + one off 5031NMML + one off 5031NMS

                              On a TeSys D or TeSys IEC relay, is there a top mounting provision that will allow you to relocate the A1 & A2 terminals from the right side to the top?

                              Issue:
                              On a TeSys D or TeSys IEC relay, is there a top mounting provision that will allow you to relocate the A1 & A2 terminals from the right side to the top?

                              Product Line:
                              TeSys D LC1D09-LC1D65A, TeSys IEC relay CAD**

                              Environment:
                              CAD, LC1D

                              Cause:
                              Assembly/wiring

                              Resolution:
                              The current TeSys IEC D line contactors ( LC1D09-LC1D65A) and the  TeSys IEC  Relay (CAD**) have A1 and A2 Terminals located on the right side of the device. To relocate the A1 & A2 Terminals, consider using the LAD4BB top-mounting wiring accessory.  Please note this device can only be used on the D line contactors or the IEC relays that are provided with AC coils. A mounting accessory for units with a DC coil is not available.

                              How many normally opened contacts in a CAD32JL?

                              Control Circuit: AC, DC or LC (Low Consumption)
                              Model D Relay 5-Pole (10 Amp)
                              Type: Instantaneous
                              Number of contacts: 5
                              Composition N/O: 3
                              Composition N/C: 2
                              Coil voltages (1)

                              For further information please visit

                              What will be the replacement on CA2DN Series?

                              Has been replaced by CAD32 series.
                              Please refer the following site for more information
                              https://www.ops-ecat.schneider-electric.com/ecat/browse.do?conf=seo_US&el_typ=product&prd_id=CAD32BD&scp_id=US_en
                              User-added image

                              What is the code for a 24 v ac coil to suit a LC1D32 contactor?

                              LXD1B7 is the code for the 24VAC coil for contactors LC1D09...38.

                              The code for complete contactor + 24VAC coil is LC1D32B7

                              Is the coil on CAD50BL polarity sensitive?

                              Issue:
                              Is the coil on CAD50BL polarity sensitive? 
                              Product Line:
                              Industrial Relays
                              Environment:
                              Tesys D IEC Style Relays
                              Cause:
                              Determine if relay will work for a specific application.                                     
                              Resolution:                                                                 
                              Yes, the DC coil is polarity sensitive - A1 is positive and A2 is negative.
                               

                              What are force guided contacts?

                              Issue:
                              What does force guided contacts mean for Contactors and Relays ?

                              Product Line:
                              Relays

                              Environment:
                              Features

                              Cause:
                              Definition needed

                              Resolution:
                              Linked contacts are contacts which are mechanically linked in such a way as to ensure that the normally closed and normally open contacts can never be closed at the same time.

                              Mechanical guiding (forced guiding) makes it impossible to close the normally closed and normally open contact simultaneously. If a normally closed contact becomes welded, it must be impossible for the normally open contacts to close when the coil is energized.
                              If a normally open contact becomes welded, it must be impossible for the normally closed contacts to close when the coil is de-energized. Also known as: forced contacts, positively activated contacts, guided contacts, and linked contacts.

                              This Forced guided contact feature is primarily required for Safety circuits and redundant control systems .

                               

                              What is the difference between the LAD4TB and LAD4TBDL bi-directional peak limiting diode?

                              Issue:
                              Identifying the difference between LAD4TB and LAD4TBDL

                              Product Line:
                              IEC contactors and starters

                              Environment:
                              Products sold and used in the United States

                              Cause:
                              Identifying the difference between two similar part numbers

                              Resolution:
                              The LAD4TB is for 24V AC coils for the Tesys Series LC1D09 through LC1D38 contactors when supplied with G7 voltage code. The LAD4TBDL is 24 vdc bi-directional diode offered as a replacement if for some reason the diode supplied with the Tesys LC1D09 through LC1D38 contactors when ordered with BD or BL voltage code breaks or is no longer working.