Quantcast

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 96VDC, Standard Coil

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 96VDC, Standard Coil

TeSys D Control Relay, 3 NO + 2 NC, <= 690V, 96VDC, Standard Coil

Item Number: CAD32DD

Retail
N/A
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height77 mm

Depth icon

Depth93 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys D control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V AC 25...400 Hz

Mounting support

  • plate
  • rail
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 1-2.5 mm²flexible with cable end
    • screw clamp terminals 1 cable(s) 1-4 mm²solid without cable end
    • screw clamp terminals 2 cable(s) 1-4 mm²solid without cable end
      • Mechanical durability

        30 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        77 mm

        Width

        45 mm

        Depth

        93 mm

        Net weight

        0.58 kg

        Standards

      • BS 4794
      • EN 60947-5
      • IEC 60947-5-1
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • CSA
        • UL
          • IP degree of protection

            IP2x front face conforming to VDE 0106

            Ambient air temperature for operation

          • -40-60 °C
          • 60-70 °C with derating
            • Ambient air temperature for storage

              -60-80 °C

              REACh Regulation

              Free of Substances of Very High Concern above the threshold

              EU RoHS Directive

              Compliant

              Mercury free

              Yes

              RoHS exemption information

              Yes

              China RoHS Regulation

              Product out of China RoHS scope. Substance declaration for your information

              Environmental Disclosure

              ENVPEP110230EN

              Circularity Profile

              ENVEOLI1102030EN

              California proposition 65

              WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

              Others

              Package 1 Height

              0.49 dm

              Package 1 Length

              0.89 dm

              Package 1 width

              1.11 dm

              Product name

              TeSys CAD

              Device short name

              CAD

              Contactor application

              control circuit

              Utilisation category

            • AC-14
            • AC-15
            • DC-13
              • Pole contact composition

                3 NO + 2 NC

                Control circuit type

                DC standard

                [Uc] control circuit voltage

                96 V DC

                [Uimp] rated impulse withstand voltage

                6 kV conforming to IEC 60947

                [Ith] conventional free air thermal current

                10 A (at 60 °C)

                Irms rated making capacity

              • 140 A AC conforming to IEC 60947-5-1
              • 250 A DC conforming to IEC 60947-5-1
                • [Icw] rated short-time withstand current

                • 100 A - 1 s
                • 120 A - 500 ms
                • 140 A - 100 ms
                  • Associated fuse rating

                    10 A gG conforming to IEC 60947-5-1

                    [Ui] rated insulation voltage

                  • 600 V UL certified
                  • 600 V CSA certified
                  • 690 V conforming to IEC 60947-5-1
                    • Tightening torque

                    • 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2
                    • 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                      • Control circuit voltage limits

                      • 0.1...0.25 Uc (-40-70 °C):drop-out DC
                      • 0.7...1.25 Uc (-40-60 °C):operational DC
                      • 1...1.25 Uc (60-70 °C):operational DC
                        • Operating time

                        • 53...72 ms coil energisation and NO closing
                        • 16...24 ms coil de-energisation and NO opening
                        • 47...63 ms coil energisation and NC opening
                        • 15...25 ms coil de-energisation and NC closing
                          • Maximum operating rate

                            180 cyc/mn

                            Time constant

                            28 ms

                            Inrush power in W

                            5.4-5.4 W (at 20 °C)

                            Hold-in power consumption in W

                            5.4-5.4 W at 20 °C

                            Minimum switching voltage

                            17 V

                            Minimum switching current

                            5 mA

                            Non-overlap time

                          • 1.5 ms on energisation between NC and NO contact
                          • 1.5 ms on de-energisation between NC and NO contact
                            • Mechanical robustness

                            • shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                            • shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                            • vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                            • vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                              • Compatibility code

                                CAD

                                Protective treatment

                                TH conforming to IEC 60068

                                Operating altitude

                                0...3000 m

                                Package 1 Weight

                                0.392 kg

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                Show all specifications

                                Frequently Asked Questions

                                hide show

                                Are replacement contacts available for a CAD32 relay?

                                Issue:
                                Contacts need to be replaced in a CAD32** relay.

                                Product Line:
                                TeSys D IEC style relays

                                Environment:
                                CAD relays

                                Resolution:
                                The TeSys D IEC style relays do not offer replacement contacts.

                                What is the replacement for a CA3KN313BD needed

                                 Use a CAD32BD

                                Will the LA4DC1U work with the new CAD32BD relay?

                                Issue:
                                Will the LA4DC1U work on the CAd32BD relay

                                Product Line:
                                IEC relays and accessories

                                Environment:
                                Products sold and used in the United States

                                Cause:
                                Identifying product compatibility

                                Resolution:
                                The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.


                                CTA-ID : 2031917

                                What does the "6" mean in a CAD326 control relay?

                                Issue:
                                What does the "6" form stand for

                                Product Line:
                                TeSys D IEC control relays 

                                Environment:
                                IEC Style control relays

                                Resolution:
                                The "6" means it has a binder head screw termination.
                                 

                                What is the replacement for the CA3DK22BD?

                                Issue:
                                What is the replacement for the CA3DK22BD?

                                Product Line:
                                Relays and Timers

                                Environment:
                                Obsolete Products

                                Cause:
                                Legacy Replacement

                                Resolution:
                                The CA3DK is Obsolete. To electrically replace it, use a CAD32BD & a LAD6K10B
                                 

                                What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                                Issue:
                                Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                                Product Line:
                                CAD Industrial Relays

                                Environment:
                                Relays and Timers

                                Resolution:
                                Inductive:
                                125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                                250V DC - 0.27 Amps make and break, 2.5 amps cont.
                                600V DC - 0.10 Amps make and break, 2.5 Amps cont.
                                Show More