Are replacement contacts available for a CAD32 relay?
Issue:
Contacts need to be replaced in a CAD32** relay.
Product Line:
TeSys D IEC style relays
Environment:
CAD relays
Resolution:
The TeSys D IEC style relays do not offer replacement contacts.
What is the replacement for a CA3KN313BD needed
Use a CAD32BD
Will the LA4DC1U work with the new CAD32BD relay?
Issue:
Will the LA4DC1U work on the CAd32BD relay
Product Line:
IEC relays and accessories
Environment:
Products sold and used in the United States
Cause:
Identifying product compatibility
Resolution:
The CAD32BD with DC coil has built-in coil suppression protection as standard so the LA4DC1U is not needed.
CTA-ID : 2031917
What does the "6" mean in a CAD326 control relay?
Issue:
What does the "6" form stand for
Product Line:
TeSys D IEC control relays
Environment:
IEC Style control relays
Resolution:
The "6" means it has a binder head screw termination.
Is the CAD32 Force guided? Are the contacts mechanically linked?
Issue:
How do the contacts on the CAD32 work
Product Line:
Relays and Timers
Environment:
Tesys D control relay
Resolution:
The CAD32 relays are force guided, and the contacts are mechanically linked.
What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?
Issue:
Checking on the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay.
Product Line:
CAD Industrial Relays
Environment:
Relays and Timers
Resolution:
Inductive:
125V DC - 0.55 Amps make and break, 2.5 Amps cont.
250V DC - 0.27 Amps make and break, 2.5 amps cont.
600V DC - 0.10 Amps make and break, 2.5 Amps cont.