Control Relay

Product Dimensions

Width icon

Width27 mm

Height icon

Height56 mm

Depth icon

Depth55.5 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Warranty

18 months

Range of product

TeSys SK control relay

Range

TeSys

Product or component type

control relay

Physical

Mercury free

Yes

REACh Regulation

Reference contains Substances of Very High Concern above the threshold

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

EU RoHS Directive

Compliant

RoHS exemption information

Yes

[Ue] rated operational voltage

<= 690 V <= 400 Hz

Mounting support

  • rail
  • plate
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1.5-6 mm²solid
    • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 1 cable(s) 0.5-6 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 0.35-6 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.35-1.5 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.35-2.5 mm²flexible without cable end
      • Mechanical durability

        10 Mcycles

        Height

        56 mm

        Width

        27 mm

        Depth

        55.5 mm

        Net weight

        0.132 kg

        Standards

      • VDE 0660
      • BS 5424
      • NF C 63-110
      • IEC 60947
        • Product certifications

          cULus

          IP degree of protection

          IP2x

          Ambient air temperature for operation

          -20-50 °C

          Ambient air temperature for storage

          -50-70 °C

          Others

          Package 1 Height

          3.5 cm

          Package 1 Length

          6.5 cm

          Package 1 Weight

          124 g

          Package 1 width

          6 cm

          Package 2 Height

          15 cm

          Package 2 Length

          40 cm

          Package 2 Weight

          4.988 kg

          Package 2 width

          15 cm

          Number of Units in Package 1

          1

          Number of Units in Package 2

          40

          Unit Type of Package 1

          PCE

          Unit Type of Package 2

          S01

          WEEE

          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

          Product name

          TeSys CASK

          Device short name

          CA3SK

          Contactor application

          control circuit

          Utilisation category

        • DC-13
        • AC-15
          • Pole contact composition

            1 NO + 1 NC

            Control circuit type

            DC standard

            [Uc] control circuit voltage

            24 V DC

            [Ith] conventional free air thermal current

            10 A (at 55 °C)

            Associated fuse rating

          • 10 A gL conforming to VDE 0660
          • 10 A gL conforming to IEC 60947
            • [Ui] rated insulation voltage

            • 690 V conforming to IEC 60947
            • 690 V conforming to VDE 0110 group C
            • 690 V conforming to BS 5424
            • 690 V conforming to UL 508
            • 690 V conforming to CSA C22.2 No 14
              • Tightening torque

                0.8 N.m - on screw clamp terminals pozidriv No 1 screw head

                Control circuit voltage limits

              • operational: 0.85...1.1 Uc (at <50 °C)
              • drop-out: 0.1...0.75 Uc (at <50 °C)
                • Operating time

                • 4...6 ms coil de-energisation and NO opening
                • 8...12 ms coil energisation and NO closing
                • 6...8 ms coil de-energisation and NC closing
                • 10...18 ms coil energisation and NC opening
                  • Maximum operating rate

                    1200 cyc/h

                    Inrush power in W

                    2.2-2.2 W (at 20 °C)

                    Hold-in power consumption in W

                    2.2-2.2 W at 20 °C

                    Heat dissipation

                    2.2-2.2 W

                    Compatibility code

                    CA3SK

                    Protective treatment

                    TC conforming to IEC 60068

                    Operating altitude

                    2000 m without derating
                    Show all specifications

                    Frequently Asked Questions

                    hide show

                    Is the CA3SK20BD still available?

                    Yes it is still available.

                    What is the replacement coil for a CA3DN31BD relay?

                    Issue:
                    What is the replacement coil for a CA3DN31BD  relay?

                    Product Line:
                    Relays and Timers

                    Environment:
                    All Products

                    Cause:
                    Product selection

                    Resolution:
                    Use an LX4D2BD.
                     

                    What is the replacement for a CA3KN313BD needed

                     Use a CAD32BD

                    Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                    Issue:
                    Why will LA1SK11 adder deck not fit on CA2SK11 relay?

                    Product Line:
                    Tesys Relays

                    Environment:
                    All Products

                    Cause:
                    Product Features

                    Resolution:
                    No, LA1SK11 mounts only on the CA2SK20 relay.




                    CTA-ID : 2014524

                    Alternative part number for relay CA3KN1FD3?

                    The alternative part number is RPM42FD + RPZF4 base.
                     

                    Are the CA2SK11UE7 and 31168-640-54 the same devices?

                    Issue:
                    Identify the difference between CA2SK11UE7 and 31168-640-54.

                    Product Line:
                    TeSys SK IEC stle relays

                    Environment:
                    TeSys SK IEC stle relays, Industrial Control Relays

                    Resolution:
                    Yes, these are the same components. CA2SK11UE7 is stocked in France and 31168-640-54 is stocked in North America (primarily used on class 8903 type L lighting contactors with form R6).
                     