K CONTROL RELAY 3NO 1NC 110VDC COIL

TeSys K Control Relay, 3 NO + 1 NC, <= 690V, 110VDC Standard Coil

Catalogue Number: CA3KN31FD
K CONTROL RELAY 3NO 1NC 110VDC COIL
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
TeSys K control relay
Range
TeSys
Product name
TeSys CAK
Product or component type
control relay
Device short name
CA3K
Contactor application
control circuit
Utilisation category
  • DC-13
  • AC-15
    • Pole contact composition
      3 NO + 1 NC
      [Ue] rated operational voltage
      <= 690 V <= 400 Hz
      Control circuit type
      DC standard
      [Uc] control circuit voltage
      110 V DC
      [Ith] conventional free air thermal current
      10 A (at 50 °C)
      Irms rated making capacity
      110 A conforming to IEC 60947
      Associated fuse rating
    • 10 A gG conforming to IEC 60947
    • 10 A gG conforming to VDE 0660
      • [Ui] rated insulation voltage
      • 690 V conforming to IEC 60947
      • 750 V conforming to VDE 0110 group C
      • 690 V conforming to BS 5424
      • 600 V conforming to CSA C22.2 No 14
        • Mounting support
        • plate
        • rail
          • Connections - terminals
          • screw clamp terminals 1 cable(s) 1.5-4 mm²solid
          • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
          • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end
          • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
          • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
          • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
            • Tightening torque
            • 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
            • 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
              • Control circuit voltage limits
              • operational: 0.8...1.15 Uc (at <50 °C)
              • drop-out: 0.1...0.75 Uc (at <50 °C)
                • Operating time
                • 10 ms coil de-energisation and NO opening
                • 30...40 ms coil energisation and NO closing
                • 15 ms coil de-energisation and NC closing
                • 25...35 ms coil energisation and NC opening
                  • Mechanical durability
                    20 Mcycles
                    Maximum operating rate
                    10000 cyc/h
                    Immunity to microbreaks
                    2 ms
                    Inrush power in W
                    3-3 W (at 20 °C)
                    Hold-in power consumption in W
                    3-3 W at 20 °C
                    Heat dissipation
                    3-3 W
                    Minimum switching voltage
                    17 V
                    Minimum switching current
                    5 mA
                    Non overlap distance
                    0.5 mm
                    Insulation resistance
                    > 10 MOhm
                    Height
                    58 mm
                    Width
                    45 mm
                    Depth
                    57 mm
                    Net weight
                    0.225 kg
                    Compatibility code
                    CA3K
                    Standards
                  • BS 5424
                  • IEC 60947
                  • NF C 63-140
                  • VDE 0660
                    • Product certifications
                    • CSA
                    • UL
                      • IP degree of protection
                        IP2x
                        Protective treatment
                        TC conforming to IEC 60068
                        Ambient air temperature for operation
                        -25-50 °C
                        Ambient air temperature for storage
                        -50-80 °C
                        Operating altitude
                        2000 m without
                        Flame retardance
                      • V1 conforming to UL 94
                      • requirement 2 conforming to NF F 16-101
                      • requirement 2 conforming to NF F 16-102
                        • Mechanical robustness
                        • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                        • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                          • Sustainable offer status
                            Green Premium product
                            REACh Regulation
                            Free of Substances of Very High Concern above the threshold
                            REACh free of SVHC
                            Yes
                            EU RoHS Directive
                            Compliant
                            Mercury free
                            Yes
                            RoHS exemption information
                            Yes
                            China RoHS Regulation
                            Product out of China RoHS scope. Substance declaration for your information
                            Environmental Disclosure
                            ENVPEP1503003EN
                            Circularity Profile
                            ENVEOLI1503003EN
                            WEEE
                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                            California proposition 65
                            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov
                            Warranty
                            18 months

                            Frequently Asked Questions

                            hide show

                            Alternative part number for relay CA3KN1FD3?

                            The alternative part number is RPM42FD + RPZF4 base.
                             

                            What is the replacement for a CA3KN313BD needed

                             Use a CAD32BD

                            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                            Issue:
                            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                            Product Line:
                            CAD Industrial Relays

                            Environment:
                            Relays and Timers

                            Resolution:
                            Inductive:
                            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                            250V DC - 0.27 Amps make and break, 2.5 amps cont.
                            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                             

                            What is the replacement coil for a CA3DN31BD relay?

                            Issue:
                            What is the replacement coil for a CA3DN31BD  relay?

                            Product Line:
                            Relays and Timers

                            Environment:
                            All Products

                            Cause:
                            Product selection

                            Resolution:
                            Use an LX4D2BD.
                             

                            What is the alternative for a CA2KN31 in 48V AC?

                            The alternative would be a CA2KN31E7.

                            For further information please visit Trade - Clipsal by Schneider Electric

                            What is the replacement for CA2KN22F5 Control Relay?

                            The replacement for the CA2KN22F5  Control Relay is a
                            CAD32F7, It has 3x normaly closed And 2 x normaly open Contacts
                            instead of 2x normaly closed and 2 x normaly open, With a 110Volt AC  Coil fitted
                            For further information please follow the bellow link

                            https://www.schneider-electric.com.au/en/search/ca2dk22f5

                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Issue:
                            What is the 480V coil for a CA2DN31T6 IEC Relay?

                            Product Line:
                            Tesys Relays

                            Environment:
                            Obsolete relays

                            Cause:
                            Product selection

                            Resolution:
                            The LX1D2T6 coil is obsolete. Replace the contactor with the new TeSys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.


                            CTA-ID : 2048217

                            What is the difference between CA2KN and CA3KN?

                            Issue:
                            What is the difference between CA2KN and CA3KN?

                            Product Line:
                            Relays and Timer

                            Environment:
                            All products

                            Cause:
                            Product features

                            Resolution:
                            CA2 has AC coil. CA3 has DC coil.