TeSys K Control Relay, 2 NO + 2 NC, <= 690V, 110VDC, Standard Coil

TeSys K Control Relay, 2 NO + 2 NC, <= 690V, 110VDC, Standard Coil

TeSys K Control Relay, 2 NO + 2 NC, <= 690V, 110VDC, Standard Coil

Item Number: CA3KN22FD

Retail
$445.86
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height58 mm

Depth icon

Depth57 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys K control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V <= 400 Hz

Mounting support

  • rail
  • plate
    • Connections - terminals

    • screw clamp terminals 1 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 2 cable(s) 1.5-4 mm²solid
    • screw clamp terminals 1 cable(s) 0.75-4 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.75-4 mm²flexible without cable end
    • screw clamp terminals 1 cable(s) 0.34-1.5 mm²flexible with cable end
    • screw clamp terminals 2 cable(s) 0.34-1.5 mm²flexible without cable end
      • Mechanical durability

        20 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        58 mm

        Width

        45 mm

        Depth

        57 mm

        Net weight

        0.225 kg

        Standards

      • BS 5424
      • IEC 60947
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • UL
        • CSA
          • IP degree of protection

            IP2x

            Ambient air temperature for operation

            -25-50 °C

            Ambient air temperature for storage

            -50-80 °C

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

             Pro-active China RoHS declaration (out of China RoHS legal scope)

            Environmental Disclosure

            ENVPEP1503003EN

            Circularity Profile

            ENVEOLI1503003EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.p65warnings.ca.gov

            Others

            Product name

            TeSys CAK

            Device short name

            CA3K

            Contactor application

            control circuit

            Utilisation category

          • AC-15
          • DC-13
            • Pole contact composition

              2 NO + 2 NC

              Control circuit type

              DC standard

              [Uc] control circuit voltage

              110 V DC

              [Ith] conventional free air thermal current

              10 A (at 50 °C)

              Irms rated making capacity

              110 A conforming to IEC 60947

              Associated fuse rating

            • 10 A gG conforming to IEC 60947
            • 10 A gG conforming to VDE 0660
              • [Ui] rated insulation voltage

              • 690 V conforming to IEC 60947
              • 750 V conforming to VDE 0110 group C
              • 690 V conforming to BS 5424
              • 600 V conforming to CSA C22.2 No 14
                • Tightening torque

                • 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm
                • 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 26 mm
                  • Control circuit voltage limits

                  • operational: 0.8...1.15 Uc (at <50 °C)
                  • drop-out: 0.1...0.75 Uc (at <50 °C)
                    • Operating time

                    • 10 ms coil de-energisation and NO opening
                    • 30...40 ms coil energisation and NO closing
                    • 15 ms coil de-energisation and NC closing
                    • 25...35 ms coil energisation and NC opening
                      • Maximum operating rate

                        10000 cyc/h

                        Immunity to microbreaks

                        2 ms

                        Inrush power in W

                        3-3 W (at 20 °C)

                        Hold-in power consumption in W

                        3-3 W at 20 °C

                        Heat dissipation

                        3-3 W

                        Minimum switching voltage

                        17 V

                        Minimum switching current

                        5 mA

                        Non overlap distance

                        0.5 mm

                        Compatibility code

                        CA3K

                        Protective treatment

                        TC conforming to IEC 60068

                        Operating altitude

                        2000 m without derating

                        Flame retardance

                      • V1 conforming to UL 94
                      • requirement 2 conforming to NF F 16-101
                      • requirement 2 conforming to NF F 16-102
                        • Mechanical robustness

                        • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                        • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                        • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                          • Unit Type of Package 1

                            PCE

                            Number of Units in Package 1

                            1

                            Package 1 Weight

                            216 g

                            Package 1 Height

                            4.5 cm

                            Package 1 width

                            6.2 cm

                            Package 1 Length

                            6.5 cm

                            Unit Type of Package 2

                            S02

                            Number of Units in Package 2

                            40

                            Package 2 Weight

                            9.14 kg

                            Package 2 Height

                            15 cm

                            Package 2 width

                            30 cm

                            Package 2 Length

                            40 cm

                            WEEE

                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                            Show all specifications

                            Documents & downloads

                            hide show

                            Frequently Asked Questions

                            hide show

                            What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                            Issue:
                            Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                            Product Line:
                            CAD Industrial Relays

                            Environment:
                            Relays and Timers

                            Resolution:
                            Inductive:
                            125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                            250V DC - 0.27 Amps make and break, 2.5 amps cont.
                            600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                             

                            What is the replacement for CA2KN22F5 Control Relay?

                            The replacement for the CA2KN22F5  Control Relay is a
                            CAD32F7, It has 3x normaly closed And 2 x normaly open Contacts
                            instead of 2x normaly closed and 2 x normaly open, With a 110Volt AC  Coil fitted
                            For further information please follow the bellow link

                            https://www.schneider-electric.com.au/en/search/ca2dk22f5

                            Alternative part number for relay CA3KN1FD3?

                            The alternative part number is RPM42FD + RPZF4 base.
                             

                            Is the CA2KN22G7 DIN rail mountable?

                            Issue:
                            Is the CA2KN22G7 DIN rail mountable?
                            Product Line:
                            Industrial Relays
                            Environment:
                            Tesys K IEC Style Relays
                            Cause:
                            Determine how to mount for application.                             
                            Resolution:                                                                 
                            Yes. They are made to mount on 35mm DIN3 type mounting rail.
                             

                            What is the maximum voltage ratings for the contacts of a CA2KN?

                            Issue:
                            What is the maximum voltage ratings for a CA2KN22F7?

                            Product Line:
                            Relays and Timers

                            Environment:
                            Industrial Relays

                            Resolution:
                            600VAC and 240VDC

                            Is a CA2KN22 available with a 277 volt AC coil ?

                            Issue:
                            Is a CA2KN22 available  with a 277 volt AC coil ?
                            Product Line:
                            Industrial Relays
                            Environment:
                            Tesys K IEC Style Rekays
                            Cause:
                            Application is calling for 277v coil.                           
                            Resolution:                                                                 
                            The voltage code for 277 vac is UE7. CA2KN22UE7 is currently obsolete.
                             

                            Is the CA3SK20BD still available?

                            Yes it is still available.

                            What is the replacement for a CA3KN313BD needed

                             Use a CAD32BD

                            Is it possible to mount a surge suppressor with LED (LAD4RCE) on the CA4KN**, low consumption DC control relay.

                            CA4KN** control contactor comes fitted with integrated surge suppressor (bidirectional diode), thus there is no need for an external surge suppressor.
                             
                            However if the additional surge suppressor on the CA4KN22** is required, then it is possible to mount the suppressor (LAD4RCE).
                             
                            If the additional surge suppressor with LED is being used just for indication to verify that power is applied to the contactor, it is advisable to use a normal LED as per the coil voltage, connected to the coil supply (A1- A2).
                             
                            This will give the indication functionality as that of the additional external surge suppressor with LED, if that is what the only requirement is.

                            Video: How to Mount a GV3P Motor Starter/Protector to a LC1D Contactor with Everlink Terminals

                            Issue:
                            How GV3P and LC1D contacto with Evelink connect to each other 

                            Product Line: 
                            Contact and Starters - IEC  

                            Environment:
                            LC1D Tesys D Contactors, GV3P Manual Motor Starter/PRotector

                            Resolution:
                            Take your GV3P and remove the Everlink terminals from the base. Line up the exposed terminals with the top of the contactor so that they mate together. Use an Allen Wrench to secure the GV3P tight to the contactor.

                            What is the replacement coil for a CA3DN31BD relay?

                            Issue:
                            What is the replacement coil for a CA3DN31BD  relay?

                            Product Line:
                            Relays and Timers

                            Environment:
                            All Products

                            Cause:
                            Product selection

                            Resolution:
                            Use an LX4D2BD.
                             

                            What is the part number for 4 pole , 10 Amp relay 2NO/2NC , 24V DC?

                            The part number for 4 pole , relay 2NO/2NC , 24V DC is CA3KN22BD
                            Follow link for data sheet:
                            https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=CA3KN22BD
                             
                            Show More