Quantcast

TeSys K Control Relay, 3 NO + 1 NC, <= 690 V, 230 V AC coil

TeSys K Control Relay, 3 NO + 1 NC, <= 690 V, 230 V AC coil

TeSys K Control Relay, 3 NO + 1 NC, <= 690 V, 230 V AC coil

Item Number: CA2KN313P7

Retail
$232.66
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height58 mm

Depth icon

Depth57 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

TeSys K control relay

Range

TeSys

Product or component type

control relay

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

[Ue] rated operational voltage

<= 690 V <= 400 Hz

Mounting support

  • plate
  • rail
    • Connections - terminals

    • spring terminals 1 cable(s) 0.75-1.5 mm²solid
    • spring terminals 1 cable(s) 0.75-1.5 mm²flexible without cable end
      • Mechanical durability

        10 Mcycles

        Insulation resistance

        > 10 MOhm

        Height

        58 mm

        Width

        45 mm

        Depth

        57 mm

        Net weight

        0.18 kg

        Standards

      • BS 5424
      • IEC 60947
      • NF C 63-140
      • VDE 0660
        • Product certifications

        • CSA
        • UL
          • Ambient air temperature for operation

            -25-50 °C

            Ambient air temperature for storage

            -50-80 °C

            REACh Regulation

            Free of Substances of Very High Concern above the threshold

            REACh free of SVHC

            Yes

            EU RoHS Directive

            Compliant

            Toxic heavy metal free

            Yes

            Mercury free

            Yes

            RoHS exemption information

            Yes

            China RoHS Regulation

             Pro-active China RoHS declaration (out of China RoHS legal scope)

            Environmental Disclosure

            ENVPEP1503003EN

            Circularity Profile

            ENVEOLI1503003EN

            California proposition 65

            WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov

            Others

            Number of Units in Package 1

            1

            Package 1 Height

            4.8 cm

            Package 1 Length

            6.2 cm

            Package 1 width

            6.5 cm

            Unit Type of Package 1

            PCE

            Product name

            TeSys CAK

            Device short name

            CA2K

            Contactor application

            control circuit

            Utilisation category

          • AC-15
          • DC-13
            • Pole contact composition

              3 NO + 1 NC

              Control circuit type

              AC at 50/60 Hz

              [Uc] control circuit voltage

              230 V AC 50/60 Hz

              [Ith] conventional free air thermal current

              10 A (at 50 °C)

              Irms rated making capacity

              110 A conforming to IEC 60947

              Associated fuse rating

            • 10 A gG conforming to IEC 60947
            • 10 A gG conforming to VDE 0660
              • [Ui] rated insulation voltage

              • 690 V conforming to IEC 60947
              • 750 V conforming to VDE 0110 group C
              • 690 V conforming to BS 5424
              • 600 V conforming to CSA C22.2 No 14
                • Control circuit voltage limits

                • drop-out: 0.2...0.75 Uc (at <50 °C)
                • operational: 0.8...1.15 Uc (at <50 °C)
                  • Operating time

                  • 10...20 ms coil de-energisation and NO opening
                  • 10...20 ms coil energisation and NO closing
                  • 15...25 ms coil de-energisation and NC closing
                  • 5...15 ms coil energisation and NC opening
                    • Maximum operating rate

                      10000 cyc/h

                      Immunity to microbreaks

                      2 ms

                      Inrush power in VA

                      30-30 VA (at 20 °C)

                      Hold-in power consumption in VA

                      4.5-4.5 VA (at 20 °C)

                      Heat dissipation

                      1.3-1.3 W

                      Minimum switching voltage

                      17 V

                      Minimum switching current

                      5 mA

                      Non overlap distance

                      0.5 mm

                      Compatibility code

                      CA2K

                      Protective treatment

                      TC conforming to IEC 60068

                      Operating altitude

                      2000 m without derating

                      Flame retardance

                    • V1 conforming to UL 94
                    • requirement 2 conforming to NF F 16-101
                    • requirement 2 conforming to NF F 16-102
                      • Mechanical robustness

                      • vibrations contactor open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
                      • vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6
                      • shocks contactor open: 10 Gn for 11 ms conforming to IEC 60068-2-27
                      • shocks contactor closed: 15 Gn for 11 ms conforming to IEC 60068-2-27
                        • Package 1 Weight

                          207 g

                          WEEE

                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                          Show all specifications

                          Frequently Asked Questions

                          hide show

                          What is the replacement for a CA3KN313BD needed

                           Use a CAD32BD

                          What the DC current contact ratings for the CAD50, CAD32, CAD503, CAD323, CAD506, and CAD326 relay?

                          Issue:
                          Checking on the DC current contact ratings for the CAD50, CAD32, CAD503,  CAD323,  CAD506, and  CAD326 relay.

                          Product Line:
                          CAD Industrial Relays

                          Environment:
                          Relays and Timers

                          Resolution:
                          Inductive:
                          125V DC - 0.55 Amps make and break, 2.5 Amps cont.
                          250V DC - 0.27 Amps make and break, 2.5 amps cont.
                          600V DC - 0.10 Amps make and break, 2.5 Amps cont.

                          Is a CA2KN22 available with a 277 volts AC coil?

                          Issue:
                          Is a CA2KN22 available  with a 277 volt AC coil ?

                          Product Line:
                          Tesys K IEC Style Relays

                          Environment:
                          Industrial Relays

                          Resolution:                                                                 
                          The voltage code for 277 vac is UE7. CA2KN22UE7 is currently obsolete.
                           

                          What is the alternative for a CA2KN31 in 48V AC?

                          The alternative would be a CA2KN31E7.

                          For further information please visit Trade - Clipsal by Schneider Electric

                          Is the CA2KN22G7 DIN rail mountable?

                          Issue:
                          Is the CA2KN22G7 DIN rail mountable?
                          Product Line:
                          Industrial Relays
                          Environment:
                          Tesys K IEC Style Relays
                          Cause:
                          Determine how to mount for application.                             
                          Resolution:                                                                 
                          Yes. They are made to mount on 35mm DIN3 type mounting rail.
                           

                          What is the 480V coil for a CA2DN31T6 IEC Relay?

                          Issue:
                          What is the 480V coil for a CA2DN31T6 IEC Relay?

                          Product Line:
                          Tesys Relays

                          Environment:
                          Obsolete relays

                          Cause:
                          Product selection

                          Resolution:
                          The LX1D2T6 coil is obsolete. Need to replace the contactor with the new Tesys product, CAD32T7. Note this is a functional equal only. Accessories for the old product may or may not fit the new design. Confirm dimensions.
                          See link for further information:https://www.se.com/ww/en/product/CAD32T7/tesys-d-control-relay---3-no-%2B-2-nc---%3C%3D-690-v---480-v-ac-standard-coil/
                          Schneider Electric CAD32T7 Image

                          CTA-ID : 2048217
                          Show More