Chassis C60 2Ph 250A 36P

Specifications

Design

Range

Acti 9

Product or component type

chassis

Device application

distribution

Physical

Range compatibility

Acti 9 Isobar A distribution board

[In] rated current

250 A

Number of poles

36 18 mm

Width

215 mm

Length

326 mm

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Device short name

MSC DC

[Icw] rated short-time withstand current

25 kA

Short-circuit withstand

25 kA 0.1 s

Number of ways

  • 1 way (incomer) - 2P
  • 36 ways (outgoer)
    • Busbar pitch

      18 mm

      Package 1 Weight

      4.899 kg
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      What are the wiring terminals on the IEC LRD* overload relays?

      Product Line:
      Tesys D line Overload Relays
       
      Resolution:
      The normally closed overload contact are terminals 95 & 96; and the normally open overload contact are terminals 97 & 98.
      T1 T2 and T3 are the load terminals. 

      The normally closed control circuit contact will open when there is a fault, this contact is typically used in series with the control circuit. 

      The normally open trip signal contact closes when a fault occurs which is typically used to control a pilot light, or alarm.