MSC18 CHASSIS ASSY 250A 84 POL

Msc18 Chassis Assy 250A 84 Pol

Catalogue Number: C325843
MSC18 CHASSIS ASSY 250A 84 POL
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Product brand
Clipsal
EU RoHS Directive
Not applicable, out of EU RoHS legal scope

Documents & downloads

hide show
Filter items
  • All

  • Technical Data Catalogues

  • Specifications

Frequently Asked Questions

hide show

What distribution board is required for the CH25843 chassis?

For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

What is the PAN assembly for C120 MCCB's

 The part code is C125123

What is the maximum cut out size of a Clipsal plate in the Standard Series?

52mm x 76mm

Example References (not comprehensive):
31VX
31VH
31VA

How many 3 pole C120 breakers can be supplied from the C125123?

That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

I am looking for the 4FCS24PK Protection Kit?

The 4FCS24PK Has been discontinued. Some contractors are required to install a metal backing behind load centres / switchboards. If this is the case we suggest obtaining sheet metal from a local fabricator.

What are the A, B, C, D, E, F, G, H, and J ground fault ampere values for the Micrologic 6.0A, 6.0P, and 6.0H on the 1600A Masterpact breaker NW16H2?

Product Line:
Circuit Breakers

Environment:
Electrical Distribution Equipment.

Resolution:
For all 1200A sensors and greater they are 500A, 640A, 720A, 800A, 880A, 960A, 1040, 1120A, and 1200A respectively.

Is the TPDL series compatible with the C-BUS lighting system?

For best outcome it is always recommended to test each type of load before commiting to any application as there can be external enviromental influences which may affect the performance of the load (LED's).
When load incompatibility is present it is recommended to use a 31LCDA, while this is not guaranteed to fix the issue, it will often produce a smoother operation.

​What is the difference between the IFE (LV434010) and IFE Gateway (LV434011)?

Product Line:
Smart Systems

Resolution:
The IFE and the IFE Gateway appear very similar (see picture below), but there is a difference.
  • The IFE (cat. no. LV434010) is the Ethernet interface for Powerpact and Masterpact LV circuit breakers.
  • The IFE Gateway (cat. no. LV434011) is the Ethernet interface for Powerpact and Masterpact LV circuit breakers, plus a gateway for Modbus-SL (serial line) connected devices. Note that the IFE Gateway is also referred to as IFE Modbus, or IFE Server.


Are NetShelter cabinets PCI Compliant?

Issue:
The need to attain PCI compliance drives the need for compliant components.

Product Line:
NetShelter SX, NetShelter CX, NetShelter WX, NetShelter SV

Environment:
All versions and serial ranges.

Cause:
The customer requires PCI compliance.

Resolution:

NetShelter cabinets can certainly be part of an environment where credit card data is protected which, in turn, can help a merchant attain PCI compliance.
Which cabinets are good choices for a PCI compliant environment: NetShelter WX, SX, SV and CX. 
There is no such thing as a “PCI Compliant” cabinet.
There is no test that can be performed on a cabinet to allow it to be deemed 'PCI Compliant'.
PCI compliance for merchants states that they need to secure their networking and IT hardware that stores and transmits credit card data.
This means that they should lock it up, protect it, and be able to audit access logs to it.
With that in mind, any IT cabinet that’s secure on all accessible surfaces can help a merchant become compliant with the PCI standard.

Please see attached file for a more indepth answer with suggestions for specific products, and photos. 

What is the part number of the extension ring to suit 240 series junction box?

Part number of the extension ring to suit 240 series junction boxes are 249/12 or 249/25. Extension Rings fit all 240 Series Junction Boxes and are designed to provide extra space for additional terminations or bring forward the fixing points to allow easier mounting of accessories.


For further information please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=249/12
https://www.clipsal.com/Trade/Products/ProductDetail?catno=249/25
User-added image

Upgrade of Power Monitoring Expert (PME) 8.x to 8.2 fails with RegBrick_x86 error

Issue
When running the installation utility to upgrade Power Monitoring Expert 8.0 or 8.1 to 8.2, the installation will stop on the copying files section with a warning:
"The feature you are trying to use is on a network resource that is unavailable."



 
When the user manually selects the file via browse the next error is that the file is not a valid installation package for the product.


Product Line
Power Monitoring Expert 8.x

Cause
This problem is a result of RegBrick_x86.msi being detected as a Trojan by some anti-virus software, McAfee for sure, and possibly other anti-virus packages.
When PME is upgraded, the installer tries to uninstall the old msi packages prior to installing the new ones. Since RegBrick_x86.msi cannot be found where expected, you are prompted to find it manually.

Resolution
Cancel the PME installation.
Uninstall RegBrick_x86.msi via Microsoft 'Program Install and Uninstall Troubleshooter'
 
1.)  Browse to the Microsoft link below:
       https://support.microsoft.com/en-us/help/17588/fix-problems-that-block-programs-from-being-installed-or-removed
2.)  Download the 'Program Install and Uninstall Troubleshooter' tool and save it locally.
3.)  Run the tool and choose 'RegBrick_x86' from the list of programs that will be presented
4.)  Then click on 'Yes, try uninstall'
5.)  Once this has been done, begin the PME installation utility again

What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

Issue:
What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

Product Line:
IEC Contactors

Environment:
Ordering

Cause:
Selection

Resolution:
The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

AC Volts ___Code     AC Volts ___Code
12 ___ J7                   208 ___ LE7
21 ___ Z7                   220 ___ M7
24 ___ B7                  230 ___ P7
32 ___ C7                  240 ___ U7
36 ___ CC7               277 ___ W7
42 ___ D7                  380 ___ Q7
48 ___ E7                   400 ___ V7
60 ___ EE7                415 ___ N7
100 ___ K7                440 ___ R7
110 ___ F7                480 ___ T7
115 ___ FE7              575 ___ SC7
120 ___ G7                600 ___ X7
127 ___ FC7              690 ___ Y7
200 ___ L7                
               
Standard Coil                Low Consumption
DC Volts ___Code          DC Volts ___Code
12 ___ JD                           5 ___ AL
24 ___ BD                         12 ___ JL
36 ___ CD                         20 ___ ZL
48 ___ ED                         24 ___ BL
60 ___ ND                         48 ___ EL
72 ___ SD                         72 ___ SL
110 ___ FD                       96 ___ DL
125 ___ GD                     110 ___ FL
220 ___ MD                    220 ___ ML
250 ___ UD                     250 ___ UL
440 ___ RD