elbow solid pvc cond 20mm

Telecommunication Conduit Fittings, Solid Elbows - Standard Colour White, 20mm

Catalogue Number: C245/20
elbow solid pvc cond 20mm
Retail
$11.16
RRP (Inc. GST)
Colour White Electric (WE)
  • White Electric 1 PCE

Specifications

hide show
Product brand
Clipsal
Range of product
Series C245
Material
PVC (polyvinyl chloride)
Diameter
20 mm
Operating angle
90 °
Length
54 mm
Inner radius
22 mm
Standards
AS/NZS 2053
Package 1 Weight
15 g
Package 1 Height
29 mm
Package 1 width
40 mm
Package 1 Length
75 mm
REACh free of SVHC
Yes
EU RoHS Directive
Pro-active compliance (Product out of EU RoHS legal scope)
Toxic heavy metal free
Yes
Mercury free
Yes
RoHS exemption information
Yes
China RoHS Regulation
 Pro-active China RoHS declaration (out of China RoHS legal scope)

Frequently Asked Questions

hide show

Whati s pitch thread for part number 1245/25?

Pitch thread is 1.5mm

What is the cover for a C2015/20?

The cover for a C2015/20 is a C2015/20C.

Is part number C2015/20 available in Red?

Yes it is and the part number is C2015/20-RD.

What is part number for Stainless Steel cover to suit C2015/20?

The part number for Stainless Steel cover to suit is a C2015/20C.

What would be a longer screw to suit Clipsals round j-boxes (Junction Boxes)?

The part number would be 248/20 which is a combination screw head 20MM 3/16 BSW.

Do Clipsal make a 3 pin, 20 amp, switched outlet with flat pins?

Yes, 20A 3 flat pin switched outlets are available in a few variants , most commonly the 2015/20, C2015/20 and 56C320F.

For further information please visit:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=2015/20
https://www.clipsal.com/Trade/Products/ProductDetail?catno=C2015/20
https://www.clipsal.com/Trade/Products/ProductDetail?catno=56C320F

 

Does the 1240/25 series come with gaskets?

No, they are light duty. Buy the 1240HL25 to obtain a heavy duty lid and gasket , or if gasket is required for retro fit then buy 1240GT
For more information on this product range please visit the Clipsal web site on the link provided
https://www.clipsal.com/Trade/search-results?q=1240

What is part number for lid to suit 1239/20/4?

Part number 1239L20 will suit any of 1239/20 series.

What is the thread type on a 1235/25?

The thread type on a 1235/25 is BS - British Standard.

For more information, please refer to the link:
https://www.clipsal.com/Trade/Products/ProductDetail?catno=1235/25 

Where can I get wiring diagrams for the BMXFCCXXXX Cables?

Wiring Diagrams for BMXFCC051, BMXFCC053, BMXFCC1001, BMXFCC101, BMXFCC103, BMXFCC201, BMXFCC203, BMXFCC301, BMXFCC303, BMXFCC501 and BMXFCC503

How do I hardwire 10kva and 20kva transformers in a 208/120 or 240/120 environment

Issue:
Implementing a hardwire stepdown transformer in a 208v or 240v environment


Product Line:

Smart-UPS / Symmetra

Environment:

APTF10KT01, APTF10KW01, and APTF20KW01, All Serial Numbers

Cause:

Unbalanced UPS outputs require a stepdown transformer to power 120v loads


Resolution:

This document refers to installing  the APTF10KT01, APTF10KW01, and APTF20KW01 transformers in a North American 120/240 or 120/208 environment. For installations in other regions please consult the users manual.

The wiring block outputs are as follows:


For domestic use, make sure that the Terminal Block Jumper is installed between the Ground Terminal and Terminal 8 on the output wiring block, as illustrated on page 8 of the user manual. Please also make sure that the input voltage switch is in the correct position.

The step-down transformer provides 240/120 output as 2 120v hots, a neutral, and a ground. It provides 208v output as a 120v hot, an 88v hot, and a ground. The 120v hot (terminal  7) and the 88v hot (terminal 9) are 180 degrees out of phase. You will measure 208v from terminals 7 to 9. The step-down transformer is not able to provide 2 120v hots that are 120 degrees out of phase as you would see with utility power.



 Note: If your installation requires both 208v and 120v output power you will need 2 separate subpanels: a 240v/120v panel and a dedicated 208v subpanel.

Is it possible to copy the program out of an LMC20 motion controller?

Yes, it is possible to copy the program out of an LMC20 motion controller.

There can be instances in which an LMC20 needs to be replaced and the program that is stored inside the LMC20 needs to be copied so that it can be loaded into the replacement LMC20.
In these instances you will need a software tool known as CodeSys Service tool.

With the Codesys Service tool, you can upload the boot project from the LMC20 to your PC.
For this, use the function "File -> Upload" in the Service tool.
The boot project contains of 2 files:
1. In the file selection box of the upload function, type manually "DEFAULT.PRG" (in capital letters !!!) and upload it
2. then, type "DEFAULT.CHK" and upload again.

The saved files can then be downloaded into the replacement LMC20.


rev 2/19/18