Chassis C120 3-Phase 250A 72P

Chassis C120 3-Phase 250A 72P

Chassis C120 3-Phase 250A 72P

Item Number: C125723

Retail
$1,976.33
RRP (Inc. GST)

Datasheet

Specifications

Design

Range

Acti 9

Product or component type

chassis

Device application

distribution

Physical

Range compatibility

Acti 9 Isobar B distribution board

[In] rated current

250 A

Number of poles

72 27 mm

Length

974 mm

Width

215 mm

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

China RoHS Regulation

Product out of China RoHS scope. Substance declaration for your information

Others

Device short name

MSC 27

Short-circuit withstand

25 kA 0.1 s

[Icw] rated short-time withstand current

25 kA

Number of ways

  • 1 way (incomer) - 3P
  • 72 (outgoer)
    • Busbar pitch

      27 mm

      Package 1 Weight

      7.9 kg

      Package 1 Height

      215 mm

      Package 1 width

      1 mm

      Package 1 Length

      1163 mm
      Show all specifications

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      How many 3 pole C120 breakers can be supplied from the C125123?

      That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

      What is the PAN assembly for C120 MCCB's

       The part code is C125123

      Will the PDL 625F work on an 80w fan

      Yes if the motor is shaded pole or split phase

      What is the temperature that will make the Micrologic A, P, and H trip with Ap fault indication?

      Issue:
      What is the temperature that will make the Micrologic A, P, and H trip with Ap fault indication?

      Product Line:
      Micrologic (proxima) trip units on Powerpact P, R and Masterpact NT, NW

      Environment:

      Cause:

      Resolution:
      Around 115 C, 239 F


      CTA-ID : 2023723

      What material is used in and what is the surface treatment for ZB2Bxx sub-bases?

      ZB2Bxx sub-bases are made of chromium plated ZnAl4.

      What distribution board is required for the CH25843 chassis?

      For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

      What is the heat dissipation (Watts loss) for the ATS22 series soft starters?

      Issue:
      What is the heat dissipation (Watts loss) for the ATS22 series soft starters?

      Product Line:
      ATS22 soft starters

      Environment:
      All models listed in the attached chart, all serial numbers

      Cause:
      Customer unable to find needed information

      Resolution:
      Please see the attached file for the heat dissipation data for the ATS22 series soft starters.

      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

      Issue:
      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

      Product Line:
      IEC Contactors

      Environment:
      Ordering

      Cause:
      Selection

      Resolution:
      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      AC Volts ___Code     AC Volts ___Code
      12 ___ J7                   208 ___ LE7
      21 ___ Z7                   220 ___ M7
      24 ___ B7                  230 ___ P7
      32 ___ C7                  240 ___ U7
      36 ___ CC7               277 ___ W7
      42 ___ D7                  380 ___ Q7
      48 ___ E7                   400 ___ V7
      60 ___ EE7                415 ___ N7
      100 ___ K7                440 ___ R7
      110 ___ F7                480 ___ T7
      115 ___ FE7              575 ___ SC7
      120 ___ G7                600 ___ X7
      127 ___ FC7              690 ___ Y7
      200 ___ L7                
                     
      Standard Coil                Low Consumption
      DC Volts ___Code          DC Volts ___Code
      12 ___ JD                           5 ___ AL
      24 ___ BD                         12 ___ JL
      36 ___ CD                         20 ___ ZL
      48 ___ ED                         24 ___ BL
      60 ___ ND                         48 ___ EL
      72 ___ SD                         72 ___ SL
      110 ___ FD                       96 ___ DL
      125 ___ GD                     110 ___ FL
      220 ___ MD                    220 ___ ML
      250 ___ UD                     250 ___ UL
      440 ___ RD