Specifications

hide show
Range
Acti 9
Device short name
MSC 27
Product or component type
chassis
Device application
distribution
Range compatibility
Acti 9 Isobar B distribution board
[In] rated current
250 A
Short-circuit withstand
25 kA 0.1 s
[Icw] rated short-time withstand current
25 kA
Number of ways
  • 1 way (incomer) - 3P
  • 36 ways (outgoer)
    • Number of poles
      36 27 mm
      Length
      488 mm
      Width
      215 mm
      Busbar pitch
      27 mm
      Package 1 Weight
      4.3 kg
      Package 1 Height
      215 mm
      Package 1 width
      1 mm
      Package 1 Length
      677 mm
      EU RoHS Directive
      Pro-active compliance (Product out of EU RoHS legal scope)
      China RoHS Regulation
      Product out of China RoHS scope. Substance declaration for your information

      Documents & downloads

      hide show
      Filter items
      • All

      • Technical Data Catalogues

      • Specifications

      Frequently Asked Questions

      hide show

      What is the PAN assembly for C120 MCCB's

       The part code is C125123

      How many 3 pole C120 breakers can be supplied from the C125123?

      That is a 3 phase, 12 pole supply with 27mm spcaing. It will supply up to 4x 3 pole breakers.

      ETSNZ - How do I wire the TSXDEY16A4 discrete IO 100...120 VAC module for a Premium PLC?

      TSXDEY16A4 wiring the 120VAC module as per the diagram:

      Are only Clipsal downrods to be used on ACES48SS fans?

       Yes. Only Clipsal downrods are recommended for ACES48SS fans.

      What is part number for a 9001 Type K 3 position maintained selector switch for a HOA application, with the following contact sequence: O O X , X O O?

      Issue:
      What is part number for a 9001 Type K 3 position maintained selector switch for a HOA application, with the following contact sequence:

      O O X
      X O O

      Product Line:
      Harmony Pushbuttons

      Environment:
      All Products

      Cause:
      Product selection

      Resolution:
      9001KS43BH13.


      CTA-ID : 15363

      Is my eco-mind energy monitoring software compatible with windows 8.1?

      The software has been developed for windows 7. You would need to change the compatibility mode to run for windows 7.

      For more information on the Ecomind please visit the Clipsal.com website on the link provided
      https://www.clipsal.com/Trade/search-results?q=ecomind

      What distribution board is required for the CH25843 chassis?

      For the customized distribution board for 72 pole (18 mm) and 12 pole (27 mm) chassis, you need to submit request for a quote to "au.estimating@schneider-electric.com". Our Standard distribution board only goes up to 60 pole (18 mm) and 12 pole (27 mm).

      What are the coil voltage codes for the LC1D09 / LC2D09 through LC1D38 / LC2D38 TeSys contactors?

      Issue:
      What are the coil voltage codes for the LC1D09 / LC2D09through LC1D38 / LC2D38 TeSys contactors?

      Product Line:
      IEC Contactors

      Environment:
      Ordering

      Cause:
      Selection

      Resolution:
      The following lists the more common voltage suffix codes for these product lines.  For a more comprehensive list and to determine compatibility with a given product, refer to the catalog below.

      AC Volts ___Code     AC Volts ___Code
      12 ___ J7                   208 ___ LE7
      21 ___ Z7                   220 ___ M7
      24 ___ B7                  230 ___ P7
      32 ___ C7                  240 ___ U7
      36 ___ CC7               277 ___ W7
      42 ___ D7                  380 ___ Q7
      48 ___ E7                   400 ___ V7
      60 ___ EE7                415 ___ N7
      100 ___ K7                440 ___ R7
      110 ___ F7                480 ___ T7
      115 ___ FE7              575 ___ SC7
      120 ___ G7                600 ___ X7
      127 ___ FC7              690 ___ Y7
      200 ___ L7                
                     
      Standard Coil                Low Consumption
      DC Volts ___Code          DC Volts ___Code
      12 ___ JD                           5 ___ AL
      24 ___ BD                         12 ___ JL
      36 ___ CD                         20 ___ ZL
      48 ___ ED                         24 ___ BL
      60 ___ ND                         48 ___ EL
      72 ___ SD                         72 ___ SL
      110 ___ FD                       96 ___ DL
      125 ___ GD                     110 ___ FL
      220 ___ MD                    220 ___ ML
      250 ___ UD                     250 ___ UL
      440 ___ RD                

      PowerChute Business Edition no longer works using JRE 8 Update 91 or greater.

      Issue:
      The PowerChute Business Edition versions listed below are unable to support JRE 8 Update 91 or above due to JRE security changes made which impact how PowerChute Business Edition functions.

      Product line:
      PowerChute Business Edition versions 9.0.3, 9.1.1, 9.2.0

      Environment:
      Windows x64, Windows x86, Linux.
      See attached compatibility list

      Cause:
      The latest release of JRE 8 Update 91 (and greater) contains a security update which breaks PowerChute Business Edition functionality.

      Solution:
      Upgrade to or install the attached PowerChute Business Edition upgrade (v9.2.1) & (9.0.4)which is shipped with JRE 8 Update 102. By upgrading to v9.2.1 or 9.0.4, the functional issues caused by the JRE 8 Update 91 changes are fixed. This upgrade is available for supported Windows and Linux operating systems.

      Note: Once you have upgraded to v9.2.1, or 9.0.4 the software will be fully functional. However, if you then decide to upgrade the JRE to a later version than Update 102 using the JRE Configuration Tool, then the additional manual changes specified in Answer ID #FA264735, FA264736 & FA253763 are still required for communications between the PowerChute Agent and PowerChute Console. 

      If your UPS is a SMT, SMX, SURTD, SRT, SMC PowerChute Agent 9.2.1 will be installed.
      If your UPS is a SU, SC, SUA, SURT, SURTA, Matrix PowerChute Agent 9.0.4 will be installed.

      Upgrade to or download v9.2.1 / 9.0.4 from:
      5 Node for Windows
      5 Node for Linux

      Unable to access PowerChute Business Edition Server from the PowerChute Business Edition Console after upgrading the JRE version with JRE Configuration Tool

      Issue:
      When upgrading the JRE version, the JRE Configuration Tool runs as expected and both APC PBE Agent (if applicable) and APC PBE Server services are started. When the PowerChute Business Edition Console is launched and username and password is entered, an error window is displayed stating that the server is not accessible.


      Product Line: 
      PowerChute Business Edition versions 9.0, 9.0.1, 9.1.0, 9.0.2, 9.1.1, 9.0.3, 9.2.0, 9.0.4, 9.2.1

      Environment:
      OS: Windows x64, x86

      Cause:
      The latest release of Java JRE 8u60 (and greater) contains a security update which prevents communication between the PowerChute Business Edition Console and the PowerChute Business Edition Server.

      Solution:
      After upgrading the Java JRE version to 8u60 (or greater), perform the following steps:

      1.  Stop the PowerChute Business Edition Agent and Server services.
      You can do this from the command line (Run as administrator) with the following command:

      Server:                                
      net stop apcpbeserver

      Agent (if installed):       
      net stop apcpbeagent

      2.  In the PowerChute JRE folder, open the file lib\security\java.security using a text editor.

      Sample JRE locations -
      Windows x86:
      C:\Program Files\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
      Windows x64:
      C:\Program Files (x86)\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
      Linux:
      /usr/java/jre1.8.0_60 (Default Java JRE install directory)
      Go to the line containing the jdk.tls.disabledAlgorithms setting and carry out the following:
      1. Remove RC4 as a disabledAlgorithm
      2. Change DH keysize restriction from 768 to 256
      Original:             
      jdk.tls.disabledAlgorithms=SSLv3, RC4, DH keySize < 768

      New:                    
      jdk.tls.disabledAlgorithms=SSLv3, DH keySize < 256

      3. The following step needs to be carried out for PowerChute Business Edition Agent versions 9.0 and 9.0.1 if it is managed by a PowerChute Business Edition Console/Server.

      In the PowerChute JRE folder, open the file lib\security\java.security using a text editor.

      Sample JRE locations -
      Windows x86:
      C:\Program Files\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
      Windows x64:
      C:\Program Files (x86)\APC\PowerChute Business Edition\JreConfigTool\1.8.0_60
      Linux:
      /usr/java/jre1.8.0_60 (Default Java JRE install directory)
      Go to the line (should be at the end of the file) containing the jdk.tls.legacyAlgorithms setting and remove 'RC4_128,' from it:

      Original:
      jdk.tls.legacyAlgorithms= \
                      K_NULL, C_NULL, M_NULL, \
                      DHE_DSS_EXPORT, DHE_RSA_EXPORT, DH_anon_EXPORT, DH_DSS_EXPORT, \
                      DH_RSA_EXPORT, RSA_EXPORT, \
                      DH_anon, ECDH_anon, \
                      RC4_128, RC4_40, DES_CBC, DES40_CBC
       
      New:    
      jdk.tls.legacyAlgorithms= \
                      K_NULL, C_NULL, M_NULL, \
                      DHE_DSS_EXPORT, DHE_RSA_EXPORT, DH_anon_EXPORT, DH_DSS_EXPORT, \
                      DH_RSA_EXPORT, RSA_EXPORT, \
                      DH_anon, ECDH_anon, \
                      RC4_40, DES_CBC, DES40_CBC

      4.  Start the PowerChute Business Edition Agent and Server services
      You can do this from the command line (Run as administrator) with the following command:

      Server:                                
      net start apcpbeserver

      Agent (if installed):
      net start apcpbeagent
       

      Are EasyPact CVS circuit breakers for sale in the USA or Canada?

      Product Line:
      EasyPact CVS circuit breakers

      Cause:
      This breaker is popular overseas and there is interest in the US

      Resolution:
      There are no plans for a general release of the EasyPact CVS circuit breaker line in North America.