switch 3g arch b style s/s

Flush Switch, 3 Gang, 250VAC, 10A, Metal Plate Range, B Style, Architrave

Catalogue Number: B33A
switch 3g arch b style s/s
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • Brown 1 PCE
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Metal Plate
Product brand
Clipsal
Device presentation
basic element with full cover plate and grid
Switch function
  • 1-way
  • 2-way
    • Actuator
      rocker
      Number of rocker
      3
      Device mounting
      flush
      Fixing mode
      by screws
      Surface treatment
      stainless steel
      Local signalling
      without
      [Ue] rated operational voltage
      250 V AC
      Rated current
      10 A
      Marking
      without marking
      EU RoHS Directive
      Compliant
      Environmental Disclosure
      ENVPEP120506EN

      Frequently Asked Questions

      hide show

      What is the dimensions for the B32A (Stainless Steel) and BB32A (Polished Brass) Architrave Switches ?

      The dimensions are:
      Length x 110mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 95mm

      What is the dimensions for B31A (Stainless Steel) and BB31A (Polished Brass) Architrave Switch ?

      The dimensions are:
      Length x 90mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 70mm

      What is the dimensions for a B31A (Stainless Steel) and BB31A (Polished Brass) Architrave Switches ?

      The dimensions are:
      Length x 140mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 125mm

      What is the part number for a metal plate, stainless steel, single gang, architrave switch?

      The part number is B31A - BK  ( for black mech and bezel )

      Why is the LCD display screen blank on a Micrologic Power or Harmonic type trip unit on a Powerpact P frame, R frame, or Masterpact circuit breaker?

      Issue:
      Why is the display blank on the trip unit?

      Product Line:
      Powerpact P frame, Powerpact R Frame, Masterpact NT, Masterpact NW

      Environment:
      Applied to Powerpact and Masterpact breakers with trip units with LCD displays.

      Cause:
      Need to power display of the trip unit without external power supply.

      Resolution:
      The LCD display on a Micrologic P or H trip unit will be blank unless the trip unit is energized.  Energization requires one of the following sets of conditions:
      1. The trip unit is energized by an external 24 Vdc applied to terminals F1-F2 (F1 negative-F2 positive)
      2. The trip unit is energized by an FFTK or HHTK test kit
      3. There is at least 100 V between two phases, AND the load reaches approximately 20% of the breaker's rated current.
      • Note that the display will not power up with primary injection testing unless one of the conditions in bullet 1 above is met.
      • Note that Ammeter trip units do not require external power and the display will come on with sufficient current flow alone.
      See the following bulletins for more information on these trip units.