switch 1g arch b style s/s

Flush Switch, 1 Gang, 250VAC, 10A, Metal Plate Range, B Style, Architrave

Catalogue Number: B31A
switch 1g arch b style s/s
Colour: White Electric
Colour: Per UOM Std.
  • Black 1 PCE
  • Brown 1 PCE
  • White Electric 1 PCE
Added to cart

Specifications

hide show
Range of product
Metal Plate
Product brand
Clipsal
Device presentation
basic element with full cover plate and grid
Switch function
  • 2-way
  • 1-way
    • Actuator
      rocker
      Number of rocker
      1
      Device mounting
      flush
      Fixing mode
      by screws
      Surface treatment
      stainless steel
      Local signalling
      without
      [Ue] rated operational voltage
      250 V AC
      Rated current
      10 A
      Marking
      without marking
      EU RoHS Directive
      Compliant
      Environmental Disclosure
      ENVPEP120506EN

      Frequently Asked Questions

      hide show

      What is the dimensions for B31A (Stainless Steel) and BB31A (Polished Brass) Architrave Switch ?

      The dimensions are:
      Length x 90mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 70mm

      What is the dimensions for a B31A (Stainless Steel) and BB31A (Polished Brass) Architrave Switches ?

      The dimensions are:
      Length x 140mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 125mm

      What is the part number for a metal plate, stainless steel, single gang, architrave switch?

      The part number is B31A - BK  ( for black mech and bezel )

      What is the dimensions for the B32A (Stainless Steel) and BB32A (Polished Brass) Architrave Switches ?

      The dimensions are:
      Length x 110mm
      Width x 35mm
      Depth x 30mm
      Mounting Centres x 95mm

      Why is the LCD display screen blank on a Micrologic Power or Harmonic type trip unit on a Powerpact P frame, R frame, or Masterpact circuit breaker?

      Issue:
      Why is the display blank on the trip unit?

      Product Line:
      Powerpact P frame, Powerpact R Frame, Masterpact NT, Masterpact NW

      Environment:
      Applied to Powerpact and Masterpact breakers with trip units with LCD displays.

      Cause:
      Need to power display of the trip unit without external power supply.

      Resolution:
      The LCD display on a Micrologic P or H trip unit will be blank unless the trip unit is energized.  Energization requires one of the following sets of conditions:
      1. The trip unit is energized by an external 24 Vdc applied to terminals F1-F2 (F1 negative-F2 positive)
      2. The trip unit is energized by an FFTK or HHTK test kit
      3. There is at least 100 V between two phases, AND the load reaches approximately 20% of the breaker's rated current.
      • Note that the display will not power up with primary injection testing unless one of the conditions in bullet 1 above is met.
      • Note that Ammeter trip units do not require external power and the display will come on with sufficient current flow alone.
      See the following bulletins for more information on these trip units.
       

      How can you copy a old ATV31 program into a new ATV312 drive?

      Issue:
      Can you copy an ATV31 drives program into the new ATV312 drive?

      Product Line:
      Altivar ATV312, ATV31

      Environment:
      All

      Cause:
      Needs to use the old file from his ATV31 and put that program into his new ATV312 drive.

      Resolution:
      Yes, you can copy the old ATV31 file into the new ATV312 drive.
      You will need to set up your new ATV312 to act like a old ATV31 by setting the  ArE parameter to 31E or 31A.
      The differences are as follows.
      31A has the knob on the face of the old ATV31 drive.
      31E does not have the knob only the 4 buttons on the face of the drive.
      To copy the old program from the ATV31 into the new ATV312 drive you will need the original ATV31 remote keypad, Powersuite software V2.6 or the Multiloader.

      See the attached pdf document for notes.

      Can an ATV31 file be converted to an ATV312 file using SoMove software?

      Issue:
      Can an ATV31 file be converted to an ATV312 file using SoMove software?

      Product line:
      ATV31, ATV312

      Environment:
      All models, all serial numbers

      Cause:
      Need to connect to Blue Hose

      Resolution:
      It is not possible to transfer a configuration from ATV31 to ATV312 with SoMove software.  You will have to use the multiloader or the old ATV31 keypad to copy an 31 file into the ATV312 drive if you configure the ArE parameter to 31A or 31 E.
      The better solution is to generate the configuration file in Off-line Project for ATV312 then upload to Drives.