Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 250 kW 400 HP
Variable speed drive UL Type 1/IP20, size 13, 380-480V
Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 250 kW 400 HP
Variable speed drive UL Type 1/IP20, size 13, 380-480V

Altivar 71 Variable Speed Drive, 280kW, 450HP, 480V, EMC Filter-Graphic Terminal

Catalogue Number: ATV71HC28N4
Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 250 kW 400 HP
Variable speed drive UL Type 1/IP20, size 13, 380-480V
Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 250 kW 400 HP
Variable speed drive UL Type 1/IP20, size 13, 380-480V
Retail
$71273.54*
RRP (Inc. GST)

Specifications

hide show
Range of product
Altivar 71
Product or component type
variable speed drive
Product specific application
complex, high-power machines
Component name
ATV71
Motor power kW
280 kW, 3 phases at 380...480 V
Motor power hp
450 hp, 3 phases at 380...480 V
Maximum motor cable length
  • 100 m shielded cable
  • 200 m unshielded cable
    • [Us] rated supply voltage
      380...480 V - 15...10 %
      Network number of phases
      3 phases
      Line current
    • 396 A for 480 V 3 phases 280 kW / 450 hp
    • 494 A for 380 V 3 phases 280 kW / 450 hp
      • EMC filter
        integrated
        Assembly style
        with heat sink
        Variant
        reinforced version
        Apparent power
        325.1 kVA at 380 V 3 phases 280 kW / 450 hp
        Prospective line Isc
        50 kA for 3 phases
        Nominal output current
      • 550 A at 2.5 kHz 380 V 3 phases 280 kW / 450 hp
      • 550 A at 2.5 kHz 460 V 3 phases 280 kW / 450 hp
        • Maximum transient current
        • 825 A for 60 s 3 phases 280 kW / 450 hp
        • 907 A for 2 s 3 phases 280 kW / 450 hp
          • Output frequency
            0.1-500 Hz
            Nominal switching frequency
            2.5 kHz
            Switching frequency
          • 2.5...8 kHz adjustable
          • 2.5...8 kHz with derating factor
            • Asynchronous motor control profile
            • voltage/frequency ratio (2 or 5 points)
            • flux vector control (FVC) with sensor (current vector)
            • sensorless flux vector control (SFVC) (voltage or current vector)
            • ENA (Energy adaptation) system for unbalanced loads
              • Type of polarization
                no impedance for Modbus
                Product destination
              • asynchronous motors
              • synchronous motors
                • Supply voltage limits
                  323-528 V
                  Supply frequency
                  50...60 Hz - 5...5 %
                  Network frequency
                  47.5...63 Hz
                  Speed range
                • 1-100 for asynchronous motor in open-loop mode, without speed feedback
                • 1-1000 for asynchronous motor in closed-loop mode with encoder feedback
                • 1-50 for synchronous motor in open-loop mode, without speed feedback
                  • Speed accuracy
                  • +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn
                  • +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn
                    • Torque accuracy
                    • +/- 15 % in open-loop mode, without speed feedback
                    • +/- 5 % in closed-loop mode with encoder feedback
                      • Transient overtorque
                      • 170-170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes
                      • 220-220 % of nominal motor torque +/- 10 % for 2 s
                        • Braking torque
                        • <= 150 % with braking or hoist resistor
                        • 30 % without braking resistor
                          • Synchronous motor control profile
                            vector control without speed feedback
                            Regulation loop
                            adjustable PI regulator
                            Motor slip compensation
                          • automatic whatever the load
                          • not available in voltage/frequency ratio (2 or 5 points)
                          • adjustable
                          • suppressable
                            • Local signalling
                              1 LED (red)drive voltage:
                              Output voltage
                              <= power supply voltage
                              Insulation
                              electrical between power and control
                              Type of cable
                            • with a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
                            • with an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC
                            • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
                            • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
                              • Electrical connection
                              • terminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
                              • terminal, clamping capacity: 4 x 185 mm² (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
                              • terminal, clamping capacity: 4 x 185 mm² (PC/-, PA/+)
                                • Tightening torque
                                • 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
                                • 41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
                                • 41 N.m, 360 lb.in (PC/-, PA/+)
                                  • Supply
                                  • internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
                                  • internal supply: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection
                                    • Analogue input number
                                      2
                                      Analogue input type
                                    • AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign
                                    • AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits
                                    • AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
                                      • Sampling duration
                                      • 2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s)
                                      • 2 ms +/- 0.5 ms (Al2) - analog input(s)
                                      • 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s)
                                      • 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s)
                                        • Response time
                                        • <= 100 ms in STO (Safe Torque Off)
                                        • AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)
                                        • R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)
                                        • R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)
                                          • Accuracy
                                          • +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
                                          • +/- 0.6 % (AI2) for a temperature variation 60 °C
                                          • +/- 1 % (AO1) for a temperature variation 60 °C
                                            • Linearity error
                                            • +/- 0.15 % of maximum value (AI1-/Al1+, AI2)
                                            • +/- 0.2 % (AO1)
                                              • Analogue output number
                                                1
                                                Analogue output type
                                              • AO1 software-configurable logic output 10 V 20-20 mA
                                              • AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits
                                              • AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits
                                                • Discrete output number
                                                  2
                                                  Discrete output type
                                                • configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
                                                • configurable relay logic: (R2A, R2B) NO - 100000 cycles
                                                  • Minimum switching current
                                                    3 mA at 24 V DC for configurable relay logic
                                                    Maximum switching current
                                                  • R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4
                                                  • R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4
                                                  • R1, R2: 5 A at 250 V AC resistive load, cos phi = 1
                                                  • R1, R2: 5 A at 30 V DC resistive load, cos phi = 1
                                                    • Discrete input number
                                                      7
                                                      Discrete input type
                                                    • LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
                                                    • LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
                                                    • LI6: switch-configurable PTC probe 0-6 , impedance: 1500 Ohm
                                                    • PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d
                                                      • Discrete input logic
                                                      • negative logic (sink) (LI1...LI5), > 16 V (state 0), < 10 V (state 1)
                                                      • positive logic (source) (LI1...LI5), < 5 V (state 0), > 11 V (state 1)
                                                      • negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1)
                                                      • positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)
                                                        • Acceleration and deceleration ramps
                                                        • automatic adaptation of ramp if braking capacity exceeded, by using resistor
                                                        • linear adjustable separately from 0.01 to 9000 s
                                                        • S, U or customized
                                                          • Braking to standstill
                                                            by DC injection
                                                            Protection type
                                                          • against exceeding limit speed: drive
                                                          • short-circuit between motor phases: drive
                                                          • thermal protection: drive
                                                          • motor phase break: motor
                                                          • power removal: motor
                                                          • thermal protection: motor
                                                          • against input phase loss: drive
                                                          • break on the control circuit: drive
                                                          • input phase breaks: drive
                                                          • line supply overvoltage: drive
                                                          • line supply undervoltage: drive
                                                          • overcurrent between output phases and earth: drive
                                                          • overheating protection: drive
                                                          • overvoltages on the DC bus: drive
                                                            • Insulation resistance
                                                              > 1 mOhm 500 V DC for 1 minute to earth
                                                              Frequency resolution
                                                            • analog input: 0.024/50 Hz
                                                            • display unit: 0.1 Hz
                                                              • Communication port protocol
                                                              • Modbus
                                                              • CANopen
                                                                • Connector type
                                                                • 1 RJ45 (on front face) for Modbus
                                                                • 1 RJ45 (on terminal) for Modbus
                                                                • male SUB-D 9 on RJ45 for CANopen
                                                                  • Physical interface
                                                                    2-wire RS 485 for Modbus
                                                                    Transmission frame
                                                                    RTU for Modbus
                                                                    Transmission rate
                                                                  • 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
                                                                  • 9600 bps, 19200 bps for Modbus on front face
                                                                  • 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
                                                                    • Data format
                                                                    • 8 bits, 1 stop, even parity for Modbus on front face
                                                                    • 8 bits, odd even or no configurable parity for Modbus on terminal
                                                                      • Number of addresses
                                                                      • 1-127 for CANopen
                                                                      • 1-247 for Modbus
                                                                        • Method of access
                                                                          slave CANopen
                                                                          Marking
                                                                          CE
                                                                          Operating position
                                                                          vertical +/- 10 degree
                                                                          Height
                                                                          1190 mm
                                                                          Depth
                                                                          377 mm
                                                                          Width
                                                                          595 mm
                                                                          Net weight
                                                                          207 kg
                                                                          Functionality
                                                                          full
                                                                          Specific application
                                                                          other applications
                                                                          Option card
                                                                        • communication card for CC-Link
                                                                        • communication card for Modbus TCP
                                                                        • communication card for Modbus/Uni-Telway
                                                                        • overhead crane card
                                                                        • communication card for Profibus DP
                                                                        • communication card for Profibus DP V1
                                                                        • controller inside programmable card
                                                                        • communication card for DeviceNet
                                                                        • communication card for Ethernet/IP
                                                                        • communication card for Fipio
                                                                        • I/O extension card
                                                                        • communication card for Interbus-S
                                                                        • interface card for encoder
                                                                        • communication card for Modbus Plus
                                                                          • Noise level
                                                                            77 dB conforming to 86/188/EEC
                                                                            Dielectric strength
                                                                          • 3535 V DC between earth and power terminals
                                                                          • 5092 V DC between control and power terminals
                                                                            • Electromagnetic compatibility
                                                                            • 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
                                                                            • conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
                                                                            • electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
                                                                            • electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
                                                                            • radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
                                                                            • voltage dips and interruptions immunity test conforming to IEC 61000-4-11
                                                                              • Standards
                                                                              • EN/IEC 61800-5-1
                                                                              • IEC 60721-3-3 class 3C2
                                                                              • EN 61800-3 environments 1 category C3
                                                                              • EN/IEC 61800-3
                                                                              • EN 55011 class A group 2
                                                                              • UL Type 1
                                                                              • EN 61800-3 environments 2 category C3
                                                                                • Product certifications
                                                                                • NOM 117
                                                                                • C-Tick
                                                                                • GOST
                                                                                • UL
                                                                                • CSA
                                                                                  • Pollution degree
                                                                                  • 2 conforming to EN/IEC 61800-5-1
                                                                                  • 3 conforming to UL 840
                                                                                    • IP degree of protection
                                                                                      IP20
                                                                                      Vibration resistance
                                                                                    • 0.6 gn (f= 10-200 Hz) conforming to EN/IEC 60068-2-6
                                                                                    • 1.5 mm peak to peak (f= 3-10 Hz) conforming to EN/IEC 60068-2-6
                                                                                      • Shock resistance
                                                                                        4 gn for 11 ms conforming to EN/IEC 60068-2-27
                                                                                        Relative humidity
                                                                                      • 5-95 % without condensation conforming to IEC 60068-2-3
                                                                                      • 5-95 % without dripping water conforming to IEC 60068-2-3
                                                                                        • Ambient air temperature for operation
                                                                                          -10-50 °C (without)
                                                                                          Ambient air temperature for storage
                                                                                          -25-70 °C
                                                                                          Operating altitude
                                                                                        • <= 1000 m without
                                                                                        • 1000...3000 m with current derating 1 % per 100 m
                                                                                          • Sustainable offer status
                                                                                            Green Premium product
                                                                                            REACh Regulation
                                                                                            Free of Substances of Very High Concern above the threshold
                                                                                            EU RoHS Directive
                                                                                            Pro-active compliance (Product out of EU RoHS legal scope)
                                                                                            Mercury free
                                                                                            Yes
                                                                                            RoHS exemption information
                                                                                            Yes
                                                                                            China RoHS Regulation
                                                                                            X
                                                                                            Environmental Disclosure
                                                                                            ENVPEP091205EN
                                                                                            WEEE
                                                                                            The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                                                            California proposition 65
                                                                                            WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                                                                                            Warranty
                                                                                            18 months

                                                                                            Documents & downloads

                                                                                            hide show
                                                                                            Filter items
                                                                                            • All

                                                                                            • CAD Files and Packs

                                                                                            • Product Brochures

                                                                                            • Technical Data Catalogues

                                                                                            • Product Environmental

                                                                                            • End of Life Manual

                                                                                            • Handout

                                                                                            • Operating Manuals

                                                                                            • eTechPub

                                                                                            • Certificates (MSDS)

                                                                                            • Marine Certificate

                                                                                            • DTM Files

                                                                                            • Software - Released

                                                                                            Frequently Asked Questions

                                                                                            hide show

                                                                                            Which ATV71 drives have the built in braking transistor?

                                                                                            Models with a rating of 160KW (250HP) or less have a built-in braking transistor.
                                                                                            ATV71H...M3, ATV71H...M3X and ATV71H075N4 to HC16N4 drives have a built-in dynamic brake transistor.
                                                                                            For ATV71HC20N4 to HC50N4 drives, a separate braking unit must be used.


                                                                                            CTA-ID : 2026409

                                                                                            What should be checked if an Altivar 61 or 71 display is showing NLP?

                                                                                            Issue:
                                                                                            Wondering what should be checked if an Altivar 61 or 71 display is showing NLP?

                                                                                            Product Line:
                                                                                            ATV61/71 drives

                                                                                            Environment:
                                                                                            All

                                                                                            Cause:
                                                                                            Drive displays 'NLP'

                                                                                            Resolution:
                                                                                            NLP indicates that no line power is present on the L1, L2 & L3 input terminals of the drive controller.

                                                                                            Check voltage at the L1, L2 & L3 terminals.
                                                                                            Check for open circuits on line contactors, circuit breakers, disconnect switches, or fuses.

                                                                                            If NLP state does not change with correct voltage present on L1, L2, & L3, remove the control board and check for loose connections of ribbon cables inside the drive.
                                                                                            WARNING: This step should be performed while the drive is powered down, and proper personal protective equipment should be worn. 

                                                                                            For example: In an ATV71HC25N4 a customer found a loose X3 connector from the control board to the board behind and above the control board. This connector was on a ribbon cable that was about 1 inch by 1 inch. Drive ran OK after this was reseated.

                                                                                            Is there a problem using Altivar 61 or Altivar 71 drives delta power system?

                                                                                            Issue:
                                                                                            Wants to use Altivar 61 or Altivar 71 drives on delta power system.

                                                                                            Product Line:
                                                                                            Altivar ATV61 and ATV71

                                                                                            Environment:
                                                                                            All

                                                                                            Cause:
                                                                                            Needs to know if the RFI filter needs to be disabled when using a corner grounded delta system?

                                                                                            Resolution:
                                                                                            As long as the input voltage remains within the normal range there should not be a problem.
                                                                                            This should be treated the same way as an impedance grounded system.
                                                                                            Remove the jumper to the left of the power terminal.
                                                                                            See the section of the installation manual for Operation on an IT (Isolated or impedance grounded neutral) system for details.
                                                                                            See the drives installation manual for more information and location of the RFI's filter tab.

                                                                                            The figure 1 example below is for the low horsepower ATV61 and ATV71 drives.


                                                                                                                                               Figure 1.

                                                                                             

                                                                                            Is there an offer for Nema 4X rated drives?

                                                                                            Issue:
                                                                                            Wondering if the ATV61 or ATV71 drives are available in type 4 or 4X enclosures?

                                                                                            Product Line:
                                                                                            Altivar ATV61 and ATV71 open type drives

                                                                                            Environment:
                                                                                            All

                                                                                            Cause:
                                                                                            Needs to get the ATV61 and ATV71 drive in a NEMA 4 or 4X stand alone enclosure.

                                                                                            Resolution:
                                                                                            There is not a standard offering for type 4 or 4X enclosures for our drives.
                                                                                            It may be possible to install the drive in a properly selected enclosure by a local panel builder or contractor.
                                                                                            Or, contact a local SquareD field office for assistance. They may be able to offer assistance with other options.

                                                                                            Can the analog output of the ATV61 or ATV71 be set up as 0-10 VDC instead of 4-20 mA?

                                                                                            Issue:
                                                                                            Needs to set up a analog output of the ATV61 or ATV71 drive, to be set up as 0-10 VDC instead of 4-20 mA.

                                                                                            Product Line:
                                                                                            ATV61 and ATV71

                                                                                            Environment:
                                                                                            All

                                                                                            Cause:
                                                                                            NA

                                                                                            Resolution:
                                                                                            Yes.
                                                                                            Go to the Input/Output menu (1.5) and set AO1 type to voltage (0-10v range). Set AO1 assignment to the proper setting. The minimum and maxim range can also be adjusted inside the 0-10 V or 4-20  mA ranges.


                                                                                             

                                                                                            Why is the keypad not included with ATV61 and ATV71 drives?

                                                                                            Issue:
                                                                                            The keypad is not included with ATV61 and ATV71 drives.

                                                                                            Product Line:
                                                                                            Altivar 61 and 71 drives

                                                                                            Environment:
                                                                                            All

                                                                                            Cause:
                                                                                            Customer concerned whether the HMI came with the drive

                                                                                            Resolution:
                                                                                            For all ATV61 and ATV71 drives without the letter Z at the end of the part number the keypad is included.
                                                                                            However, it is easy to not notice the keypad in the packaging material. The keypad is located inside folded cardboard that also functions as packing material. Check inside all folded cardboard packing materials. There is no sticker to indicate that the keypad is inside.

                                                                                            ATV61 & ATV71 drives with the letter Z at the end of the part number do not include the removable LCD HMI keypad display. These units do have a simplified LED display and programming keys on the face of the control board itself. The removable LCD HMI keypad display may be installed on these units.


                                                                                             

                                                                                            Do the electronic boards of the Altivar 61 and Altivar 71 drives have conformal coating?

                                                                                            Issue:
                                                                                            Do the electronic boards of the Altivar 61 and Altivar 71 drives have conformal coating?

                                                                                            Product Line:
                                                                                            Altivar ATV61 and ATV71

                                                                                            Environment:
                                                                                            Suffix S337 only

                                                                                            Cause:
                                                                                            Needs to know if you can order the ATV61 ATV71 drive with conformal coating?

                                                                                            Resolution:
                                                                                            For the ATV61 & ATV71 drives there is an option to have product treated for increased protection for dusty and corrosive environments. This product is not stocked. Add 'S337' to the end of the catalog number and multiply the listed price by 1.2 to obtain new price. With this option, exposed copper is tinned, circuit boards are conformal coated in critical areas and plastics are treated to better withstand the corrosive nature of certain oils. This option is standard on 55kW/75HP @ 230 Vac and higher & 90kW/125HP @ 460 Vac and higher.

                                                                                            The standard ATV61 and ATV71 drives are designed for maximum ambient pollution as follows:
                                                                                            ATV71:
                                                                                            H...M3, 71HD11M3X, HD15M3X, H075N4 to HD18N4 are Degree 2 conforming to IEC/EN 61800-5-1
                                                                                            HD18M3X to HD75M3X, HD22N4 to HC50N4 are Degree 3 conforming to IEC/EN 61800-5-1

                                                                                            ATV61:
                                                                                            H...M3, HD11M3X, HD15M3X, H075N4 to HD18N4 are Degree 2 conforming to IEC/EN 61800-5-1
                                                                                            HD18M3X to HD90M3X, HD22N4 to HC63N4 are Degree 3 conforming to IEC/EN 61800-5-1


                                                                                             

                                                                                            How many drive configuration files can be stored in the ATV71 keypad?

                                                                                            Issue:   
                                                                                            Storing drive configuration files in the ATV61 / ATV71 keypad.
                                                                                             
                                                                                            Product Line:   
                                                                                            ATV61 ,ATV71
                                                                                             
                                                                                            Environment:  
                                                                                            All
                                                                                             
                                                                                            Cause:  
                                                                                            Ffiles stored in keypad
                                                                                             
                                                                                            Resolution:   
                                                                                            The keypad can store up to 4 files.
                                                                                            To access and manage these files: Go to menu 1.12 (FACTORY SETTINGS) (FCS-)
                                                                                            See programming manual for details, if needed.


                                                                                             

                                                                                            What is the recommended Fuse or Circuit Breaker (OCPD) size for Altivar 61 drives?

                                                                                            Refer to the attached Quick Start Annex, document S1B86981. 
                                                                                             

                                                                                            When do the heatsink fans run on the ATV61 / ATV71 series drives?

                                                                                            Issue:
                                                                                            When do the heatsink fans run on the ATV61 / ATV71 series drives?

                                                                                            Product Line:
                                                                                            Altivar 61 and Altivar 71 series drives

                                                                                            Environment:
                                                                                            All models, All serial numbers.

                                                                                            Cause:
                                                                                            Information not available in current literature.

                                                                                            Resolution:
                                                                                            Heat sink fan operation differs depending on the frame size of the drive:
                                                                                            - for size 2 to 5B drives, fans start when the drive thermal state reaches a temperature level --> THD parameter = 70%.  The fans turns off when drive thermal is less than 60%
                                                                                            - for size 6 to 8 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 1 minute after the run command is removed.
                                                                                            - for size 9 to 15 drives and 690V range drives, the fans run when the run command is given or when the drive thermal is greater than or equal to 70% and turns off when the drive thermal is less than 60% and runs for 10 minutes after the run command is removed.

                                                                                            For example, an ATV61HD18M3X drive (size 6), the heatsink fan starts when a Run command is given.


                                                                                             

                                                                                            Are the ATV61/71 high horsepower drives available without the DC choke?

                                                                                            Yes.  Add a D suffix to the drive part number.
                                                                                            For example:
                                                                                            ATV61HC22N4 includes a DC choke.
                                                                                            ATV61HC22N4D does not include a DC choke.

                                                                                            Note that if a DC choke is not used, a jumper wire, of sufficient current capacity, must  be installed between the PA and PO terminals.  A good rule of thumb is to use the same size wire that is on the DC choke for the jumper wire.   Also, if the DC choke is not used, a 5% line reactor ahead of the drive is Mandatory.  Failure to use a 5% line reactor ahead of the drive if no DC choke is present can result in damage to the drive that warranty does not cover.


                                                                                            CTA-ID : 2061651

                                                                                            What is the part number of the Main Control board for ATV71HD22N4?

                                                                                            Issue:
                                                                                            ATV71HD22N4:  Need to replace the Main Control board ?

                                                                                            Product Line:
                                                                                            ATV71

                                                                                            Environment:
                                                                                            ATV71HO75N4, ATV71HU15N4, ATV71HU22N4, ATV71HU30N4, ATV71HU40N4, ATV71HU55N4, ATV71HU75N4, ATV71HD11N4, ATV71HD15N4, ATV71HD18N4, ATV71HD22N4, ATV71HD30N4, ATV71HD37N4, ATV71HD45N4, ATV71HD55N4, ATV71HD75N4

                                                                                            Cause:
                                                                                            Need the Main Control board part number.

                                                                                            Resolution:
                                                                                            The Main Control board part number for these drive is VX4A71100Y
                                                                                            Show More