Quantcast

Altivar 71 Variable Speed Drive, 250kW, 400HP, 480V, EMC Filter-Graphic Terminal

Altivar 71 Variable Speed Drive, 250kW, 400HP, 480V, EMC Filter-Graphic Terminal

Altivar 71 Variable Speed Drive, 250kW, 400HP, 480V, EMC Filter-Graphic Terminal

Item Number: ATV71HC25N4

Datasheet

Product Dimensions

Width icon

Width595 mm

Height icon

Height1190 mm

Depth icon

Depth377 mm

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altivar 71

Product or component type

variable speed drive

Product destination

  • synchronous motors
  • asynchronous motors

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Local signalling

1 LED (red) for drive voltage

Type of cable

  • with a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
  • with an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC
  • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
  • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR

Supply

  • internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 ma,="" protection="" type:="" overload="" and="" short-circuit="">
  • internal supply: 24 V DC (21-27 V), <200 ma,="" protection="" type:="" overload="" and="" short-circuit="">

Protection type

  • against exceeding limit speed: drive
  • short-circuit between motor phases: drive
  • thermal protection: drive
  • motor phase break: motor
  • power removal: motor
  • thermal protection: motor
  • against input phase loss: drive
  • break on the control circuit: drive
  • input phase breaks: drive
  • line supply overvoltage: drive
  • line supply undervoltage: drive
  • overcurrent between output phases and earth: drive
  • overheating protection: drive
  • overvoltages on the DC bus: drive

Insulation resistance

> 1 mOhm 500 V DC for 1 minute to earth

Communication port protocol

  • CANopen
  • Modbus

Connector type

  • 1 RJ45 (on front face) for Modbus
  • 1 RJ45 (on terminal) for Modbus
  • male SUB-D 9 on RJ45 for CANopen

Marking

CE

Height

1190 mm

Depth

377 mm

Width

595 mm

Net weight

207 kg

Standards

  • EN/IEC 61800-5-1
  • UL Type 1
  • IEC 60721-3-3 class 3C2
  • EN 61800-3 environments 1 category C3
  • EN/IEC 61800-3
  • EN 55011 class A group 2
  • EN 61800-3 environments 2 category C3

Product certifications

  • NOM 117
  • GOST
  • CSA
  • C-Tick
  • UL

IP degree of protection

IP20

Relative humidity

  • 5...95 % without condensation conforming to IEC 60068...2-3
  • 5...95 % without dripping water conforming to IEC 60068...2-3

Ambient air temperature for operation

-10...50 °C (without derating)

Ambient air temperature for storage

-25...70 °C

EU RoHS Directive

Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free

Yes

RoHS exemption information

Yes

China RoHS Regulation

X

Environmental Disclosure

ENVPEP091205EN

California proposition 65

WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Others

Package 1 Bare Product Quantity

1

Product specific application

complex, high-power machines

Component name

ATV71

Motor power kW

  • 220 kW, 3 phases at 380...480 V
  • 250 kW, 3 phases at 380...480 V

Motor power hp

  • 350 hp, 3 phases at 380...480 V
  • 400 hp, 3 phases at 380...480 V

Maximum motor cable length

  • 100 m shielded cable
  • 200 m unshielded cable

[Us] rated supply voltage

380...480 V - 15...10 %

Network number of phases

3 phases

Line current

  • 320 A for 480 V 3 phases 220 kW / 350 hp
  • 357 A for 480 V 3 phases 250 kW / 400 hp
  • 396 A for 380 V 3 phases 220 kW / 350 hp
  • 444 A for 380 V 3 phases 250 kW / 400 hp

EMC filter

integrated

Assembly style

with heat sink

Variant

reinforced version

Apparent power

  • 260.6 kVA at 380 V 3 phases 220 kW / 350 hp
  • 292.2 kVA at 380 V 3 phases 250 kW / 400 hp

Prospective line Isc

50 kA for 3 phases

Nominal output current

  • 427 A at 2.5 kHz 380 V 3 phases 220 kW / 350 hp
  • 427 A at 2.5 kHz 460 V 3 phases 220 kW / 350 hp
  • 481 A at 2.5 kHz 380 V 3 phases 250 kW / 400 hp
  • 481 A at 2.5 kHz 460 V 3 phases 250 kW / 400 hp

Maximum transient current

  • 640 A for 60 s 3 phases 220 kW / 350 hp
  • 704 A for 2 s 3 phases 220 kW / 350 hp
  • 721 A for 60 s 3 phases 250 kW / 400 hp
  • 793 A for 2 s 3 phases 250 kW / 400 hp

Output frequency

0.1...500 Hz

Nominal switching frequency

2.5 kHz

Switching frequency

  • 2.5...8 kHz adjustable
  • 2.5...8 kHz with derating factor

Asynchronous motor control profile

  • sensorless flux vector control (SFVC) (voltage or current vector)
  • flux vector control (FVC) with sensor (current vector)
  • voltage/frequency ratio (2 or 5 points)
  • ENA (Energy adaptation) system for unbalanced loads

Type of polarization

no impedance for Modbus

Supply voltage limits

323...528 V

Supply frequency

50...60 Hz - 5...5 %

Network frequency

47.5...63 Hz

Speed range

  • 1...100 for asynchronous motor in open-loop mode, without speed feedback
  • 1...1000 for asynchronous motor in closed-loop mode with encoder feedback
  • 1...50 for synchronous motor in open-loop mode, without speed feedback

Speed accuracy

  • +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn
  • +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn

Torque accuracy

  • +/- 15 % in open-loop mode, without speed feedback
  • +/- 5 % in closed-loop mode with encoder feedback

Transient overtorque

  • 170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes
  • 220 % of nominal motor torque +/- 10 % for 2 s

Braking torque

  • <= 150="" %="" with="" braking="" or="" hoist="">
  • 30 % without braking resistor

Synchronous motor control profile

vector control without speed feedback

Regulation loop

adjustable PI regulator

Motor slip compensation

  • not available in voltage/frequency ratio (2 or 5 points)
  • automatic whatever the load
  • adjustable
  • suppressable

Output voltage

<= power="" supply="">

Insulation

electrical between power and control

Electrical connection

  • terminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
  • terminal, clamping capacity: 4 x 185 mm² (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
  • terminal, clamping capacity: 4 x 185 mm² (PC/-, PA/+)

Tightening torque

  • 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
  • 41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
  • 41 N.m, 360 lb.in (PC/-, PA/+)

Analogue input number

2

Analogue input type

  • AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign
  • AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits
  • AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits

Sampling duration

  • 2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s)
  • 2 ms +/- 0.5 ms (Al2) - analog input(s)
  • 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s)
  • 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s)

Response time

  • <= 100="" ms="" in="" sto="" (safe="" torque="">
  • AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)
  • R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)
  • R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)

Accuracy

  • +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
  • +/- 0.6 % (AI2) for a temperature variation 60 °C
  • +/- 1 % (AO1) for a temperature variation 60 °C

Linearity error

  • +/- 0.15 % of maximum value (AI1-/Al1+, AI2)
  • +/- 0.2 % (AO1)

Analogue output number

1

Analogue output type

  • AO1 software-configurable logic output 10 V 20-20 mA
  • AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits
  • AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits

Discrete output number

2

Discrete output type

  • configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
  • configurable relay logic: (R2A, R2B) NO - 100000 cycles

Minimum switching current

3 mA at 24 V DC for configurable relay logic

Maximum switching current

  • R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4
  • R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4
  • R1, R2: 5 A at 250 V AC resistive load, cos phi = 1
  • R1, R2: 5 A at 30 V DC resistive load, cos phi = 1

Discrete input number

7

Discrete input type

  • LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
  • LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
  • LI6: switch-configurable PTC probe 0-6 , impedance: 1500 Ohm
  • PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d

Discrete input logic

  • negative logic (sink) (LI1...LI5), > 16 V (state 0), < 10="" v="" (state="">
  • positive logic (source) (LI1...LI5), < 5="" v="" (state="" 0),=""> 11 V (state 1)
  • negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10="" v="" (state="">
  • positive logic (source) (LI6)if configured as logic input, < 5="" v="" (state="" 0),=""> 11 V (state 1)

Acceleration and deceleration ramps

  • automatic adaptation of ramp if braking capacity exceeded, by using resistor
  • linear adjustable separately from 0.01 to 9000 s
  • S, U or customized

Braking to standstill

by DC injection

Frequency resolution

  • analog input: 0.024/50 Hz
  • display unit: 0.1 Hz

Physical interface

2-wire RS 485 for Modbus

Transmission frame

RTU for Modbus

Transmission rate

  • 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
  • 9600 bps, 19200 bps for Modbus on front face
  • 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen

Data format

  • 8 bits, 1 stop, even parity for Modbus on front face
  • 8 bits, odd even or no configurable parity for Modbus on terminal

Number of addresses

  • 1...127 for CANopen
  • 1...247 for Modbus

Method of access

slave CANopen

Operating position

vertical +/- 10 degree

Functionality

full

Specific application

other applications

Option card

  • communication card for CC-Link
  • communication card for Modbus TCP
  • communication card for Modbus/Uni-Telway
  • overhead crane card
  • communication card for Profibus DP
  • communication card for Profibus DP V1
  • controller inside programmable card
  • communication card for DeviceNet
  • communication card for EtherNet/IP
  • communication card for Fipio
  • I/O extension card
  • communication card for Interbus-S
  • interface card for encoder
  • communication card for Modbus Plus

Noise level

77 dB conforming to 86/188/EEC

Dielectric strength

  • 3535 V DC between earth and power terminals
  • 5092 V DC between control and power terminals

Electromagnetic compatibility

  • 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
  • conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
  • electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
  • electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
  • voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Pollution degree

  • 2 conforming to EN/IEC 61800-5-1
  • 3 conforming to UL 840

Vibration resistance

  • 0.6 gn (f= 10-200 Hz) conforming to EN/IEC 60068-2-6
  • 1.5 mm peak to peak (f= 3-10 Hz) conforming to EN/IEC 60068-2-6

Shock resistance

4 gn for 11 ms conforming to EN/IEC 60068-2-27

Operating altitude

  • <= 1000="" m="" without="">
  • 1000...3000 m with current derating 1 % per 100 m

Unit Type of Package 1

PCE

Number of Units in Package 1

1

Package 1 Height

43.0 cm

Package 1 Width

51.0 cm

Package 1 Length

122.5 cm

Package 1 Weight

68.0 kg

WEEE

The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Show all specifications

Documents & downloads

hide show
Filter items
  • All

  • CAD Files and Packs

  • Technical Data Catalogues

  • Installation Instruction

  • Environmental Disclosure

  • End of Life Manual

  • Operating Manuals

  • Technical Drawing

  • Certificates (MSDS)

  • Declaration of Conformity

  • eTechPub

  • Software - Release

  • DTM files

Frequently Asked Questions

hide show

What is the inrush current of the ATV61 High horse power VFDs?

Issue:
Inrush current of the ATV61 / ATV71 High horse power VFDs.

Product Line:
ATV61HC11N4,  ATV61HC31N4, ATV61HC25N4,  ATV61HC40N4,  ATV61HC63N4
ATV71HD90N4, ATV71HC20N4,  ATV71HC25N4,  ATV71HC31N4,  ATV71HC50N4 

Environment:
All 

Cause:
Application requirement.

Resolution:
Inrush current
Drive power  [kW]             I peak [A] (~2ms)                  I peak [A] (~2ms)
ATV71    ATV61               @ 480V +10%                        @ 400V
90               110                   275                                        208
200             250                   556                                        421
250             315                   764                                        579
310             400                   802                                        608
500             630                  1500                                     1136