Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 220 kW 350 HP

Altivar 71 Variable Speed Drive, 250kW, 400HP, 480V, EMC Filter-Graphic Terminal

Catalogue Number: ATV71HC25N4
Variable speed drive Altivar 71 UL type 1/IP20 three-phase supply voltage: 380…480V 50/60 Hz, 220 kW 350 HP
Colour:
Colour: Per UOM Std.
  • 1 PCE
Added to cart
Successfully added, you can view your cart here

Key Features & Specifications

hide show
Range of product
Altivar 71
Product or component type
variable speed drive
Product specific application
complex, high-power machines
Component name
ATV71
Motor power kW
  • 220 kW, 3 phases at 380...480 V
  • 250 kW, 3 phases at 380...480 V
    • Motor power hp
    • 350 hp, 3 phases at 380...480 V
    • 400 hp, 3 phases at 380...480 V
      • Maximum motor cable length
      • 100 m shielded cable
      • 200 m unshielded cable
        • [Us] rated supply voltage
          380...480 V - 15...10 %
          Network number of phases
          3 phases
          Line current
        • 320 A for 480 V 3 phases 220 kW / 350 hp
        • 357 A for 480 V 3 phases 250 kW / 400 hp
        • 396 A for 380 V 3 phases 220 kW / 350 hp
        • 444 A for 380 V 3 phases 250 kW / 400 hp
          • EMC filter
            integrated
            Assembly style
            with heat sink
            Variant
            reinforced version
            Apparent power
          • 260.6 kVA at 380 V 3 phases 220 kW / 350 hp
          • 292.2 kVA at 380 V 3 phases 250 kW / 400 hp
            • Prospective line Isc
              50 kA for 3 phases
              Nominal output current
            • 427 A at 2.5 kHz 380 V 3 phases 220 kW / 350 hp
            • 427 A at 2.5 kHz 460 V 3 phases 220 kW / 350 hp
            • 481 A at 2.5 kHz 380 V 3 phases 250 kW / 400 hp
            • 481 A at 2.5 kHz 460 V 3 phases 250 kW / 400 hp
              • Maximum transient current
              • 640 A for 60 s 3 phases 220 kW / 350 hp
              • 704 A for 2 s 3 phases 220 kW / 350 hp
              • 721 A for 60 s 3 phases 250 kW / 400 hp
              • 793 A for 2 s 3 phases 250 kW / 400 hp
                • Output frequency
                  0.1-500 Hz
                  Nominal switching frequency
                  2.5 kHz
                  Switching frequency
                • 2.5...8 kHz adjustable
                • 2.5...8 kHz with derating factor
                  • Asynchronous motor control profile
                  • sensorless flux vector control (SFVC) (voltage or current vector)
                  • flux vector control (FVC) with sensor (current vector)
                  • voltage/frequency ratio (2 or 5 points)
                  • ENA (Energy adaptation) system for unbalanced loads
                    • Type of polarization
                      no impedance for Modbus
                      Product destination
                    • synchronous motors
                    • asynchronous motors
                      • Supply voltage limits
                        323-528 V
                        Supply frequency
                        50...60 Hz - 5...5 %
                        Network frequency
                        47.5...63 Hz
                        Speed range
                      • 1-100 for asynchronous motor in open-loop mode, without speed feedback
                      • 1-1000 for asynchronous motor in closed-loop mode with encoder feedback
                      • 1-50 for synchronous motor in open-loop mode, without speed feedback
                        • Speed accuracy
                        • +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn
                        • +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn
                          • Torque accuracy
                          • +/- 15 % in open-loop mode, without speed feedback
                          • +/- 5 % in closed-loop mode with encoder feedback
                            • Transient overtorque
                            • 170-170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes
                            • 220-220 % of nominal motor torque +/- 10 % for 2 s
                              • Braking torque
                              • <= 150 % with braking or hoist resistor
                              • 30 % without braking resistor
                                • Synchronous motor control profile
                                  vector control without speed feedback
                                  Regulation loop
                                  adjustable PI regulator
                                  Motor slip compensation
                                • not available in voltage/frequency ratio (2 or 5 points)
                                • automatic whatever the load
                                • adjustable
                                • suppressable
                                  • Local signalling
                                    1 LED (red)drive voltage:
                                    Output voltage
                                    <= power supply voltage
                                    Insulation
                                    electrical between power and control
                                    Type of cable
                                  • with a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
                                  • with an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC
                                  • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
                                  • without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
                                    • Electrical connection
                                    • terminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
                                    • terminal, clamping capacity: 4 x 185 mm² (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
                                    • terminal, clamping capacity: 4 x 185 mm² (PC/-, PA/+)
                                      • Tightening torque
                                      • 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR)
                                      • 41 N.m, 360 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3)
                                      • 41 N.m, 360 lb.in (PC/-, PA/+)
                                        • Supply
                                        • internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection
                                        • internal supply: 24 V DC (21-27 V), <200 mA, protection type: overload and short-circuit protection
                                          • Analogue input number
                                            2
                                            Analogue input type
                                          • AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign
                                          • AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits
                                          • AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits
                                            • Sampling duration
                                            • 2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s)
                                            • 2 ms +/- 0.5 ms (Al2) - analog input(s)
                                            • 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s)
                                            • 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s)
                                              • Response time
                                              • <= 100 ms in STO (Safe Torque Off)
                                              • AO1 2 ms, tolerance +/- 0.5 ms for analog output(s)
                                              • R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s)
                                              • R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)
                                                • Accuracy
                                                • +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C
                                                • +/- 0.6 % (AI2) for a temperature variation 60 °C
                                                • +/- 1 % (AO1) for a temperature variation 60 °C
                                                  • Linearity error
                                                  • +/- 0.15 % of maximum value (AI1-/Al1+, AI2)
                                                  • +/- 0.2 % (AO1)
                                                    • Analogue output number
                                                      1
                                                      Analogue output type
                                                    • AO1 software-configurable logic output 10 V 20-20 mA
                                                    • AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits
                                                    • AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits
                                                      • Discrete output number
                                                        2
                                                        Discrete output type
                                                      • configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles
                                                      • configurable relay logic: (R2A, R2B) NO - 100000 cycles
                                                        • Minimum switching current
                                                          3 mA at 24 V DC for configurable relay logic
                                                          Maximum switching current
                                                        • R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4
                                                        • R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4
                                                        • R1, R2: 5 A at 250 V AC resistive load, cos phi = 1
                                                        • R1, R2: 5 A at 30 V DC resistive load, cos phi = 1
                                                          • Discrete input number
                                                            7
                                                            Discrete input type
                                                          • LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm
                                                          • LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm
                                                          • LI6: switch-configurable PTC probe 0-6 , impedance: 1500 Ohm
                                                          • PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d
                                                            • Discrete input logic
                                                            • negative logic (sink) (LI1...LI5), > 16 V (state 0), < 10 V (state 1)
                                                            • positive logic (source) (LI1...LI5), < 5 V (state 0), > 11 V (state 1)
                                                            • negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1)
                                                            • positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)
                                                              • Acceleration and deceleration ramps
                                                              • automatic adaptation of ramp if braking capacity exceeded, by using resistor
                                                              • linear adjustable separately from 0.01 to 9000 s
                                                              • S, U or customized
                                                                • Braking to standstill
                                                                  by DC injection
                                                                  Protection type
                                                                • against exceeding limit speed: drive
                                                                • short-circuit between motor phases: drive
                                                                • thermal protection: drive
                                                                • motor phase break: motor
                                                                • power removal: motor
                                                                • thermal protection: motor
                                                                • against input phase loss: drive
                                                                • break on the control circuit: drive
                                                                • input phase breaks: drive
                                                                • line supply overvoltage: drive
                                                                • line supply undervoltage: drive
                                                                • overcurrent between output phases and earth: drive
                                                                • overheating protection: drive
                                                                • overvoltages on the DC bus: drive
                                                                  • Insulation resistance
                                                                    > 1 mOhm 500 V DC for 1 minute to earth
                                                                    Frequency resolution
                                                                  • analog input: 0.024/50 Hz
                                                                  • display unit: 0.1 Hz
                                                                    • Communication port protocol
                                                                    • CANopen
                                                                    • Modbus
                                                                      • Connector type
                                                                      • 1 RJ45 (on front face) for Modbus
                                                                      • 1 RJ45 (on terminal) for Modbus
                                                                      • male SUB-D 9 on RJ45 for CANopen
                                                                        • Physical interface
                                                                          2-wire RS 485 for Modbus
                                                                          Transmission frame
                                                                          RTU for Modbus
                                                                          Transmission rate
                                                                        • 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal
                                                                        • 9600 bps, 19200 bps for Modbus on front face
                                                                        • 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen
                                                                          • Data format
                                                                          • 8 bits, 1 stop, even parity for Modbus on front face
                                                                          • 8 bits, odd even or no configurable parity for Modbus on terminal
                                                                            • Number of addresses
                                                                            • 1-127 for CANopen
                                                                            • 1-247 for Modbus
                                                                              • Method of access
                                                                                slave CANopen
                                                                                Marking
                                                                                CE
                                                                                Operating position
                                                                                vertical +/- 10 degree
                                                                                Height
                                                                                1190 mm
                                                                                Depth
                                                                                377 mm
                                                                                Width
                                                                                595 mm
                                                                                Net weight
                                                                                207 kg
                                                                                Functionality
                                                                                full
                                                                                Specific application
                                                                                other applications
                                                                                Option card
                                                                              • communication card for CC-Link
                                                                              • communication card for Modbus TCP
                                                                              • communication card for Modbus/Uni-Telway
                                                                              • overhead crane card
                                                                              • communication card for Profibus DP
                                                                              • communication card for Profibus DP V1
                                                                              • controller inside programmable card
                                                                              • communication card for DeviceNet
                                                                              • communication card for Ethernet/IP
                                                                              • communication card for Fipio
                                                                              • I/O extension card
                                                                              • communication card for Interbus-S
                                                                              • interface card for encoder
                                                                              • communication card for Modbus Plus
                                                                                • Noise level
                                                                                  77 dB conforming to 86/188/EEC
                                                                                  Dielectric strength
                                                                                • 3535 V DC between earth and power terminals
                                                                                • 5092 V DC between control and power terminals
                                                                                  • Electromagnetic compatibility
                                                                                  • 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
                                                                                  • conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
                                                                                  • electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
                                                                                  • electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
                                                                                  • radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
                                                                                  • voltage dips and interruptions immunity test conforming to IEC 61000-4-11
                                                                                    • Standards
                                                                                    • EN/IEC 61800-5-1
                                                                                    • UL Type 1
                                                                                    • IEC 60721-3-3 class 3C2
                                                                                    • EN 61800-3 environments 1 category C3
                                                                                    • EN/IEC 61800-3
                                                                                    • EN 55011 class A group 2
                                                                                    • EN 61800-3 environments 2 category C3
                                                                                      • Product certifications
                                                                                      • NOM 117
                                                                                      • GOST
                                                                                      • CSA
                                                                                      • C-Tick
                                                                                      • UL
                                                                                        • Pollution degree
                                                                                        • 2 conforming to EN/IEC 61800-5-1
                                                                                        • 3 conforming to UL 840
                                                                                          • IP degree of protection
                                                                                            IP20
                                                                                            Vibration resistance
                                                                                          • 0.6 gn (f= 10-200 Hz) conforming to EN/IEC 60068-2-6
                                                                                          • 1.5 mm peak to peak (f= 3-10 Hz) conforming to EN/IEC 60068-2-6
                                                                                            • Shock resistance
                                                                                              4 gn for 11 ms conforming to EN/IEC 60068-2-27
                                                                                              Relative humidity
                                                                                            • 5-95 % without condensation conforming to IEC 60068-2-3
                                                                                            • 5-95 % without dripping water conforming to IEC 60068-2-3
                                                                                              • Ambient air temperature for operation
                                                                                                -10-50 °C (without)
                                                                                                Ambient air temperature for storage
                                                                                                -25-70 °C
                                                                                                Operating altitude
                                                                                              • <= 1000 m without
                                                                                              • 1000...3000 m with current derating 1 % per 100 m
                                                                                                • Sustainable offer status
                                                                                                  Green Premium product
                                                                                                  REACh Regulation
                                                                                                  Free of Substances of Very High Concern above the threshold
                                                                                                  EU RoHS Directive
                                                                                                  Pro-active compliance (Product out of EU RoHS legal scope)
                                                                                                  Mercury free
                                                                                                  Yes
                                                                                                  RoHS exemption information
                                                                                                  Yes
                                                                                                  China RoHS Regulation
                                                                                                  X
                                                                                                  Environmental Disclosure
                                                                                                  ENVPEP091205EN
                                                                                                  Circularity Profile
                                                                                                  N/A
                                                                                                  WEEE
                                                                                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                                                                                  California proposition 65
                                                                                                  WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                                                                                                  Warranty
                                                                                                  18 months

                                                                                                  Documents & downloads

                                                                                                  hide show
                                                                                                  Filter items
                                                                                                  • All

                                                                                                  • CAD Files and Packs

                                                                                                  • Product Brochures

                                                                                                  • Movies

                                                                                                  • Technical Data Catalogues

                                                                                                  • Catalog Page

                                                                                                  • Technical Leaflet

                                                                                                  • Product Environmental

                                                                                                  • End of Life Manual

                                                                                                  • Handout

                                                                                                  • Installation Instruction

                                                                                                  • Data Bulletin

                                                                                                  • Operating Manuals

                                                                                                  • System User Guide

                                                                                                  • Specifications

                                                                                                  • Specification for Tender

                                                                                                  • Application Solutions

                                                                                                  • Case Studies

                                                                                                  • eTechPub

                                                                                                  • Certificates (MSDS)

                                                                                                  • Marine Certificate

                                                                                                  • White Paper

                                                                                                  • DTM Files

                                                                                                  • Software - Released

                                                                                                  • Software - Updates

                                                                                                  • EDS Files

                                                                                                  • GSD files