Number of Units in Package 1
1
Number of Units in Package 2
14
Unit Type of Package 1
PCE
Unit Type of Package 2
S03
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product specific application
simple machine
Network number of phases
3 phases
[Us] rated supply voltage
200...480 V - 10...10 %
Motor power kW
15 kW, 3 phases at 400 V7.5 kW, 3 phases at 230 V
Motor power hp
10 hp, 3 phases at 230 V20 hp, 3 phases at 460 V
Utilisation category
AC-53B conforming to EN/IEC 60947-4-2
Current consumption
100 mA
Type of start
start with voltage ramp
Power dissipation in W
2.5 W at full load and at end of starting322.5 W in transient state
Assembly style
with heat sink
Supply voltage limits
180-528 V
Supply frequency
50...60 Hz - 5...5 %
Network frequency
47.5...63 Hz
Output voltage
<= power supply voltage
[Uc] control circuit voltage
24 V DC +/- 10 %
Starting time
adjustable from 1 to 10 s1 s / 50 10 s / 5 5 s / 10
Deceleration time symb
adjustable from 1 to 10 s
Starting torque
30...80 % of starting torque of motor connected directly on the line supply
Discrete input type
logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
Discrete input voltage
24...40 V
Input output isolation
galvanic between power and control
Discrete input logic
positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
Discrete output type
open collector logic LO1 end of starting signalrelay outputs R1A, R1C NO
Discrete output voltage
24 V (voltage limits: 6...30 V) open collector logic
Minimum switching current
10 mA at 6 V DC for relay outputs
Maximum switching current
relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive loadrelay outputs: 2 A at 250 V AC AC-15 cos phi = 0.5 and L/R = 20 ms inductive load
Maximum switching voltage
440 V relay outputs
Display type
1 LED (green) for starter powered up1 LED (yellow) for nominal voltage reached
Electrical connection
4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuitscrew connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuitscrew connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuitscrew connector - rigid 2 0.5...1 mm² AWG 17 control circuitscrew connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuitscrew connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
Operating position
vertical +/- 10 degree
Power range
7-11 kW at 200-240 V 3 phases15-25 kW at 380-440 V 3 phases
Motor starter type
soft starter
Electromagnetic compatibility
conducted and radiated emissions level B conforming to CISPR 11immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3voltage/current impulse level 3 conforming to IEC 61000-4-5conducted and radiated emissions level 3 conforming to IEC 61000-4-6immunity to conducted interference caused by radio-electrical fields conforming to IEC 61000-4-11conducted and radiated emissions level B conforming to IEC 60947-4-2damped oscillating waves level 3 conforming to IEC 61000-4-12electrostatic discharge level 3 conforming to IEC 61000-4-2EMC immunity conforming to EN 50082-1EMC immunity conforming to EN 50082-2harmonics conforming to IEC 1000-3-2harmonics conforming to IEC 1000-3-4immunity to electrical transients level 4 conforming to IEC 61000-4-4
Pollution degree
2 conforming to EN/IEC 60947-4-2
Vibration resistance
1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-61.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Operating altitude
<= 1000 m without derating> 1000 m with current derating of 2.2 % per additional 100 m