Quantcast

Altistart 22 Soft Starter ATS22 Control, 220V Power 230V(110kW)/400...440V

Altistart 22 Soft Starter ATS22 Control, 220V Power 230V(110kW)/400...440V

Altistart 22 Soft Starter ATS22 Control, 220V Power 230V(110kW)/400...440V

Item Number: ATS22C41Q

Retail
$11,570.34
RRP (Inc. GST)

Product Dimensions

Width icon

Width206 mm

Height icon

Height425 mm

Depth icon

Depth299 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altistart 22

Product or component type

soft starter

Product destination

asynchronous motors

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

IP degree of protection

IP00

Function available

internal bypass

Output current

0.4...1 Icl adjustable

Communication port protocol

Modbus

Connector type

1 RJ45

Protection type

  • phase failure: line
  • thermal protection: motor
  • thermal protection: starter
    • Marking

      CE

      Height

      425 mm

      Width

      206 mm

      Depth

      299 mm

      Net weight

      33 kg

      Standards

      EN/IEC 60947-4-2

      Product certifications

    • GOST
    • CCC
    • CSA
    • UL
    • C-Tick
      • Relative humidity

        0-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

        Ambient air temperature for operation

      • -10-40 °C (without derating)
      • 40-60 °C (with current derating 2.2 % per °C)
        • Ambient air temperature for storage

          -25-70 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          EU RoHS Directive

          Pro-active compliance (Product out of EU RoHS legal scope)

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          X

          Environmental Disclosure

          ENVPEP100402EN

          Circularity Profile

          ENVEOLI110805EN

          California proposition 65

          WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

          Others

          Product specific application

          pumps and fans

          Component name

          ATS22

          Network number of phases

          3 phases

          [Us] rated supply voltage

          230...440 V - 15...10 %

          Motor power kW

        • 110 kW 230 V
        • 220 kW 400 V
        • 220 kW 440 V
          • Factory setting current

            388 A

            Power dissipation in W

            177 W for standard applications

            Utilisation category

            AC-53A

            Type of start

            start with torque control (current limited to 3.5 In)

            IcL starter rating

            410 A for connection in the motor supply line for standard applications

            Assembly style

            with heat sink

            Supply voltage limits

            195-484 V

            Supply frequency

            50...60 Hz - 10...10 %

            Network frequency

            45...66 Hz

            Device connection

          • to the motor delta terminals
          • in the motor supply line
            • [Uc] control circuit voltage

              230 V - 15...10 % 50/60 Hz

              Control circuit consumption

              20 W

              Discrete output number

              2

              Discrete output type

            • relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
            • relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
              • Minimum switching current

                100 mA at 12 V DC (relay outputs)

                Maximum switching current

              • 5 A 250 V AC resistive 1 relay outputs
              • 5 A 30 V DC resistive 1 relay outputs
              • 2 A 250 V AC inductive 0.4 20 ms relay outputs
              • 2 A 30 V DC inductive 7 ms relay outputs
                • Discrete input number

                  3

                  Discrete input type

                  (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm

                  Discrete input voltage

                  24 V <= 30 V

                  Discrete input logic

                  positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA

                  PTC probe input

                  750 Ohm

                  Communication data link

                  serial

                  Physical interface

                  RS485 multidrop

                  Transmission rate

                  4800, 9600 or 19200 bps

                  Installed device

                  31

                  Type of cooling

                  forced convection

                  Operating position

                  vertical +/- 10 degree

                  Power range

                • 110-220 kW at 380-440 V 3 phases
                • 110-220 kW at 200-240 V 3 phases
                  • Motor starter type

                    soft starter

                    Electromagnetic compatibility

                  • conducted and radiated emissions level A conforming to IEC 60947-4-2
                  • damped oscillating waves level 3 conforming to IEC 61000-4-12
                  • electrostatic discharge level 3 conforming to IEC 61000-4-2
                  • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                  • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                  • voltage/current impulse level 3 conforming to IEC 61000-4-5
                    • Vibration resistance

                    • 1 gn (f= 13-200 Hz) conforming to EN/IEC 60068-2-6
                    • 1.5 mm (f= 2-13 Hz) conforming to EN/IEC 60068-2-6
                      • Shock resistance

                        15 gn for 11 ms conforming to EN/IEC 60068-2-27

                        Noise level

                        56 dB

                        Pollution degree

                        level 2 conforming to IEC 60664-1

                        Operating altitude

                      • <= 1000 m without derating
                      • > 1000...< 2000 m with current derating of 2.2 % per additional 100 m
                        • Package 1 Weight

                          26.8 kg

                          Package 1 Height

                          4.9 dm

                          Package 1 width

                          3.7 dm

                          Package 1 Length

                          5.45 dm

                          WEEE

                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                          Show all specifications

                          Documents & downloads

                          hide show
                          Filter items
                          • All

                          • Product Brochures

                          • CAD Files and Packs

                          • Technical Data Catalogues

                          • Product Environmental

                          • End of Life Manual

                          • Installation Instruction

                          • Operating Manuals

                          • Certificates (MSDS)

                          • Marine Certificate

                          • eTechPub

                          • Declaration of Conformity

                          • DTM Files

                          • Software - Release

                          Frequently Asked Questions

                          hide show

                          What's the difference between ATS22..S6U and ATS22...S6 Softstart models?

                          Issue:
                          Differences between an ATS22..S6U and  ATS22..S6 soft start models.

                          Product Line:
                          Altistart 22 ATS22

                          Environment:
                          All models, All series

                          Cause: 
                          Altistart has difference voltage suffix S6U and S6.  

                          Resolution:
                          The ATS22..S6 model requires 220vac control power and has 24vdc logic inputs.





                          The ATS22..S6U model requires 110vac control power and has 110vac logic inputs.


                          Are lugs included with ATS22 Soft Starts?

                          Issue:
                          ATS22 Soft Starts lugs inclusion

                          Product Line:
                          ATS22, Altivar

                          Environment:
                          All

                          Cause:
                          N/A

                          Resolution:
                          Smaller units (ATS22D17 thru ATS22D88) have a cage style connector to accept power circuit wiring with built-in terminals.
                          Larger units (ATS22C11 thru ATS22C59) have bus bar landing pads only.  Lugs are not included, but are available for separate purchase. Please see the attached documents for part numbers and instructions.

                          The ATS22C17S6U can also accept the smaller lug DZ2FG1 (single lug) or DZ1FG6 (set of 6 lugs).
                          This has been confirmed with Level 3 support.

                          How can you tell what the nominal current range is on the ATS22 soft starter?

                          Issue:
                          Reading the Nominal Curren Range of the ATS22 from part number

                          Product Line:
                          Altistart ATS22

                          Environment:
                          All

                          Cause:
                          Needs to be able to tell the soft starters current ratings.

                          Resolution:
                          Look at the part number example the ATS22D88 is rated for 88 amps  or the ATS22C17 is rated for 170 amps.
                           

                          Does the Altistart 22 use 24Vdc control voltage?

                          Issue:
                          Can we use an external 24Vdc control voltage on a Altistart 22?

                          Product Line:
                          Altistart 22

                          Environment:
                          ATS22...S6 ATS22..Q 

                          Cause:
                          N/A

                          Resolution:
                          Only the ATS22...S6 and ATS22...Q units can accept 24Vdc control voltage but uses 220Vac to power on the softstart
                          while the ATS22...S6U uses 110Vac for control voltage and to power on the softstart.

                          NOTE:
                          • ATS22...Q units has the same wirings as ATS22...S6 units. 
                          • ATS22...Q units are not sold in the US.

                          What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

                          Issue:
                          ATS48 fuse size for circuit control going to CL1 and CL2

                          Product Line:
                          Altistart 48, ATS48

                          Environment:
                          All open style units.  All models, All Serial numbers.

                          Cause:
                          Selection of Fuses.

                          Resolution:

                          ATS48D17Y and ATS48D22Y we recommend Class CC 600V 0.5 A fuses.

                          ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y we recommend Class CC 600V 0.6 A fuses.

                          ATS48C21Y, ATS48C24Y, and ATS48C32Y we recommend Class CC 600V 1.0 A fuses.

                          ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y we recommend Class CC 600V, 1.5 A fuses.

                          Information provided in Table 31 page 83) of document S1A37491 Altistart 48 Y-range Soft Start Controllers Instruction Bulletin.

                          What is the VA consumption of CL1, CL2 control power on an ATS48?

                          Issue:
                          VA consumption of CL1, CL2 control power on an ATS48

                          Product Line:
                          Altistart 48, ATS48

                          Environment:
                          All models, All serial numbers.

                          Cause:
                          Need to know the power consumption.

                          Resolution:
                          ATS48D17Y and ATS48D22Y require 25 Watts.
                          ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y require 30 Watts.
                          ATS48C21Y, ATS48C25Y, and ATS48C32Y require 50 Watts
                          ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y require 80 Watts.

                          Data from Table 31 (page 83) of document S1A37491: Altistart 48 Y-Range Soft Start Controllers Instruction Bulletin
                          Show More