Soft start - soft stop units Altistart 22 - size 3 - 3/4 view
Soft start - soft stop units Altistart 22 - size 3 - front view
Soft start - soft stop units Altistart 22 - size 3 - 3/4 view
Soft start - soft stop units Altistart 22 - size 3 - front view

Altistart 22 Soft Starter Control, 220V Power 230V(37kW)/400...440V(75kW)

Catalogue Number: ATS22C14Q
Soft start - soft stop units Altistart 22 - size 3 - 3/4 view
Soft start - soft stop units Altistart 22 - size 3 - front view
Soft start - soft stop units Altistart 22 - size 3 - 3/4 view
Soft start - soft stop units Altistart 22 - size 3 - front view
Colour:
Colour: Per UOM Std.
  • 1 PCE

Specifications

hide show
Range of product
Altistart 22
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
pumps and fans
Component name
ATS22
Network number of phases
3 phases
[Us] rated supply voltage
230...440 V - 15...10 %
Motor power kW
  • 37 kW 230 V
  • 75 kW 400 V
  • 75 kW 440 V
    • Factory setting current
      131 A
      Power dissipation in W
      82 W for standard applications
      Utilisation category
      AC-53A
      Type of start
      start with torque control (current limited to 3.5 In)
      IcL starter rating
      140 A for connection in the motor supply line for standard applications
      IP degree of protection
      IP00
      Assembly style
      with heat sink
      Function available
      internal bypass
      Supply voltage limits
      195-484 V
      Supply frequency
      50...60 Hz - 10...10 %
      Network frequency
      45...66 Hz
      Device connection
    • in the motor supply line
    • to the motor delta terminals
      • [Uc] control circuit voltage
        230 V - 15...10 % 50/60 Hz
        Control circuit consumption
        20 W
        Discrete output number
        2
        Discrete output type
      • relay outputs R1 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
      • relay outputs R2 230 V running, alarm, trip, stopped, not stopped, starting, ready C/O
        • Minimum switching current
          100 mA at 12 V DC (relay outputs)
          Maximum switching current
        • 5 A 250 V AC resistive 1 relay outputs
        • 5 A 30 V DC resistive 1 relay outputs
        • 2 A 250 V AC inductive 0.4 20 ms relay outputs
        • 2 A 30 V DC inductive 7 ms relay outputs
          • Discrete input number
            3
            Discrete input type
            (LI1, LI2, LI3) logic, 5 mA 4.3 kOhm
            Discrete input voltage
            24 V <= 30 V
            Discrete input logic
            positive logic LI1, LI2, LI3 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
            Output current
            0.4...1 Icl adjustable
            PTC probe input
            750 Ohm
            Communication port protocol
            Modbus
            Connector type
            1 RJ45
            Communication data link
            serial
            Physical interface
            RS485 multidrop
            Transmission rate
            4800, 9600 or 19200 bps
            Installed device
            31
            Protection type
          • phase failure: line
          • thermal protection: motor
          • thermal protection: starter
            • Marking
              CE
              Type of cooling
              forced convection
              Operating position
              vertical +/- 10 degree
              Height
              356 mm
              Width
              150 mm
              Depth
              229.5 mm
              Net weight
              18 kg
              Power range
            • 30-50 kW at 200-240 V 3 phases
            • 55-100 kW at 380-440 V 3 phases
              • Motor starter type
                soft starter
                Electromagnetic compatibility
              • conducted and radiated emissions level A conforming to IEC 60947-4-2
              • damped oscillating waves level 3 conforming to IEC 61000-4-12
              • electrostatic discharge level 3 conforming to IEC 61000-4-2
              • immunity to electrical transients level 4 conforming to IEC 61000-4-4
              • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
              • voltage/current impulse level 3 conforming to IEC 61000-4-5
                • Standards
                  EN/IEC 60947-4-2
                  Product certifications
                • UL
                • CSA
                • C-Tick
                • GOST
                • CCC
                  • Vibration resistance
                  • 1 gn (f= 13-200 Hz) conforming to EN/IEC 60068-2-6
                  • 1.5 mm (f= 2-13 Hz) conforming to EN/IEC 60068-2-6
                    • Shock resistance
                      15 gn for 11 ms conforming to EN/IEC 60068-2-27
                      Noise level
                      56 dB
                      Pollution degree
                      level 2 conforming to IEC 60664-1
                      Relative humidity
                      0-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                      Ambient air temperature for operation
                    • -10-40 °C (without)
                    • 40-60 °C (with current derating 2.2 % per °C)
                      • Ambient air temperature for storage
                        -25-70 °C
                        Operating altitude
                      • <= 1000 m without
                      • > 1000...< 2000 m with current derating of 2.2 % per additional 100 m
                        • Sustainable offer status
                          Green Premium product
                          REACh Regulation
                          Free of Substances of Very High Concern above the threshold
                          EU RoHS Directive
                          Pro-active compliance (Product out of EU RoHS legal scope)
                          Mercury free
                          Yes
                          RoHS exemption information
                          Yes
                          China RoHS Regulation
                          X
                          Environmental Disclosure
                          ENVPEP100401EN
                          Circularity Profile
                          ENVEOLI110804EN
                          WEEE
                          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                          California proposition 65
                          WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                          Warranty
                          18 months

                          Frequently Asked Questions

                          hide show

                          What are the dimensions for the VW3G48101, remote keypad for the ATS48?

                          Issue:
                          What are the dimensions for remote keypad for the ATS48?

                          Product Line:
                          Altistart 48

                          Environment:
                          All

                          Cause:
                          N/A

                          Resolution:
                          Remote keypad part# VW3G48101
                          Width = 2 5/8 inches
                          Height = 4 1/4 inches
                          Depth = 5/8 inches
                          This includes a clear membrane cover and a trim bezel.

                          What's the difference between ATS22..S6U and ATS22...S6 Softstart models?

                          Issue:
                          What's the difference between an ATS22..S6U and  ATS22..S6 soft start models?

                          Product Line:
                          Altistart 22 ATS22

                          Environment:
                          All models, All series

                          Cause: 
                          Altistart has difference voltage suffix S6U and S6.  

                          Resolution:
                          The ATS22..S6 model requires 220vac control power and has 24vdc logic inputs.





                          The ATS22..S6U model requires 110vac control power and has 110vac logic inputs.


                          Are lugs included with ATS22 Soft Starts?

                          Issue:
                          Are lugs included with ATS22 Soft Starts?

                          Product Line:
                          ATS22

                          Environment:
                          All

                          Cause:
                          N/A

                          Resolution:
                          Smaller units (ATS22D17 thru ATS22D88) have a cage style connector to accept power circuit wiring with built-in terminals.
                          Larger units (ATS22C11 thru ATS22C59) have bus bar landing pads only.  Lugs are not included, but are available for separate purchase. Please see the attached documents for part numbers and instructions.

                          What are the minimum required clearances for the ATS48 unit for enclosure mounting.

                          Issue:
                          What are the minimum clearances required on the ATS48 soft starters?

                          Product line:
                          Altistart 48, ATS48

                          Environment:
                          all

                          Cause:
                          Mounting inside an enclosure

                          Resolution:
                          There is a minimum of 4 inches (100 mm) on the top and bottom of the softstart.  A minimum clearance of 2 inches (50mm) on each sides.
                          The enclosure must also allow for proper ventilation to maintain a temperature of 40C (104F) and required wire bending space.

                          Can the operating time be reset to zero on the ATS48?

                          Issue:
                          Needs to reset the operating time to zero on the ATS48.

                          Product line:
                          Altistart 48, softstart

                          Environment:
                          all

                          Cause:
                          Reset operating time

                          Resolution:
                          Yes.  Can go into the dRc menu and in the rPr parameter:  The options available here are:

                          - no: function inactive
                          - APH: kWh reset to zero
                          - trE: operating time reset to zero

                          The reset command must be confirmed with ENT. APH and trE take effect immediately.
                          The parameter then automatically returns to no.
                           

                          What are the dimensions of the ATS22D17 compared to the ATS22D47?

                          The dimension of ATS22D17 to ATS22D47 are identical

                          What is the part number for Control Power Transformer for ATS46D75N, ATS46D88N, ATS46C11N or ATS46C14N soft starter?

                           ***REJECT***   Duplicate to FA107489     VY1G461402.


                          CTA-ID : 2014567

                          What are the dimensions of the Soft Starter part number ATS22D62Q?

                          The dimensions of the Soft Starter part number ATS22D62Q are as follows:

                          Height 295 mm
                          Width 145 mm
                          Depth 207 mm

                          https://www.schneider-electric.com.au/en/search/ATS22D62Q

                          What is the replacement part number for the SCR module for ATS23C15N or ATS23C24N?

                          Issue:   What is the replacement part number for the SCR module for ATS23C15N or ATS23C24N?
                           
                          Product Line:   ATS23
                           
                          Environment:  ATS23C15N ATS23C24N
                           
                          Cause:   N/A
                           
                          Resolution:   No parts available replace starter



                           

                          What is the part number of the A2 busbarr on the Altistart ATS23C10N so he could replace it?

                          Issue:   What is the part number of the A2 busbarr on the Altistart ATS23C10N so he could replace it?
                           
                          Product Line:   ATS23
                           
                          Environment:  All
                           
                          Cause:   N/A
                           
                          Resolution:   Not a replacement part  replace starter with a currrent model
                           

                          Are Softstarters acceptable for use in a Fire Pump applications?

                          Issue:
                          Are Softstarters acceptable for use in a Fire Pump applications?

                          Product line:
                          Altistart 22 48 ATS22 ATS48

                          Environment:
                          all

                          Cause:
                          Fire pump systems typically require the motors to run until they fail, without faulting the controller

                          Resolution:
                          No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.
                           

                          What is the suggested shorting contactor part number for an ATS48C14Y?

                          Issue:
                          What is the suggested shorting contactor part number for an ATS48C14Y?

                          Product Line:
                          Altistart 48 , ATS48

                          Environment:
                          ATS48C11Y , ATS48C14Y 

                          Cause:
                          Custom enclosure

                          Resolutin:
                          LC1D115 G7  (120vac coil control voltage )

                          Do we have any IP2X type of kit for ATS22C480Q?

                          No, We don't do  any IP2X type of kit for ATS22C480Q.

                          What is the part number for soft starter 45KW?

                          Can customer replace the power terminal block with the blue plastic piece located at the top of the ATS23C15N unit where the line power comes in?

                          Issue:   Can customer replace the power terminal block with the blue plastic piece located at the top of the ATS23C15N unit where the line power comes in?
                           
                          Product Line:   ATS23
                           
                          Environment:  All
                           
                          Cause:   N/A
                           
                          Resolution:   No. No parts available. Replace starter with a current model..


                           

                          How can you tell what the nominal current range is on the ATS22 soft starter?

                          Issue:
                          How can you tell what the nominal current range is on the ATS22 soft starter?

                          Product Line:
                          Altistart ATS22

                          Environment:
                          All

                          Cause:
                          Needs to be able to tell the soft starters current ratings.

                          Resolution:
                          Look at the part number example the ATS22D88 is rated for 88 amps  or the ATS22C17 is rated for 170 amps.
                           

                          Could you use the ATS46 remote keypad kit to replace the Altivar ATV16 remote keypad kit?

                          Issue: Could you use the ATS46 remote keypad kit to replace the Altivar ATV16 remote keypad kit?
                           
                          Product Line: ATV16
                           
                          Environment: All
                           
                          Cause: Keypad
                           
                          Resolution: Yes, you could. The part number for the kit is VW3G46103.  These keypads are obsolete and no longer available.


                           

                          What is the minimum size enclosure needed to put a ATS22D32Q into?

                          Minimum size 600x500x250 based on metal enclosure 
                          If they require a plastic enclosure it will need to be larger to provide adequate airflow.

                          Are the ATS46D17N, ATS46D22N, ATS46D32N, ATS46D38N, ATS46D47N, ATS46D62N, ATS46D75N, ATS46D88N, ATS46C11N or ATS46C14N repaired in the field or is it sent to the depot for repair?

                          This unit normally goes in for repair to the depot for warranty work.

                          However, if this unit is part of an enclosed soft starter package (8636, 8638 or 8639) or part of an MCC within warranty, the repairs can be done by field services.
                          If a customer would like to buy the suspected failed components and have repairs done on site that is acceptable. SquareD would not pay for travel or labor expenses in this case.

                          Contact AC Drives and Soft Starters product support group (DPSG) at 919-266-8600 for technical support if doing field repairs.

                          ATS46C17N and larger units are generally filed repaired.

                          Are external motor overloads needed when running the motor with ATS46 softstart?

                          Issue: Are external motor overloads needed when running the motor with ATS46 softstart?
                           
                          Product Line: ATS46
                           
                          Environment: All
                           
                          Cause: N/A
                           
                          Resolution: The ATS46 has integrated motor thermal protection.
                          The thermal overload class can be adjusted to provide Class 2, 10, 10A, 15, 20, 25 or 30 overload protection as defined per IEC 947-4-2. The thermal overload protection may be turned off if external protection is provided.
                          External overload protection may be provided if there are multiple motors or if there is full voltage bypass available.


                           

                          What is the part number for the main control board for the ATS46?

                          Issue:
                          What is the part number for the main control board for the ATS46?

                          Product Line:
                          Altistart ATS46

                          Environment:
                          All

                          Cause:
                          Replacement part

                          Resolution:
                          The part number is VX4G461 however this part is no longer available.  The customer will have to replace the entire ATS46 softstarter with an ATS48.



                          CTA-ID : 2005457

                          What is the ATS48 line voltage operating range?

                          Issue:
                          What is the ATS48 line voltage operating range?

                          Product line:
                          Altistart 48, ATS48

                          Environment:
                          all

                          Cause:
                          n/a

                          Resolution:
                          The Altistart 48 is suitable for three phase supply voltages that range from 208VAC to 690VAC , 50/60Hz.  The tolerance of the voltage supply is -15% to +10%. 

                           

                          What is the maximum and minimum acceleration time on the ATS48 and ATS22?

                          Issue:
                          What is the maximum and minimum acceleration time on the ATS48?

                          Product line:
                          Altistart 22 Altistart 48, ATS22 ATS48

                          Environment:
                          all

                          Cause:
                          n/a

                          Resolution:
                          The possible setting for acceleration is from 1 to 60 seconds

                           

                          Why does SoMove not show phase B current on an ATS22 with the Q suffix in the monitor menu?

                          Issue:
                          SoMove monitor input current
                           
                          Product Line:
                          ATS22
                           
                          Environment:
                          Q suffix
                           
                          Cause:
                          None
                           
                          Resolution:
                          The "Q" versions are european model and these do no have current transformers on phase "B".  Therefore the monitor in SoMove will not show this phase.
                           

                          What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

                          Issue:
                          What size fuses are used in the ATS48 for the control circuit going to CL1 and CL2?

                          Product Line:
                          Altistart 48, ATS48

                          Environment:
                          All open style units.  All models, All Serial numbers.

                          Cause:
                          Selection of Fuses.

                          Resolution:

                          ATS48D17Y and ATS48D22Y we recommend Class CC 600V 0.5 A fuses.

                          ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y we recommend Class CC 600V 0.6 A fuses.

                          ATS48C21Y, ATS48C24Y, and ATS48C32Y we recommend Class CC 600V 1.0 A fuses.

                          ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y we recommend Class CC 600V, 1.5 A fuses.

                          Information provided in Table 31 page 83) of document S1A37491 Altistart 48 Y-range Soft Start Controllers Instruction Bulletin.

                          What is the VA consumption of CL1, CL2 control power on an ATS48?

                          Issue:
                          VA consumption of CL1,CL2 control power on an ATS48.

                          Product Line:
                          Altistart 48, ATS48

                          Environment:
                          All models, All serial numbers.

                          Cause:
                          Need to know the power consumption.

                          Resolution:
                          ATS48D17Y and ATS48D22Y require 25 Watts.
                          ATS48D32Y, ATS48D38Y, ATS48D47Y, ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y, ATS48C14Y, and ATS48C17Y require 30 Watts.
                          ATS48C21Y, ATS48C25Y, and ATS48C32Y require 50 Watts
                          ATS48C41Y, ATS48C48Y, ATS48C59Y, ATS48C66Y, ATS48C79Y, ATS48M10Y and ATS48M12Y require 80 Watts.

                          Data from Table 31 (page 83) of document S1A37491: Altistart 48 Y-Range Soft Start Controllers Instruction Bulletin

                          How do you set the ATS48 softstarter for a Heavy (Severe) Duty Application?

                          Issue:
                          How do you set the ATS48 softstarter for a Heavy Duty or Severe Application?

                          Product line:
                          Altistart 48, ATS48 soft start

                          Environment:
                          all

                          Cause:
                          Rating guide shows Normal and Severe (or Heavy Duty)

                          Resolution:
                          There is no switch or setting to designate ``Heavy Duty``
                          Oversize the ATS48 selection by one size, based on the motor FLA rating.  For example, for a 50HP @ 460V, select the 60HP size. 

                          In addition to the default Programming, set the overload class (PRO > THP ) to 20.
                           

                          What is the operating temperature rating of the ATS48?

                          Issue:
                          What is the operating temperature rating of the ATS48?

                          Product Line:
                          Altistart 48

                          Environment:
                          All

                          Cause:
                          N/A

                          Resolution:
                          14 to +104 *F (-10 *C to +40 *C) without derating.
                          Up to +140 *F (+60 *C), derate the current by 2% for each *C above 40 *C.
                          14 to 122 *F (-10 *C to +50 *C) with user provided shorting/bypass contactor.

                          What are the dimensions and weight for the ATS48?

                          Issue:
                          What are the dimensions and weight for the ATS48?

                          Product Line:
                          ATS48

                          Environment:
                          All

                          Cause:
                          N/A


                          Resolution:
                          Dimensions and weights can be found in the instruction bulletin number S1A37491 Altistart 48 Y-Range Softstarts Installation Guide. See attachment.














                           

                          What is the part number of the replacement control board for the ATS48?

                          Issue:
                          What is the part number of the replacement control board for the ATS48?

                          Product Line:
                          Altistart 48 

                          Environment:
                          All models

                          Cause:
                          Replacement

                          Resolution:
                          The control board is part number VX4G481, common to all ATS48 models.

                          Will the ATS22 display light up with control voltage only?

                          Issue:
                          Will the ATS22 display light up with control voltage only?

                          Product Line:
                          ALTISTART 22

                          Environment:
                          All
                           
                          Cause:
                          Troubleshooting

                          Resolution:
                          Yes, the display should light with control voltage applied.  

                          If the display does not light up:
                          Disconnect any remote HMI that you may have connected
                          Verify the correct control voltage is measured at the ATS22 terminals CL1 and CL2
                              For models ATS22...S6 and ATS22...Q the control voltage should measure ~230vac
                              For models ATS22...S6U the control voltage should measure ~110vac

                          Can you access the fault history in an ATS46 softstart using ModBus?

                          Issue: Can you access the fault history in an ATS46 softstart using ModBus?
                           
                          Product Line: ATS46
                           
                          Environment: All
                           
                          Cause: N/A
                           
                          Resolution: from the Global Help desk;
                          ``You can access by ModBus with W4090 (from 1 to 4) for the fault number, the value is in W4069 and W4091 is used by the ATS to Recall the fault.``

                          What I think this means is that if you put a value of 1 in word 4090, the most recent fault will be reported in W4091. If you put a 2 in 4090, you will read the next oldest fault in 4091. 4090 is used as a pointer, and 4091 is used to display the value that is pointed to.


                           

                          ATS48 soft starter internal fan part numbers.

                          Issue:
                          Does the Altistart 48 soft start have an internal fan?

                          Product Line:
                          Altistart 48

                          Environment:
                          All models, all serial numbers

                          Cause
                          Replacement and repair pars

                          Resolution:  
                          The following list shows the softstart part number along with the part number and (quantity) of the fan kits needed for each softstarter. 


                          ATS48D32Y - VZ3V481 (1)
                          ATS48D38Y - VZ3V481 (1)

                          ATS48D47Y - VZ3V4811 (1)

                          ATS48D62Y - VZ3V482 (1)
                          ATS48D75Y - VZ3V482 (1)
                          ATS48D88Y - VZ3V482 (1)
                          ATS48C11Y - VZ3V482 (1)

                          ATS48C14Y - VZ3V483 (1)
                          ATS48C17Y - VZ3V483 (1)

                          ATS48C21Y - VZ3V484 (1)
                          ATS48C25Y - VZ3V484 (1)
                          ATS48C32Y - VZ3V484 (1)

                          ATS48C41Y - VZ3V485 (1)
                          ATS48C48Y - VZ3V485 (1)
                          ATS48C59Y - VZ3V485 (1)
                          ATS48C66Y - VZ3V485 (1)

                          ATS48C79Y - VZ3V485 (2)
                          ATS48M10Y - VZ3V485 (2)
                          ATS48M12Y - VZ3V485 (2)



                           

                          What does OHF on the ATS48 mean? Could not find this code in the Installation Guide bulletin #30072-450-61.

                          Issue:
                          ATS48  What does OHF mean?  Could not find this code in the Installation Guide bulletin #30072-450-61.

                          Product Line:
                          Altistart 48 Soft Starters

                          Environment:
                          All

                          Cause:
                          ATS48 getting an OHF fault. Fault does not appear in the Installation Guide bulletin #30072-450-61

                          Resolution:
                          OHF indicates a starter thermal fault.

                          Recommendations:
                          Check the mechanism (wear, mechanical play, lubrication, blockages, etc.).
                          Check the sizing of the starter in relation to the motor and the mechanical requirement.
                          Check the operation of the fan, ensuring that the air passage is not obstructed in any way and the heatsink is clean.
                          Ensure that the mounting recommendations are observed.
                          Check ambient temp around the starter. Wait for the ATS48 to cool before restarting.

                          OHF was omitted from the Installation Guide bulletin #30072-450-61 but will be included in the next release of the manual.
                           

                          In the 30072-450-61 manual for the ATS48 on page 76, it shows contacts for ``KM1`` & ``KM2``. What are they?

                          Issue:
                          What is the meaning in the wiring diagram of the contacts labelled KM1 and KM2 feeding into the IC1 forward contactor and IC2 reverse contactor?

                          Product line:
                          Altistart 48, ATS48

                          Environment:
                          All enclosed

                          Cause:
                          Typo error in the instruction bulletin

                          Resolution:
                          This is an error in the manual.  KM1 should be labelled IC1 and KM2 should be labelled IC2.
                          These are auxiliary contacts from the forward and reverse isolation contactors, used for electrical interlocking.  This helps prevent closure of both contactors at the same time. 

                           

                          Is a line isolation contactor or shunt trip circuit breaker needed with Schneider Electric ATS48 Soft Starters?

                          Issue:
                          Is a line isolation contactor or shunt trip circuit breaker needed with Schneider Electric ATS48 Soft Starters?

                          Product Line:
                          Altistart 48 Soft Starters

                          Environment:
                          All

                          Cause:
                          Need to know whether a contactor or breaker needs to be used

                          Resolution:
                          Since the solid-state switches may be incapable of completely blocking the motor power should a fault occur, auxiliary isolation on the line side of the controller is required. Use either a circuit breaker equipped with a shunt trip coil or an electromagnetic contactor. Connect the isolation device to the fault relay of the controller so that it opens the controller power circuit in the event of a controller fault. The isolation device must be capable of interrupting motor locked rotor current.


                           

                          The ATS22 does not display current on LCr2, do I have a faulty unit?

                          This is normal operation because the ATS22.../Q has CT's installed in the U and W phases only, no sensor installed in the V phase.
                           
                          On the ATS22..S6 ( dedicated mainly for US market) three CT's are used and LcR2 indicates a value. The three sensors are used in US market because the ground fault detection is mandatory.
                           

                          What is the replacement cooling fan part number for the ATS22C41S6U soft starter?

                          Issue:
                          What is the replacement cooling fan part number for the ATS22C41S6U soft starter?

                          Product Line:
                          ATS22C41S6U

                          Environment:
                          All 

                          Cause:
                          Replacement cooling fan. 

                          Resolution:
                          The replacement cooling fan part number  VZ3V22D1110V.
                          However this part number is not loaded on the system to order so its not available yet. 

                          What is the ATS48 soft starters dissipated watts loss for calculating heat loss for enclosure sizing?

                          Issue:
                          Looking for the watts loss on a  ATS48 soft start, for calculating heat loss, for enclosure sizing.

                          Product Line:
                          Altistart ATS48 soft starters

                          Environment:
                          All

                          Cause:
                          Needs to know the dissipated heat loss in watts the ATS48 soft starter will produce when running at full load.

                          Resolution:
                          See the table below and choose the ATS48's watt loss based on if a shorting contactor is being used or not.





                           

                          How is the current rating on an ATS48 soft start determined from the part number?

                          Issue:
                          How is the current rating on an ATS48 soft start determined from the part number?

                          Product Line:
                          All ATS48, Altistart 48

                          Environment:
                          All models, all versions

                          Resolution:

                          The ATS48 part numbering system is as follows:

                          The letter after ATS48 indicates the placement of the decimal point with the following 2 digits.
                          "D" means there are 2 digits to the left of the Decimal:  (Example:  ATS48D17Y would be rated for 17.0 amps)
                          "C" means there are 3 digits to the left of the decimal:  (Example: ATS48C17Y would be rated for 170.0 amps)
                          "M" means there are 4 digits to the left of the decimal: (Example:  ATS48M12Y would be rated for 1200.0 amps)


                          ATS48 softstart current ratings:
                          ATS48D17Y - 17A          ATS48C11Y - 110A          ATS48M10Y - 1000A         
                          ATS48D22Y - 22A          ATS48C14Y - 140A          ATS48M12Y - 1200A
                          ATS48D32Y - 32A          ATS48C17Y - 170A         
                          ATS48D38Y - 38A          ATS48C21Y - 210A         
                          ATS48D47Y - 47A          ATS48C25Y - 250A         
                          ATS48D62Y - 62A          ATS48C32Y - 320A         
                          ATS48D75Y - 75A          ATS48C41Y - 410A         
                          ATS48D88Y - 88A          ATS48C48Y - 480A          
                                                                 ATS48C59Y - 590A          
                                                                 ATS48C66Y - 660A          
                                                                 ATS48C79Y - 790A       

                          What is the part number for the power terminal shrouds for the ATS22C11S6U Soft Starter?

                          Issue:
                          What is the part number for the power terminal shrouds for the ATS22 series Soft Starters?

                          Product Line:
                          ATS22 series soft starters.

                          Environment:
                          ATS22C11S6,S6U..C17S6,S6U and ATS22C21S6,S6U..C59S6,S6U   All serial numbers.

                          Cause:
                          Customer has requested optional terminal shrouds.

                          Resolution:
                          For the ATS22C11S6,S6U through ATS22C17S6,S6U, the part number is LA9F702.
                          For the ATS22C21S6,S6U through ATS22C59S6,S6U, the part number is LA9F703.
                           
                          The thermal shroud kit includes a set of 6 power terminal protection shrouds.

                          What is the total distortion of ATS48?

                          Schneider Electric does not have measured values of harmonics produced by softstarters.

                          Softstarters conform to the following norm:
                          IEC 60947-4-2: Low-voltage switchgear and controlgear - Contactors and motor-starters - AC semiconductor motor controllers and starters,
                          which states, concerning harmonics:

                          "8.3.2.1.1 Harmonics
                          Subclause 7.3.3.2.2 of IEC 60947-1:2007 applies with the following addition:
                          Because no significant harmonic emissions are produced in the FULL-ON state, tests are not
                          required on those controllers or starters which run only in the FULL-ON state or which are
                          by-passed by a mechanical switching device after completing a start, for example, Forms 2
                          and 3 and certain Form 1 controllers or starters.

                          8.3.3.6 Harmonics and commutation notches
                          The test values and procedures are given in 9.3.5.2.5.

                          9.3.5.2.5 Harmonics and commutation notches
                          No requirement, the test levels are under study for the future."

                          So, no special considerations or filtering are required for soft start applications.

                          This is the reason why we do not make tests for that.

                          Anyway, in the past some calculations were done to estimate it.
                          ATS48 generates significant current harmonics only during the acceleration/deceleration phase, in steady state (when the thyristors are full conducting) they are negligible THD<2% and 0% with the starter bypassed.
                          The harmonics level is difficult to calculate accurately because depends on the impedance of the all installation and it varies with the motor load (power factor is not constant).

                          The following maximum values, are typical for a general case (during ACC/DEC only):
                          Row 5 : 20% of fundamental
                          Row 7 : 14% of fundamental
                          Row 11 : 9% of fundamental
                          Row 13 : 6.7% of fundamental
                          Higher rows are practically negligible.

                          Some tests were done for Row 3, unfortunately not for nominal load : less than 10% can appears with a low power factor.

                          Is the manual starter connected before or after the ATS48?

                          Issue:
                          Is the manual starter connection before or after the ATS48?

                          Product Line:
                          ATS48

                          Environment:
                           All

                          Cause:
                          Installation / Setup

                          Resolution:
                          It is recommended to be installed before the ATS48 not after.

                          What are the part numbers for the ATS22 Protection Shrouds for the Power Terminals?

                          Issue:
                          What are the part numbers for the ATS22 Protection Shrouds for the Power Terminals?

                          Product Line:
                          ATS22 Altistart 22

                          Environment:
                          All

                          Cause:
                          Need replacement parts

                          Resolution:
                          Set of 6 power terminal protection shrouds
                          ATS22C11S6,S6U ..C17S6,S6U      LA9F702
                          ATS22C21S6,S6U ..C59S6,S6U      LA9F703

                          What are the dimensions and weigh of the ATS48C11Y?

                          Issue: 
                          What are the dimensions and weight of the ATS48C11Y?

                          Product Line:

                          ATS48

                          Environment:
                          ATS48D62Y, ATS48D75Y, ATS48D88Y, ATS48C11Y  

                          Cause:
                          N/A

                          Resolution:
                          Width - 7.48 "
                          Height - 11.42"
                          Depth - 9.25"

                          Weight - 18.3 lbs

                          What is the heat dissipation (Watts loss) for the ATS22 series soft starters?

                          Issue:
                          What is the heat dissipation (Watts loss) for the ATS22 series soft starters?

                          Product Line:
                          ATS22 soft starters

                          Environment:
                          All models listed in the attached chart, all serial numbers

                          Cause:
                          Customer unable to find needed information

                          Resolution:
                          Please see the attached file for the heat dissipation data for the ATS22 series soft starters.

                          What are the bus bars made of for a high HP Altistart ATS46 softstart?

                          Issue: What are the bus bars made of for a high HP Altistart ATS46 softstart?
                           
                          Product Line: ATS46
                           
                          Environment: All
                           
                          Cause: N/A
                           
                          Resolution: Tin plated copper.


                           

                          What is the replacement control board for the ATS22 soft starts?

                          Issue:
                          Customer has a fault that will not clear, or inputs are not responding. 

                          Product line:
                          ATS22, Altistart 22

                          Environment:
                          S6 and S6U models only.

                          Cause:
                          n/a

                          Resolution:
                          The part numbers for a replacement control board is VX4A221110V for the ATS22-S6U units and VX4A221220V for the ATS22-S6 units.  These parts are only available for sale to Schneider Electric Services, or Schneider Electric Industrial Repairs.

                          The control board must be replaced by Schneider Electric only.  Contact the Repair Services at 1-800-950-9550 to arrange a repair, or your local Services location for on site replacement. 
                           

                          Are the ATS48 and ATS22 softstarters are rated for a category 4 circuit?

                          Issue:
                          Are the ATS48 and ATS22 softstarters are rated for a category 4 circuit?

                          Product Line:
                          ATS22 and ATS48

                          Environment:
                          All serial numbers for ATS22 and ATS48

                          Cause:
                          N/A

                          Resolution:
                          We do not have any safety features implemented in ATS22/48, no any safety validated scheme, certificate etc.
                          However, one can use a  typical category 4 safety scheme where the ATSxx is connected just before the motor:
                          See attachment

                          Safety is based on safety elements (relays, contactors, safety PLC...) and the ATSxx operates like a motor.
                          ATSxx does store any energy (no capacitors) so safety contactors are doing safety cut-off the ATSxx+motor.


                           

                          We have an softstarter ATS48C48Q that is displaying the OCF code. We have been following the instruction on User´s Manual : checking the motor and wir...

                          Goals and Symptoms

                          We have an softstarter ATS48C48Q that is displaying the OCF code. We have been following the instruction on User´s Manual : checking the motor and wire isolation, by-pass circuits testing, and the others instrucctions. We didn´t find anything that explains the situation. The OCF code is displayed randomly, in anytime, inclusive without the RUN command actived and without the power supply L1-L2-L3 conected. Could you say us what antohers causes are posible? We already have changed the control board, but the result is the same : the OCF code continues diplaying.

                          Facts and Changes

                          OCF

                          Causes and Fixes

                          Try to replace the power board because a bad solding is also possible, or the best way is to replace the complet product.


                          Legacy KB System (APS) Data: RESL156439 V3.0, Originally authored by on , Last Edited by on
                          Related ranges: Altistart 48