Key Features & Specifications

hide show
Range of product
Altistart 01
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
simple machine
Device short name
ATS01
Network number of phases
3 phases
[Us] rated supply voltage
380...415 V - 10...10 %
Motor power kW
15 kW, 3 phases at 380...415 V
IcL starter rating
32 A
Utilisation category
AC-53B conforming to EN/IEC 60947-4-2
Current consumption
160 A at nominal load
Type of start
start with voltage ramp
Power dissipation in W
  • 4.5 W at full load and at end of starting
  • 324.5 W in transient state
    • Assembly style
      with heat sink
      Function available
      integrated bypass
      Supply voltage limits
      342-456 V
      Supply frequency
      50...60 Hz - 5...5 %
      Network frequency
      47.5...63 Hz
      Output voltage
      <= power supply voltage
      [Uc] control circuit voltage
      built into the starter
      Starting time
    • adjustable from 1 to 10 s
    • 1 s / 50
    • 10 s / 5
    • 5 s / 10
      • Deceleration time symb
        adjustable from 1 to 10 s
        Starting torque
        30...80 % of starting torque of motor connected directly on the line supply
        Discrete input type
        logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
        Discrete input voltage
        24...40 V
        Discrete input logic
        positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
        Discrete output current
      • 2 A DC-13
      • 3 A AC-15
        • Discrete output type
        • open collector logic LO1 end of starting signal
        • relay outputs R1A, R1C NO
          • Discrete output voltage
            24 V (voltage limits: 6...30 V) open collector logic
            Minimum switching current
            10 mA at 6 V DC for relay outputs
            Maximum switching current
          • relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
          • relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
            • Display type
            • 1 LED (green) for starter powered up
            • 1 LED (yellow) for nominal voltage reached
              • Tightening torque
              • 0.5-0.5 N.m
              • 1.9-2.5 N.m
                • Electrical connection
                • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                • 4 mm screw clamp terminal - flexible with cable end 1 1...6 mm² AWG 10 power circuit
                • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                  • Marking
                    CE
                    Operating position
                    vertical +/- 10 degree
                    Height
                    154 mm
                    Width
                    45 mm
                    Depth
                    131 mm
                    Net weight
                    0.56 kg
                    Compatibility code
                    ATS01N2
                    Power range
                    15-25 kW at 380-440 V 3 phases
                    Motor starter type
                    soft starter
                    Electromagnetic compatibility
                  • conducted and radiated emissions level B conforming to CISPR 11
                  • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                  • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                  • micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
                  • voltage/current impulse level 3 conforming to IEC 61000-4-5
                  • conducted and radiated emissions level B conforming to IEC 60947-4-2
                  • damped oscillating waves level 3 conforming to IEC 61000-4-12
                  • electrostatic discharge level 3 conforming to IEC 61000-4-2
                  • EMC immunity conforming to EN 50082-1
                  • EMC immunity conforming to EN 50082-2
                  • harmonics conforming to IEC 1000-3-2
                  • harmonics conforming to IEC 1000-3-4
                  • immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
                    • Standards
                      EN/IEC 60947-4-2
                      Product certifications
                    • C-Tick
                    • CSA
                    • CCC
                    • GOST
                    • UL
                    • B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
                      • IP degree of protection
                        IP20
                        Pollution degree
                        2 conforming to EN/IEC 60947-4-2
                        Vibration resistance
                      • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                      • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                        • Shock resistance
                          15 gn for 11 ms conforming to EN/IEC 60068-2-27
                          Relative humidity
                          5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                          Ambient air temperature for operation
                        • -10-40 °C (without)
                        • 40-50 °C (with current derating of 2 % per °C)
                          • Ambient air temperature for storage
                            -25-70 °C conforming to EN/IEC 60947-4-2
                            Operating altitude
                          • <= 1000 m without
                          • > 1000 m with current derating of 2.2 % per additional 100 m
                            • REACh Regulation
                              Free of Substances of Very High Concern above the threshold
                              REACh free of SVHC
                              Yes
                              EU RoHS Directive
                              Pro-active compliance (Product out of EU RoHS legal scope)
                              Toxic heavy metal free
                              Yes
                              Mercury free
                              Yes
                              RoHS exemption information
                              Yes
                              China RoHS Regulation
                              X
                              WEEE
                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Warranty
                              18 months

                              Documents & downloads

                              hide show
                              Filter items
                              • All

                              • CAD Files and Packs

                              • Product Brochures

                              • Technical Data Catalogues

                              • End of Life Manual

                              • Installation Instruction

                              • Handout

                              • Product Environmental

                              • Data Bulletin

                              • Operating Manuals

                              • Application Solutions

                              • Certificates (MSDS)

                              • eTechPub

                              Frequently Asked Questions

                              hide show

                              Does the ATS01 come with a shorting contactor?

                              Issue:
                              Does the ATS01 come with a shorting contactor?

                              Product Line:
                              Altistat 01

                              Environment:
                              All

                              Cause:
                              N/A

                              Resolution:
                              All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                              Is the LH4N still available?

                              Issue:
                              Is the LH4N still available?

                              Product Line:
                              LH4N

                              Environment:
                              All models and all serial numbers

                              Cause:
                              Customer was looking for purchasing the LH4N112RT7.

                              Resolution:
                              No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                               

                              Are Softstarters acceptable for use in a Fire Pump applications?

                              Issue:
                              Are Softstarters acceptable for use in a Fire Pump applications?

                              Product line:
                              Altistart 22 48 ATS22 ATS48

                              Environment:
                              all

                              Cause:
                              Fire pump systems typically require the motors to run until they fail, without faulting the controller

                              Resolution:
                              No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.
                               

                              How can ATS01N2...LU, QN, RT be started without control wires?

                              Issue:
                              How can ATS01N2...LU, QN, RT be started without control wires?

                              Product Line:
                              Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number

                              Environment:
                              All

                              Cause:
                              Need to start the Soft Starter with power up

                              Resolution:
                              Add a jumper between terminals LI+ and LI2.  This provides a continuous RUN command.  When power is supplied to the ATS01, it will immediately begin to start the motor.  Removing power will result in a freewheel stop.

                               

                              What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?

                              What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?


                              Issue:

                              Adjusting Altistart 01 Soft Starters


                              Product Line:
                              Altistart 01


                              Environment:
                              All


                              Cause:
                              N/A


                              Resolution:

                              For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                              For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.