Quantcast

Soft-Start Stop 9A 380 415V

Soft-Start Stop 9A 380 415V

Soft-Start Stop 9A 380 415V

Item Number: ATS01N209QN

Retail
$1,265.96
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height124 mm

Depth icon

Depth131 mm

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altistart 01

Product or component type

soft starter

Product destination

asynchronous motors

Warranty

18 months

Physical

Function available

integrated bypass

Marking

CE

Height

124 mm

Width

45 mm

Depth

131 mm

Net weight

0.42 kg

Standards

EN/IEC 60947-4-2

Product certifications

  • GOST
  • B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
  • CCC
  • CSA
  • C-Tick
  • UL
    • IP degree of protection

      IP20

      Relative humidity

      5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

      Ambient air temperature for operation

    • -10-40 °C (without derating)
    • 40-50 °C (with current derating of 2 % per °C)
      • Ambient air temperature for storage

        -25-70 °C conforming to EN/IEC 60947-4-2

        REACh Regulation

        Free of Substances of Very High Concern above the threshold

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Pro-active compliance (Product out of EU RoHS legal scope)

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        X

        California proposition 65

        WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

        Others

        Number of Units in Package 1

        1

        Package 1 Height

        5.3 cm

        Package 1 Length

        17.3 cm

        Package 1 width

        15.2 cm

        Unit Type of Package 1

        PCE

        Product specific application

        simple machine

        Device short name

        ATS01

        Network number of phases

        3 phases

        [Us] rated supply voltage

        380...415 V - 10...10 %

        Motor power kW

        4 kW, 3 phases at 380...415 V

        IcL starter rating

        9 A

        Utilisation category

        AC-53B conforming to EN/IEC 60947-4-2

        Current consumption

        45 A at nominal load

        Type of start

        start with voltage ramp

        Power dissipation in W

      • 4 W at full load and at end of starting
      • 94 W in transient state
        • Assembly style

          with heat sink

          Supply voltage limits

          342-456 V

          Supply frequency

          50...60 Hz - 5...5 %

          Network frequency

          47.5...63 Hz

          Output voltage

          <= power supply voltage

          [Uc] control circuit voltage

          built into the starter

          Starting time

        • 1 s / 100
        • 5 s / 20
        • 10 s / 10
        • adjustable from 1 to 10 s
          • Deceleration time symb

            adjustable from 1 to 10 s

            Starting torque

            30...80 % of starting torque of motor connected directly on the line supply

            Discrete input type

            logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm

            Discrete input voltage

            24...40 V

            Discrete input logic

            positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA

            Discrete output current

          • 2 A DC-13
          • 3 A AC-15
            • Discrete output type

            • open collector logic LO1 end of starting signal
            • relay outputs R1A, R1C NO
              • Discrete output voltage

                24 V (voltage limits: 6...30 V) open collector logic

                Minimum switching current

                10 mA at 6 V DC for relay outputs

                Maximum switching current

              • relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
              • relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
                • Display type

                • 1 LED (green) for starter powered up
                • 1 LED (yellow) for nominal voltage reached
                  • Tightening torque

                  • 0.5-0.5 N.m
                  • 1.9-2.5 N.m
                    • Electrical connection

                    • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                    • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                    • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                    • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                    • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                    • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                      • Operating position

                        vertical +/- 10 degree

                        Compatibility code

                        ATS01N2

                        Power range

                        4-6 kW at 380-440 V 3 phases

                        Motor starter type

                        soft starter

                        Electromagnetic compatibility

                      • conducted and radiated emissions level B conforming to CISPR 11
                      • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                      • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                      • micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
                      • voltage/current impulse level 3 conforming to IEC 61000-4-5
                      • conducted and radiated emissions level B conforming to IEC 60947-4-2
                      • damped oscillating waves level 3 conforming to IEC 61000-4-12
                      • electrostatic discharge level 3 conforming to IEC 61000-4-2
                      • EMC immunity conforming to EN 50082-1
                      • EMC immunity conforming to EN 50082-2
                      • harmonics conforming to IEC 1000-3-2
                      • harmonics conforming to IEC 1000-3-4
                      • immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
                        • Pollution degree

                          2 conforming to EN/IEC 60947-4-2

                          Vibration resistance

                        • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                        • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                          • Shock resistance

                            15 gn for 11 ms conforming to EN/IEC 60068-2-27

                            Operating altitude

                          • <= 1000 m without derating
                          • > 1000 m with current derating of 2.2 % per additional 100 m
                            • Package 1 Weight

                              535 g

                              WEEE

                              The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                              Show all specifications

                              Frequently Asked Questions

                              hide show

                              Does the ATS01 come with a shorting contactor?

                              Issue:
                              Does the ATS01 have an internal shorting contactor?

                              Product Line:
                              Altistat 01

                              Environment:
                              All

                              Cause:
                              N/A

                              Resolution:
                              All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                              What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?

                              For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                              For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.
                               

                              Is the LH4N still available?

                              Issue:
                              LH4N availability

                              Product Line:
                              LH4N

                              Environment:
                              All models and all serial numbers

                              Cause:
                              Customer was looking for purchasing the LH4N112RT7.

                              Resolution:
                              No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                               

                              Are Softstarters acceptable for use in a Fire Pump applications?

                              Issue:
                              Softstarters for use in a Fire Pump applications

                              Product line:
                              Altistart 22 48 ATS22 ATS48

                              Environment:
                              all

                              Cause:
                              Fire pump systems typically require the motors to run until they fail, without faulting the controller

                              Resolution:
                              No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.
                               

                              How can ATS01N2...LU, QN, RT be started without control wires?

                              Issue:
                              Start ATS01N2...LU, QN, RT without control wires.

                              Product Line:
                              Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number

                              Environment:
                              All

                              Cause:
                              Need to start the Soft Starter with power up

                              Resolution:
                              Add a jumper between terminals LI+ and LI2.  This provides a continuous RUN command.  When power is supplied to the ATS01, it will immediately begin to start the motor.  Removing power will result in a freewheel stop.

                               

                              Does Schneider offer a soft start for a single phase motor?

                              Issue:
                              Soft start for a single phase motor?

                              Product Line:
                              ATS01

                              Environment:
                              All

                              Cause:
                              Needs a soft starter for a single phase motor. 

                              Resolution:
                              Yes, but the offering is limited.  The ATS01N1**FT products are rated for single phase motors up to 2HP at 240V and 1/2HP at 120V.
                              See the attachment beginning on page 34.  Reference page 40 for part number selection.
                              Show More