Assembly style
with heat sink
Supply voltage limits
342...456 V
Supply frequency
50...60 Hz - 5...5 %
Network frequency
47.5...63 Hz
Output voltage
<= power="" supply="">=>
[Uc] control circuit voltage
built into the starter
Starting time
- 1 s / 100
- 5 s / 20
- 10 s / 10
- adjustable from 1 to 10 s
Deceleration time symb
adjustable from 1 to 10 s
Starting torque
30...80 % of starting torque of motor connected directly on the line supply
Discrete input type
logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8="" ma="" 27="">=>
Discrete input voltage
24...40 V
Discrete input logic
positive LI1, LI2, BOOST at State 0: < 5="" v="" and=""><= 0.2="" ma="" at="" state="" 1:=""> 13 V, >= 0.5 mA=>
Discrete output type
- open collector logic LO1 end of starting signal
- relay outputs R1A, R1C NO
Discrete output voltage
24 V (voltage limits: 6...30 V) open collector logic
Minimum switching current
10 mA at 6 V DC for relay outputs
Maximum switching current
- relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
- relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
Display type
- 1 LED (green) for starter powered up
- 1 LED (yellow) for nominal voltage reached
Tightening torque
- 0.5...0.5 N.m
- 1.9...2.5 N.m
Electrical connection
- 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
- screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
- screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
- 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
- screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
- screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
- 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
- screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
- 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
- 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
Operating position
vertical +/- 10 degree
Compatibility code
ATS01N2
Power range
4...6 kW at 380...440 V 3 phases
Motor starter type
soft starter
Electromagnetic compatibility
- conducted and radiated emissions level B conforming to CISPR 11
- immunity to electrical transients level 4 conforming to IEC 61000-4-4
- immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
- micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
- voltage/current impulse level 3 conforming to IEC 61000-4-5
- conducted and radiated emissions level B conforming to IEC 60947-4-2
- damped oscillating waves level 3 conforming to IEC 61000-4-12
- electrostatic discharge level 3 conforming to IEC 61000-4-2
- EMC immunity conforming to EN 50082-1
- EMC immunity conforming to EN 50082-2
- harmonics conforming to IEC 1000-3-2
- harmonics conforming to IEC 1000-3-4
- immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
Pollution degree
2 conforming to EN/IEC 60947-4-2
Vibration resistance
- 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
- 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
Shock resistance
15 gn for 11 ms conforming to EN/IEC 60068-2-27
Operating altitude
- <= 1000="" m="" without="">=>
- > 1000 m with current derating of 2.2 % per additional 100 m
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Unit Type of Package 2
P06
Number of Units in Package 2
112
Package 2 Weight
74.124 kg
Unit Type of Package 3
S03
Number of Units in Package 3
14
Package 3 Weight
8.053 kg
WEEE
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Product specific application
simple machine
Network number of phases
3 phases
[Us] rated supply voltage
380...415 V - 10...10 %
Motor power kW
4 kW, 3 phases at 380...415 V
Utilisation category
AC-53B conforming to EN/IEC 60947-4-2
Current consumption
45 A at nominal load
Type of start
start with voltage ramp
Power dissipation in W
- 4 W at full load and at end of starting
- 94 W in transient state