Specifications

hide show
Range of product
Altistart 01
Product or component type
soft starter
Product destination
asynchronous motors
Product specific application
simple machine
Device short name
ATS01
Network number of phases
3 phases
[Us] rated supply voltage
380...415 V - 10...10 %
Motor power kW
  • 3 kW, 3 phases at 380...415 V
  • 1.5 kW, 3 phases at 380...415 V
  • 2.2 kW, 3 phases at 380...415 V
    • IcL starter rating
      6 A
      Utilisation category
      AC-53B conforming to EN/IEC 60947-4-2
      Current consumption
      30 A at nominal load
      Type of start
      start with voltage ramp
      Power dissipation in W
    • 4 W at full load and at end of starting
    • 64 W in transient state
      • Assembly style
        with heat sink
        Function available
        integrated bypass
        Supply voltage limits
        342-456 V
        Supply frequency
        50...60 Hz - 5...5 %
        Network frequency
        47.5...63 Hz
        Output voltage
        <= power supply voltage
        [Uc] control circuit voltage
        built into the starter
        Starting time
      • 1 s / 100
      • 5 s / 20
      • 10 s / 10
      • adjustable from 1 to 10 s
        • Deceleration time symb
          adjustable from 1 to 10 s
          Starting torque
          30...80 % of starting torque of motor connected directly on the line supply
          Discrete input type
          logic (LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
          Discrete input voltage
          24...40 V
          Discrete input logic
          positive LI1, LI2, BOOST at State 0: < 5 V and <= 0.2 mA at State 1: > 13 V, >= 0.5 mA
          Discrete output current
        • 2 A DC-13
        • 3 A AC-15
          • Discrete output type
          • open collector logic LO1 end of starting signal
          • relay outputs R1A, R1C NO
            • Discrete output voltage
              24 V (voltage limits: 6...30 V) open collector logic
              Minimum switching current
              10 mA at 6 V DC for relay outputs
              Maximum switching current
            • relay outputs: 2 A at 250 V AC cos phi = 0.5 and L/R = 20 ms inductive load
            • relay outputs: 2 A at 30 V DC cos phi = 0.5 and L/R = 20 ms inductive load
              • Display type
              • 1 LED (green) for starter powered up
              • 1 LED (yellow) for nominal voltage reached
                • Tightening torque
                • 1.9-2.5 N.m
                • 0.5-0.5 N.m
                  • Electrical connection
                  • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                  • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                  • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                  • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                  • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                  • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                  • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                  • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                  • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                  • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                    • Marking
                      CE
                      Operating position
                      vertical +/- 10 degree
                      Height
                      124 mm
                      Width
                      45 mm
                      Depth
                      131 mm
                      Net weight
                      0.42 kg
                      Compatibility code
                      ATS01N2
                      Power range
                    • 1.1-2 kW at 380-440 V 3 phases
                    • 2.2-3 kW at 380-440 V 3 phases
                      • Motor starter type
                        soft starter
                        Electromagnetic compatibility
                      • conducted and radiated emissions level B conforming to CISPR 11
                      • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                      • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                      • micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
                      • voltage/current impulse level 3 conforming to IEC 61000-4-5
                      • conducted and radiated emissions level B conforming to IEC 60947-4-2
                      • damped oscillating waves level 3 conforming to IEC 61000-4-12
                      • electrostatic discharge level 3 conforming to IEC 61000-4-2
                      • EMC immunity conforming to EN 50082-1
                      • EMC immunity conforming to EN 50082-2
                      • harmonics conforming to IEC 1000-3-2
                      • harmonics conforming to IEC 1000-3-4
                      • immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
                        • Standards
                          EN/IEC 60947-4-2
                          Product certifications
                        • UL
                        • B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
                        • CSA
                        • GOST
                        • C-Tick
                        • CCC
                          • IP degree of protection
                            IP20
                            Pollution degree
                            2 conforming to EN/IEC 60947-4-2
                            Vibration resistance
                          • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                          • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                            • Shock resistance
                              15 gn for 11 ms conforming to EN/IEC 60068-2-27
                              Relative humidity
                              5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
                              Ambient air temperature for operation
                            • -10-40 °C (without)
                            • 40-50 °C (with current derating of 2 % per °C)
                              • Ambient air temperature for storage
                                -25-70 °C conforming to EN/IEC 60947-4-2
                                Operating altitude
                              • <= 1000 m without
                              • > 1000 m with current derating of 2.2 % per additional 100 m
                                • REACh Regulation
                                  Free of Substances of Very High Concern above the threshold
                                  REACh free of SVHC
                                  Yes
                                  EU RoHS Directive
                                  Pro-active compliance (Product out of EU RoHS legal scope)
                                  Toxic heavy metal free
                                  Yes
                                  Mercury free
                                  Yes
                                  RoHS exemption information
                                  Yes
                                  China RoHS Regulation
                                  X
                                  WEEE
                                  The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                  California proposition 65
                                  WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov
                                  Warranty
                                  18 months

                                  Documents & downloads

                                  hide show
                                  Filter items
                                  • All

                                  • CAD Files and Packs

                                  • Product Brochures

                                  • Technical Data Catalogues

                                  • End of Life Manual

                                  • Installation Instruction

                                  • Handout

                                  • Product Environmental

                                  • Data Bulletin

                                  • Operating Manuals

                                  • Application Solutions

                                  • Certificates (MSDS)

                                  • eTechPub

                                  Frequently Asked Questions

                                  hide show

                                  Does the ATS01 come with a shorting contactor?

                                  Issue:
                                  Does the ATS01 come with a shorting contactor?

                                  Product Line:
                                  Altistat 01

                                  Environment:
                                  All

                                  Cause:
                                  N/A

                                  Resolution:
                                  All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                                  Is the LH4N still available?

                                  Issue:
                                  Is the LH4N still available?

                                  Product Line:
                                  LH4N

                                  Environment:
                                  All models and all serial numbers

                                  Cause:
                                  Customer was looking for purchasing the LH4N112RT7.

                                  Resolution:
                                  No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                                   

                                  Are Softstarters acceptable for use in a Fire Pump applications?

                                  Issue:
                                  Are Softstarters acceptable for use in a Fire Pump applications?

                                  Product line:
                                  Altistart 22 48 ATS22 ATS48

                                  Environment:
                                  all

                                  Cause:
                                  Fire pump systems typically require the motors to run until they fail, without faulting the controller

                                  Resolution:
                                  No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.
                                   

                                  How can ATS01N2...LU, QN, RT be started without control wires?

                                  Issue:
                                  How can ATS01N2...LU, QN, RT be started without control wires?

                                  Product Line:
                                  Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number

                                  Environment:
                                  All

                                  Cause:
                                  Need to start the Soft Starter with power up

                                  Resolution:
                                  Add a jumper between terminals LI+ and LI2.  This provides a continuous RUN command.  When power is supplied to the ATS01, it will immediately begin to start the motor.  Removing power will result in a freewheel stop.

                                   

                                  What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?

                                  What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?


                                  Issue:

                                  Adjusting Altistart 01 Soft Starters


                                  Product Line:
                                  Altistart 01


                                  Environment:
                                  All


                                  Cause:
                                  N/A


                                  Resolution:

                                  For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                  For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.
                                   

                                  Does Schneider offer a soft start for a single phase motor?

                                  Issue:
                                  Soft start for a single phase motor?

                                  Product Line:
                                  ATS01

                                  Environment:
                                  All

                                  Cause:
                                  Needs a soft starter for a single phase motor. 

                                  Resolution:
                                  Yes, the ATS01N1**FT products are rated for single phase motors up to 2HP at 240V.

                                  What is the replacement for the High HP ATS01N softstarters?

                                  Issue:
                                  Wants to order the ATS01N230LY, ATS01N244LY, ATS01N272LY or ATS01N285LY

                                  Product line:
                                  ATS01, Altistart 01, High HP

                                  Environment:
                                  All models

                                  Cause:
                                  The launch of the ATS22 in 2011 caused the High HP units to become redundant.

                                  Resolution:

                                  The ATS01 High HP units were replaced with the ATS22 units.  These are functional replacements only.  The ATS01 had no overload protection, an internal power supply and simple dial adjustments.  The ATS22 will require external 120V or 230V power.  There are no dials to adjust, but the unit will need to be programmed.  See the ATS22 User Maual, document BBV51300 to review the wiring, dimensions and programming.

                                  ATS01N230LY - 32A rated.  Replaced by ATS22D32S6U
                                  ATS01N244LY - 44A rated.  Replaced by ATS22D47S6U
                                  ATS01N272LY - 72A rated.  Replaced by ATS22D75S6U
                                  ATS01N285LY - 85A rated.  Replaced by ATS22D88S6U

                                   

                                  What are the adjustment ranges for the dials on an ATSU01N2..LT?

                                  For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                  For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                  CTA-ID : 2061385

                                  What are the adjustment ranges for the dials on an ATS01N1..FT?

                                  For the START TIME dial, setpoint A is 1second and setpoint E is 5seconds.  There is a linear relationship from A to E setpoints.
                                  For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                  CTA-ID : 2061387

                                  What are the dimensions for the ATS01N230LY and ATS01N244LY?

                                  Issue:
                                  What are the dimensions for the ATS01N230LY and ATS01N244LY?

                                  Product Line:
                                  Altistart 01

                                  Environment:
                                  All

                                  Cause:
                                  N/A

                                  Resolution:
                                  Both units have the same dimensions:
                                  4.96 (126 mm) inches deep
                                  5.75 (146 mm) inches tall
                                  7.09 (180 mm) inches wide

                                  What control voltage is needed for an ATS01N2..LY?

                                  Issue;
                                  What control voltage is needed for an ATS01N2..LY?

                                  Product Line:
                                  ATS01

                                  Environment:
                                  ATS01N2..LY

                                  Cause:
                                  Control power required on terminals 06-07.

                                  Resolution:
                                  The control power applied to terminals 06-07 is specified at 110Vac +-10%, 20VA.

                                  What is the combination SCCR rating for ATSU01 with the U-Line starters?

                                  Issue:
                                  Customer is using the ATSU01 with the mounted Tesys U-Line motor starter.  They are looking to coordinate the short circuit current rating.

                                  Product line:
                                  ATSU01, U-Line, Altistart 01, ATS01

                                  Environment:
                                  All models.

                                  Cause:
                                  n/a

                                  Resolution:
                                  Per Product Marketing, we do not have any combination SCCR ratings for the ATS and U-Line devices.  The ATSU01 and ATS01 have a standalone rating of 5kA.  Except the ATS01N103FT and ATS01N106FT, which are 1kA. 
                                   

                                  What control voltage is needed for an ATS01N1..FT softstart?

                                  Issue:
                                  What control voltage is needed for an ATS01N1..FT?


                                  Product Line:
                                  Altistart 01


                                  Environment:
                                  All


                                  Cause:
                                  N/A


                                  Resolution:
                                  The ATS01..FT models accommodate several control voltage options:
                                  110 - 230Vac can be connected to terminal CL2 and neutral to CL1/0
                                  24Vac or 24Vdc can be connected (+) to terminal 24V and (-) to CL1/0