Soft Starter 25A 110 480V

Soft Starter 25A 110 480V

Soft Starter 25A 110 480V

Item Number: ATS01N125FT

Retail
$1,332.51
RRP (Inc. GST)

Product Dimensions

Width icon

Width45 mm

Height icon

Height124 mm

Depth icon

Depth131 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Altistart 01

Product or component type

soft starter

Product destination

asynchronous motors

Warranty

18 months

Physical

Function available

integrated bypass

Marking

CE

Height

124 mm

Width

45 mm

Depth

131 mm

Net weight

0.35 kg

Standards

EN/IEC 60947-4-2

Product certifications

  • B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
  • C-Tick
  • CCC
  • GOST
  • CSA
  • UL
    • IP degree of protection

      IP20

      Relative humidity

      5-95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

      Ambient air temperature for operation

    • -10-40 °C (without derating)
    • 40-50 °C (with current derating of 2 % per °C)
      • Ambient air temperature for storage

        -25-70 °C conforming to EN/IEC 60947-4-2

        REACh free of SVHC

        Yes

        EU RoHS Directive

        Pro-active compliance (Product out of EU RoHS legal scope)

        Toxic heavy metal free

        Yes

        Mercury free

        Yes

        RoHS exemption information

        Yes

        China RoHS Regulation

        X

        Circularity Profile

        ENVEOLI100217EN

        California proposition 65

        WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov

        Others

        Product specific application

        simple machine

        Device short name

        ATS01

        Network number of phases

        1 phase

        [Us] rated supply voltage

        110...480 V - 10...10 %

        Motor power kW

      • 11 kW, 3 phases at 400 V
      • 3 kW, 3 phases at 230 V
      • 4 kW, 3 phases at 230 V
      • 9 kW, 3 phases at 400 V
      • 7.5 kW, 3 phases at 400 V
      • 5.5 kW, 3 phases at 230 V
      • 2.2 kW, 1 phase at 230 V
        • Motor power hp

        • 11 hp, 3 phases at 460 V
        • 2 hp, 3 phases at 210 V
        • 3 hp, 3 phases at 210 V
        • 5 hp, 3 phases at 230 V
        • 9 hp, 3 phases at 460 V
        • 7.5 hp, 3 phases at 230 V
          • IcL starter rating

            25 A

            Utilisation category

            AC-53B conforming to EN/IEC 60947-4-2

            Current consumption

            125 A at nominal load

            Type of start

            start with voltage ramp

            Power dissipation in W

          • 1 W at full load and at end of starting
          • 126 W in transient state
            • Assembly style

              with heat sink

              Supply voltage limits

              99-528 V

              Supply frequency

              50...60 Hz - 5...5 %

              Network frequency

              47.5...63 Hz

              Output voltage

              <= power supply voltage

              [Uc] control circuit voltage

            • 110 V AC +/- 10 % at 35 mA
            • 24 V AC/DC +/- 10 % at 30 mA
            • 240 V AC +/- 10 % at 80 mA
              • Starting time

              • 1 s / 100
              • 5 s / 20
              • adjustable from 1 to 5 s
                • Starting torque

                  30...80 % of starting torque of motor connected directly on the line supply

                  Discrete output current

                • 2 A DC-13
                • 3 A AC-15
                  • Tightening torque

                  • 0.5-0.5 N.m
                  • 1.9-2.5 N.m
                    • Electrical connection

                    • 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 2 0.5...1.5 mm² AWG 16 control circuit
                    • screw connector - rigid 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit
                    • screw connector - rigid 2 0.5...1 mm² AWG 17 control circuit
                    • screw connector - flexible with cable end 1 0.5...1.5 mm² AWG 16 control circuit
                    • 4 mm screw clamp terminal - flexible without cable end 1 1.5...10 mm² AWG 8 power circuit
                    • screw connector - flexible without cable end 1 0.5...2.5 mm² AWG 14 control circuit
                    • 4 mm screw clamp terminal - flexible with cable end 2 1...6 mm² AWG 10 power circuit
                    • 4 mm screw clamp terminal - flexible without cable end 2 1.5...6 mm² AWG 10 power circuit
                      • Operating position

                        vertical +/- 10 degree

                        Compatibility code

                        ATS01N1

                        Power range

                      • 2.2-3 kW at 200-240 V 3 phases
                      • 2.2-3 kW at 200-240 V 1 phase
                      • 4-6 kW at 200-240 V 3 phases
                      • 7-11 kW at 200-240 V 3 phases
                      • 7-11 kW at 380-440 V 3 phases
                        • Motor starter type

                          soft starter

                          Electromagnetic compatibility

                        • conducted and radiated emissions level B conforming to CISPR 11
                        • immunity to electrical transients level 4 conforming to IEC 61000-4-4
                        • immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3
                        • micro-cuts and voltage fluctuation conforming to IEC 61000-4-11
                        • voltage/current impulse level 3 conforming to IEC 61000-4-5
                        • conducted and radiated emissions level B conforming to IEC 60947-4-2
                        • damped oscillating waves level 3 conforming to IEC 61000-4-12
                        • electrostatic discharge level 3 conforming to IEC 61000-4-2
                        • EMC immunity conforming to EN 50082-1
                        • EMC immunity conforming to EN 50082-2
                        • harmonics conforming to IEC 1000-3-2
                        • harmonics conforming to IEC 1000-3-4
                        • immunity to conducted interference caused by radio-electrical fields level 3 conforming to IEC 61000-4-6
                          • Pollution degree

                            2 conforming to EN/IEC 60947-4-2

                            Vibration resistance

                          • 1 gn (f= 13-150 Hz) conforming to EN/IEC 60068-2-6
                          • 1.5 mm peak to peak (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
                            • Shock resistance

                              15 gn for 11 ms conforming to EN/IEC 60068-2-27

                              Operating altitude

                            • <= 1000 m without derating
                            • > 1000 m with current derating of 2.2 % per additional 100 m
                              • Unit Type of Package 1

                                PCE

                                Number of Units in Package 1

                                1

                                Package 1 Weight

                                401 g

                                Package 1 Height

                                5.2 cm

                                Package 1 width

                                15.5 cm

                                Package 1 Length

                                17.5 cm

                                Unit Type of Package 2

                                S03

                                Number of Units in Package 2

                                14

                                Package 2 Weight

                                6.294 kg

                                Package 2 Height

                                30 cm

                                Package 2 width

                                30 cm

                                Package 2 Length

                                40 cm

                                Unit Type of Package 3

                                P06

                                Number of Units in Package 3

                                112

                                Package 3 Weight

                                44.912 kg

                                Package 3 Height

                                75 cm

                                Package 3 width

                                60 cm

                                Package 3 Length

                                80 cm

                                WEEE

                                The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
                                Show all specifications

                                Frequently Asked Questions

                                hide show

                                Does the ATS01 come with a shorting contactor?

                                Issue:
                                Does the ATS01 come with a shorting contactor?

                                Product Line:
                                Altistat 01

                                Environment:
                                All

                                Cause:
                                N/A

                                Resolution:
                                All of the ALTISTART 01 models, except the ATS01N103FT and ATS01N106FT, have an internal shorting contactor as standard.

                                Is the LH4N still available?

                                Issue:
                                Is the LH4N still available?

                                Product Line:
                                LH4N

                                Environment:
                                All models and all serial numbers

                                Cause:
                                Customer was looking for purchasing the LH4N112RT7.

                                Resolution:
                                No, the LH4N soft starter is obsolete. Please replace with the appropriate ATS01 or ATS22 soft starter. Consider application needs and features of currently-offered products.


                                 

                                Are Softstarters acceptable for use in a Fire Pump applications?

                                Issue:
                                Are Softstarters acceptable for use in a Fire Pump applications?

                                Product line:
                                Altistart 22 48 ATS22 ATS48

                                Environment:
                                all

                                Cause:
                                Fire pump systems typically require the motors to run until they fail, without faulting the controller

                                Resolution:
                                No. The softstarters are not rated for Fire pump requirements and does not meet the requirements.
                                 

                                Does Schneider offer a soft start for a single phase motor?

                                Issue:
                                Soft start for a single phase motor?

                                Product Line:
                                ATS01

                                Environment:
                                All

                                Cause:
                                Needs a soft starter for a single phase motor. 

                                Resolution:
                                Yes, but the offering is limited.  The ATS01N1**FT products are rated for single phase motors up to 2HP at 240V and 1/2HP at 120V.
                                See the attachment beginning on page 34.  Reference page 40 for part number selection.

                                What are the adjustment ranges for the dials on an ATS01N1..FT?

                                For the START TIME dial, setpoint A is 1second and setpoint E is 5seconds.  There is a linear relationship from A to E setpoints.
                                For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                CTA-ID : 2061387

                                How can ATS01N2...LU, QN, RT be started without control wires?

                                Issue:
                                How can ATS01N2...LU, QN, RT be started without control wires?

                                Product Line:
                                Altistart 01 Soft Starters with "LU", "QN", or "RT" at the end of the part number

                                Environment:
                                All

                                Cause:
                                Need to start the Soft Starter with power up

                                Resolution:
                                Add a jumper between terminals LI+ and LI2.  This provides a continuous RUN command.  When power is supplied to the ATS01, it will immediately begin to start the motor.  Removing power will result in a freewheel stop.

                                 

                                What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?

                                What are the adjustment ranges for the dials on an ATS01N2..LU/QN/RT?


                                Issue:

                                Adjusting Altistart 01 Soft Starters


                                Product Line:
                                Altistart 01


                                Environment:
                                All


                                Cause:
                                N/A


                                Resolution:

                                For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.
                                 

                                What control voltage is needed for an ATS01N1..FT softstart?

                                Issue:
                                What control voltage is needed for an ATS01N1..FT?


                                Product Line:
                                Altistart 01


                                Environment:
                                All


                                Cause:
                                N/A


                                Resolution:
                                The ATS01..FT models accommodate several control voltage options:
                                110 - 230Vac can be connected to terminal CL2 and neutral to CL1/0
                                24Vac or 24Vdc can be connected (+) to terminal 24V and (-) to CL1/0

                                 

                                What is the combination SCCR rating for ATSU01 with the U-Line starters?

                                Issue:
                                Customer is using the ATSU01 with the mounted Tesys U-Line motor starter.  They are looking to coordinate the short circuit current rating.

                                Product line:
                                ATSU01, U-Line, Altistart 01, ATS01

                                Environment:
                                All models.

                                Cause:
                                n/a

                                Resolution:
                                Per Product Marketing, we do not have any combination SCCR ratings for the ATS and U-Line devices.  The ATSU01 and ATS01 have a standalone rating of 5kA.  Except the ATS01N103FT and ATS01N106FT, which are 1kA. 
                                 

                                What are the adjustment ranges for the dials on an ATSU01N2..LT?

                                For both the START TIME and STOP TIME dials, setpoint A is 1second and setpoint E is 10seconds.  There is a linear relationship from A to E setpoints.
                                For the INITIAL VOLTAGE dial, setpoint A is 30% and setpoint E is 80% of full voltage.  There is a linear relationship from A to E setpoints.



                                CTA-ID : 2061385

                                ATS01N222RT Can you do a soft stop?

                                Issue: 
                                How do I get the ATS01 to softstop? 
                                 
                                Product Line:
                                ATS01 Altistart 01 Altivar

                                Environment:
                                ATS01.....RT

                                Cause:
                                Need soft stopping. 

                                Resolve: 
                                If you have a jumper between LI2 and LI+ terminals, you will have soft starting with line power and a coast to stop when line power is removed.

                                If you have a start-stop signal that closes LI2 to LI+ to start, it will softstart according to the start dial.  When you open this contact it will soft stop (decelerate) according to the stop dial setting.

                                What is the replacement for the High HP ATS01N softstarters?

                                Issue:
                                Wants to order the ATS01N230LY, ATS01N244LY, ATS01N272LY or ATS01N285LY

                                Product line:
                                ATS01, Altistart 01, High HP

                                Environment:
                                All models

                                Cause:
                                The launch of the ATS22 in 2011 caused the High HP units to become redundant.

                                Resolution:

                                The ATS01 High HP units were replaced with the ATS22 units.  These are functional replacements only.  The ATS01 had no overload protection, an internal power supply and simple dial adjustments.  The ATS22 will require external 120V or 230V power.  There are no dials to adjust, but the unit will need to be programmed.  See the ATS22 User Maual, document BBV51300 to review the wiring, dimensions and programming.

                                ATS01N230LY - 32A rated.  Replaced by ATS22D32S6U
                                ATS01N244LY - 44A rated.  Replaced by ATS22D47S6U
                                ATS01N272LY - 72A rated.  Replaced by ATS22D75S6U
                                ATS01N285LY - 85A rated.  Replaced by ATS22D88S6U

                                 
                                Show More