Phaseo Battery Control Module, 24..28.8VDC, 24V, 20A, for Regulated SMPS

Phaseo Battery Control Module, 24..28.8VDC, 24V, 20A, for Regulated SMPS

Phaseo Battery Control Module, 24..28.8VDC, 24V, 20A, for Regulated SMPS

Item Number: ABL8BBU24200

Retail
$1,560.90
RRP (Inc. GST)

Product Dimensions

Width icon

Width60 mm

Height icon

Height125 mm

Depth icon

Depth160 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range of product

Phaseo

Product or component type

battery control module

Sustainable offer status

Green Premium product

Warranty

18 months

Physical

Connections - terminals

  • for diagnostic relay: removable screw terminal block, connection capacity: 1 x 0.75 mm²
  • for input connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
  • for output connection: screw type terminals, connection capacity: 2 x 0.5...2 x 10 mm² AWG 20...AWG 8
    • Fixing mode

    • by clips on 35 mm symmetrical DIN rail, operating position: horizontal
    • by clips on 35 mm symmetrical DIN rail, operating position: vertical
      • Marking

        CE

        Local signalling

      • 1 C/O relayalarm status:
      • 1 C/O relaybattery status:
      • 1 C/O relaypower supply status:
      • LCD screenmodule status:
        • Width

          60 mm

          Height

          125 mm

          Depth

          160 mm

          Net weight

          0.5 kg

          Product certifications

        • RCM
        • EAC
          • Standards

          • UL 508
          • CSA C22.2 No 60950-1
            • Ambient air temperature for operation

              -25-60 °C

              Ambient air temperature for storage

              -40-85 °C

              Environmental characteristic

            • EMC conforming to EN 61000-6-3
            • EMC conforming to EN/IEC 61000-6-2
            • safety conforming to EN/IEC 60950-1
            • safety conforming to EN/IEC 61204-3
              • IP degree of protection

                IP20 conforming to EN/IEC 60529

                Relative humidity

              • 0-90 % during operation
              • 0-95 % during storage
                • REACh Regulation

                  Reference contains Substances of Very High Concern above the threshold

                  REACh free of SVHC

                  Yes

                  EU RoHS Directive

                  Pro-active compliance (Product out of EU RoHS legal scope)

                  Mercury free

                  Yes

                  RoHS exemption information

                  Yes

                  China RoHS Regulation

                  X

                  Environmental Disclosure

                  ENVPEP121210EN

                  Circularity Profile

                  ENVEOLI1212010EN

                  California proposition 65

                  WARNING: This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov

                  Others

                  Input voltage

                  24...28.8 V DC

                  Output voltage

                • (Ubattery-0.5) V in battery mode DC
                • (Uin-0.25) V in nominal mode DC
                  • Maximum output current

                    20 A

                    Input voltage limits

                    22...30 V

                    Maximum power dissipation in W

                    7 W

                    Activation threshold

                    adjustable 22...36 V

                    Number of output channels

                    1

                    Holding current

                  • 15 A
                  • 4 A
                  • 5 A
                  • 7 A
                  • 1 A
                  • 20 A
                  • 3 A
                  • 10 A
                  • 2 A
                  • 6 A
                  • 8 A
                    • Current consumption

                    • 0.6 A on load
                    • 0.1 mA no load
                    • <= 40.6 A
                      • Output protection type

                      • against overload, protection technology: 1.5 x In
                      • against short-circuits, protection technology: battery-backed mode, automatic reset
                      • against short-circuits, protection technology: power-supplied mode
                        • Operating altitude

                          2000 m

                          Name of test

                        • electrostatic discharges conforming to EN/IEC 61000-4-2
                        • emission conforming to EN 61000-6-3
                        • induced electromagnetic field conforming to EN/IEC 61000-4-6 level 3
                        • radiated electromagnetic field conforming to EN/IEC 61000-4-3 level 3
                        • rapid transient conforming to IEC 61000-4-4 level 3
                        • surge conforming to EN/IEC 61000-4-5 level 2
                        • conducted/radiated emissions conforming to EN 55022 class B, 20 %
                          • Holding time

                          • 20 mn
                          • 2 s
                          • 5 h
                          • 3 h
                          • 5 mn
                          • 1 mn
                          • 7 mn
                          • 30 s
                          • 5 s
                          • 10 s
                          • 3 mn
                          • 4 mn
                          • 40 mn
                          • 2 h
                          • 0.5 s
                          • 1 s
                          • 2 mn
                          • 15 mn
                          • 10 mn
                          • 1 h
                          • 8 mn
                          • 9 mn
                          • 50 mn
                          • 30 mn
                          • 6 mn
                            • Holding solution

                              use of battery modules

                              Compatibility code

                              ABL8B

                              Dielectric strength

                            • 500 V between input and ground
                            • 500 V between output and ground
                              • Overvoltage category

                                class II conforming to VDE 0106-1

                                MTBF reliability

                                718708 H at 24 V DC with UTE C80-810 calculation method

                                Vibration resistance

                              • 2 gn (f= 11.9-150 Hz) conforming to EN/IEC 61131-2
                              • 3.5 mm (f= 3-11.9 Hz) conforming to EN/IEC 61131-2
                                • Unit Type of Package 1

                                  PCE

                                  Number of Units in Package 1

                                  1

                                  Package 1 Weight

                                  1.468 kg

                                  Package 1 Height

                                  9 cm

                                  Package 1 width

                                  19.5 cm

                                  Package 1 Length

                                  19.5 cm

                                  Unit Type of Package 2

                                  S03

                                  Number of Units in Package 2

                                  8

                                  Package 2 Weight

                                  11.929 kg

                                  Package 2 Height

                                  30 cm

                                  Package 2 width

                                  30 cm

                                  Package 2 Length

                                  40 cm

                                  Unit Type of Package 3

                                  P06

                                  Number of Units in Package 3

                                  72

                                  Package 3 Weight

                                  118.7 kg

                                  Package 3 Height

                                  80 cm

                                  Package 3 width

                                  80 cm

                                  Package 3 Length

                                  60 cm

                                  PVC free

                                  Yes
                                  Show all specifications

                                  Documents & downloads

                                  hide show
                                  Filter items
                                  • All

                                  • CAD Files and Packs

                                  • Product Brochures

                                  • Technical Data Catalogues

                                  • Installation Instruction

                                  • Product Environmental

                                  • End of Life Manual

                                  • eTechPub

                                  • Certificates (MSDS)

                                  Frequently Asked Questions

                                  hide show

                                  What is the alternative to ABL4WSR24200?

                                  Replacement is ABL8WPS24200

                                  What is the replacement for ABL4RSM24200?

                                  Replacement is the ABL8RPM24200 .

                                  What is the replacement for a ABL8WPS24200

                                  Use a ABL4WSR24200.

                                  What is the operating temperature range on the ABL8WPS24200 and ABL8WPS24400 power supplies?

                                  Issue:
                                  Needs environmental data for ABL8WPS24200 and ABL8WPS24400.

                                  Product Line:
                                  Relays and Timers

                                  Environment:
                                  ABL Phaseo Power Supplies
                                   
                                  Resolution:
                                  Per expanded catalog DIA3ED207041EN-US, page 30, "-13°F to 140°F with derating from 122 °F or  (-25 to +60 derating from 50°C)".

                                  What is the mean time between failures (MTBF) for ABL8RPM24200?

                                  The 2 MTBF values for ABL8RPM24200 are;

                                  • 717000h for 100Vac
                                  • 695000h for 240Vac

                                   
                                   
                                   
                                   

                                  What is the replacement for ABL4RPM24100?

                                  ABL8RPS24100
                                  Show More