Frequently Asked Questions
hide
show
Is it possible to connect PowerTag C devices (I/O and 2DI) to SmartLink SI B or SI D ?
PowerTag C A9XMC1D3 and A9XMC2D3 cannot be connected to a Smartlink A9XMZA08 or A9XMWA20.
PowerTag C devices are only compatible with PowerTag Link gateways A9XMWD20 or A9XMWD100 with FW 1.4.5.
What is the Alternative for code14885 ?
A9XPCM04 - set of 4 connetors
Can I connect a PowerTag Ambient A9XST114 to a PowerTag Link or Smartlink SIB / SID gateway ?
PowerTag Ambient A9XST114 is not compatible with PowerTag Link (A9XMWD20 and A9XMWD20) or Smartlink gateways (A9XMZA08 and A9XMZA20).
A9XST114 is a thermal sensor that can only be paired with Acti 9 PowerTag Link C gateway (A9XELC10).
How do you connect to UL 1077 Comb Bus Bars # 10285, 10286, or 10287?
Issue:
How to wire comb busbars 10285, 10286, or 10287
Product Line:
Multi-9 Circuit Breaker accessories
Environment:
Molded Case Circuit Breakers
Cause:
Cannot find equivalent to insulated connectors used with UL 489 and IEC comb bus bars. Need to know how the UL 1077 comb bus bars are wired.
Resolution:
Field wiring is applied directly to the comb bus bar by inserting both the wire and the tooth of the comb bus bar into the same box lug of the Multi-9 breaker. Alternatively, an appropriately sized breaker applied to the busbar can be backfed to power the bus.