Add-on block; Vigi iC60 25/63A 1PPN

Acti9 iC60 Earth Leakage Add-on Block, 1P + N, 63A - 300mA, A Type

Catalogue Number: A9V06663
Add-on block; Vigi iC60 25/63A 1PPN
Retail
$1392.42*
RRP (Inc. GST)

Specifications

hide show
Range
Acti 9
Range of product
iC60
Product or component type
add-on residual current devices
Device short name
Vigi iC60
Poles description
1P + N
Neutral position
left
[In] rated current
63 A
Earth-leakage sensitivity
300 mA
Earth-leakage protection time delay
instantaneous
Earth-leakage protection class
type A
Network type
AC
Network frequency
50/60 Hz
[Ue] rated operational voltage
240 V AC 50/60 Hz conforming to IEC 61009-1
Standards
  • EN 61009-1
  • IEC 61009-1
    • 9 mm pitches
      4
      Device location in system
      outgoer
      Residual current tripping technology
      voltage independent
      [Ui] rated insulation voltage
      500 V AC 50/60 Hz conforming to IEC 60947-2
      [Uimp] rated impulse withstand voltage
      6 kV conforming to IEC 60947-2
      Range compatibility
      Acti 9 iC60
      Product compatibility
      single terminal
      Local signalling
      trip indicator
      Mounting mode
      clip-on
      Mounting support
      DIN rail
      Electrical connection to mcb
      by screws
      Comb busbar and distribution block compatibility
      bottom: YES
      Height
      91 mm
      Width
      54 mm
      Depth
      73.5 mm
      Net weight
      0.165 kg
      Connections - terminals
    • tunnel type terminal downside for 1 cable(s) 1-35 mm² rigid without cable end
    • tunnel type terminal downside for 1 cable(s) 1-25 mm² flexible without cable end
    • tunnel type terminal downside for 1 cable(s) 1-25 mm² flexible with cable end
      • Wire stripping length
        14 mm for bottom connection
        Tightening torque
        3.5-3.5 N.m bottom
        IP degree of protection
      • IP20 conforming to IEC 60529
      • IP40 (modular enclosure) conforming to IEC 60529
        • Pollution degree
          3 conforming to IEC 60947-2
          Electromagnetic compatibility
          8/20 µs impulse withstand, 250 A conforming to IEC 61009-1
          Ambient air temperature for operation
          -5-60 °C
          Ambient air temperature for storage
          -40-85 °C
          Sustainable offer status
          Green Premium product
          REACh Regulation
          Free of Substances of Very High Concern above the threshold
          EU RoHS Directive
          Compliant
          Mercury free
          Yes
          RoHS exemption information
          Yes
          China RoHS Regulation
          Product out of China RoHS scope. Substance declaration for your information
          Environmental Disclosure
          ENVPEP1409017EN
          WEEE
          The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
          Warranty
          18 months

          Frequently Asked Questions

          hide show

          Do you do a 3 pole version of a 4RCBM232/30?

          Unfortunately we do not offer a 3 pole version of a 4RCBM230/30.

          However as an alternative we can offer a A9F54432 (4 Pole 32A Circuit Breaker) and a A9V06763 (Vigi Block).

          For further information please visit www.clipsal.com/Trade

          Is there a shunt trip that can be used in conjunction with a iSW series?

          No unfortunately the ISW series can't be used with shunt release.

          For further information please visit Global Specialist in Energy Management | Schneider Electric

          Is there an alternative for a 1 module RCD-MCB part number 4RCBE116/30D?

          Yes, however it is larger in size as it requires 4 modules. The replacement part numbers are A9F55116 + A9V02663.

          What is a 1 pole 20 amp "D" curve RCBO?

          Use a 1 pole 20 amp "D" curve breaker A9F55120 and add the vigi unit A9V02663 to make the Combo ...(now 3 poles wide)
          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9F55120
          and vigi
          https://eshop.schneider-electric.com/product.aspx?org=21&lang=1&dist=276&prod_id=A9V02663

          User-added image
           User-added image

          How can I make 1 Pole 10 Amps B Curve 30mA RCBO?

          To make 1 Pole 10 Amps B Curve 30mA RCBO, you need the following:
          A9F53110 - 1 Pole 10 Amps B Curve Breaker (https://www.schneider-electric.com.au/en/search/A9F53110)
          +
          A9V02663 - 2 Pole 30mA 63 Amps Add-on Vigi to suit 1 Pole iC60 Breakers (https://www.schneider-electric.com.au/en/search/A9F53110)

          Please note the total width of this combination will be equal to 3 Poles standard RCBO (3 x 18mm)

          what is the Australian replacement for a A9C20663?

          The replacement is a Acti 9 A9C20863

          Is A9A27006 suitable to use on A9S66463?

          Yes, A9A27006 is suitable to use on A9S66463

           

          What is the suitable vigi unit to suit with the A9F54332?

          A9F54332 is a 3 pole breaker.
          They have an option of having 3 pole vigi (A9V51363) or 4 pole vigi (A9V02763) for neutral conection .