Acti9 iARC 1PN 25A AFD
Acti9 iARC 1PN 25A AFDS-ON
Acti9 iARC 1PN 25A AFD
Acti9 iARC 1PN 25A AFDS-ON

Acti9 iARC 1PN 25A AFDS

Catalogue Number: A9TS1225
Acti9 iARC 1PN 25A AFD
Acti9 iARC 1PN 25A AFDS-ON
Acti9 iARC 1PN 25A AFD
Acti9 iARC 1PN 25A AFDS-ON
Retail
$360.13
RRP (Inc. GST)

Specifications

hide show
Range
Acti9
Product or component type
arc fault detection switch
Product specific application
arc fault detection
Product name
Acti 9 iARC
Device short name
iARC
Poles description
1P + N
Neutral position
left
Network type
AC
Rated breaking and making capacity
Im = 500 A
Rated conditional short-circuit current
  • upstream MCB 25A: Inc 10 kA
  • upstream RCBO 25A: Inc 10 kA
    • Device location in system
      outgoer
      Maximum [In] rated current
      25 A
      Network frequency
      50 Hz
      [Ue] rated operational voltage
      230...240 V AC 50 Hz conforming to IEC 62606
      [Ui] rated insulation voltage
    • 250 V AC 50 Hz between phase and neutral
    • 400 V AC 50 Hz between phases
      • [Uimp] rated impulse withstand voltage
        4 kV conforming to IEC 62606
        Threshold tripping voltage
        275 V +/- 5 V
        Contact position indicator
        yes
        Control type
        toggle
        Local signalling
        ON, OFF, fault trip
        Mounting mode
        clip-on
        Mounting support
        DIN rail
        Mechanical durability
        20000 cycles
        Electrical durability
        10000 cycles 240 V AC 50 Hz conforming to IEC 62606
        Heat dissipation
        4.38-4.38 W at 240 V - 25 A
        Connections - terminals
      • tunnel type terminal2 cable(s) 2.5-2.5 mm² rigid
      • tunnel type terminal1 cable(s) 16-16 mm² rigid
      • tunnel type terminal2 cable(s) 2.5-2.5 mm² flexible
      • tunnel type terminal1 cable(s) 10-10 mm² flexible
        • Cable entry
          top and bottom
          Locking options description
          padlocking device
          Wire stripping length
          14 mm
          Tightening torque
          2-2 N.m
          9 mm pitches
          4
          Height
          91 mm
          Width
          36 mm
          Depth
          75 mm
          Net weight
          205 g
          IP degree of protection
          IP20 conforming to IEC 60529
          Pollution degree
          2 conforming to IEC 62606
          Overvoltage category
          III
          Tropicalisation
          severity B conforming to IEC 60068-2-30 for 28 d
          Relative humidity
          95-95 % at 55-55 °C
          Operating altitude
          2000 m
          Ambient air temperature for operation
          -25-60 °C
          Ambient air temperature for storage
          -40-80 °C
          Standards
          IEC 62606
          Quality labels
          RCM
          Sustainable offer status
          Green Premium product
          EU RoHS Directive
          Compliant
          Mercury free
          Yes
          RoHS exemption information
          Yes
          China RoHS Regulation
          Product out of China RoHS scope. Substance declaration for your information
          Environmental Disclosure
          ENVPEP1906001EN
          Circularity Profile
          ENVEOLI1906001EN

          Documents & downloads

          hide show
          Filter items
          • All

          • End of Life Manual

          • Installation Instruction

          • Product Environmental

          • Certificates (MSDS)

          Frequently Asked Questions

          hide show

          What is the part number for 2 pole 25amp Acti 9 C/B?

          A9F44225

          Can an AFDD replace an earth leakage current protection device?

          The new AFDD comes with different versions:
          - Without a protection against earth leakage current (Catalogue No. A9TS1225 for commercial applications). In this case, AFDD, can help to provide a protection against arc faults (serial arc faults, parallel arc faults and arc to earth). Indeed, even if it helps to protect against electrical arcs between phase and earth, because of its design and technology, monitoring and protection provided by arc detectors is not equivalent to the one provided by a traditional earth leakage protection device.
          - With a protection against earth leakage current. All Clipsal branded AFDD references for residential applications and remaining Schneider branded AFDD references for commercial applications come with protection against earth leakage current. in this case AFDD can provide a combined protection against overcurrent, overvoltage, arc faults (serial arc fault, parallel arc fault and arc to earth) and earth leakage.
           

          What is the replacement part for a 26896 RCB?

          The replacement part is a A9D61820.
          A9D11220 is best solution
          A9D11820 is an alternative 1 pole wide but no Neutral switching
          A9D61820 is an alternative 1 pole wide but no Neutral switching and only 6kA