Acti9 iDPN H VigiArc 1PN C 6A 30mA A

Acti9 iDPN H VigiArc 1PN C 6A 30mA A

Acti9 iDPN H VigiArc 1PN C 6A 30mA A

Item Number: A9T27606

Retail
$611.55
RRP (Inc. GST)

Product Dimensions

Width icon

Width36 mm

Height icon

Height91 mm

Depth icon

Depth75 mm

See full specifications

Datasheet

Barcode

Qty UoM EAN Colour
-
-
-

Specifications

Design

Range

Acti9

Product or component type

arc fault detection RCBO

Sustainable offer status

Green Premium product

Warranty

24 months

Physical

Standards

  • EN/IEC 62606
  • AS/NZS 61009.1
    • [In] rated current

      6 A

      [Ue] rated operational voltage

    • 230/240 V AC 50 Hz conforming to AS/NZS 61009.1
    • 230/240 V AC 50 Hz conforming to IEC 62606
      • Control type

        toggle

        Local signalling

        ON, OFF, fault trip

        Mounting mode

        clip-on

        Mounting support

        DIN rail

        Mechanical durability

        20000 cycles

        Electrical durability

        20000 cycles 240 V AC 50 Hz conforming to AS/NZS 61009.1

        Cable entry

        top and bottom

        Connections - terminals

      • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² rigid
      • tunnel type terminal for 1 cable(s) 16-16 mm² rigid
      • tunnel type terminal for 2 cable(s) 2.5-2.5 mm² flexible
      • tunnel type terminal for 1 cable(s) 10-10 mm² flexible
        • Wire stripping length

          14 mm

          Height

          91 mm

          Width

          36 mm

          Depth

          75 mm

          Net weight

          205 g

          IP degree of protection

          IP20 conforming to IEC 60529

          Relative humidity

          95-95 % at 55-55 °C

          Ambient air temperature for operation

          -25-60 °C

          Ambient air temperature for storage

          -40-80 °C

          REACh Regulation

          Free of Substances of Very High Concern above the threshold

          EU RoHS Directive

          Compliant

          Mercury free

          Yes

          RoHS exemption information

          Yes

          China RoHS Regulation

          Product out of China RoHS scope. Substance declaration for your information

          Environmental Disclosure

          ENVPEP1906001EN

          Circularity Profile

          ENVEOLI1906001EN

          Others

          Product name

          Acti9 iDPN H VigiARC

          Product specific application

          arc fault detection

          Device short name

          iDPN H VigiARC

          Poles description

          1P + N

          Number of protected poles

          1

          Curve code

          C

          Breaking capacity

          7500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1

          Rated breaking and making capacity

          Idm 500 A at 240 V AC 50 Hz conforming to AS/NZS 61009.1

          Neutral position

          left

          Earth-leakage sensitivity

          30 mA

          Network type

          AC

          Earth-leakage protection time delay

          instantaneous

          Earth-leakage protection class

          class A

          Suitability for isolation

          yes

          Residual current tripping technology

          voltage dependent

          Trip unit technology

          thermal-magnetic

          Earth-leakage protection

          integrated

          Network frequency

          50 Hz

          Device location in system

          outgoer

          Magnetic tripping limit

          5...10 x In

          Limitation class

          3 conforming to AS/NZS 61009.1

          [Ui] rated insulation voltage

        • 250 V AC 50 Hz between phase and neutral
        • 400 V AC 50 Hz between phases
          • Threshold tripping voltage

            275 V +/- 5 V

            [Uimp] rated impulse withstand voltage

            4 kV conforming to AS/NZS 61009.1

            Contact position indicator

            yes

            Overvoltage category

            III

            Locking options description

            padlocking device

            Tightening torque

            2-2 N.m

            Comb busbar and distribution block compatibility

            YES

            9 mm pitches

            4

            Heat dissipation

            2.89-2.89 W at 240 V - 6 A

            Pollution degree

          • 2 conforming to AS/NZS 61009.1
          • 2 conforming to IEC 62606
            • Tropicalisation

              severity B conforming to IEC 60068-2-30 for 28 d

              Operating altitude

              2000 m

              Quality labels

              RCM
              Show all specifications

              Documents & downloads

              hide show
              Filter items
              • All

              • Installation Instruction

              • End of Life Manual

              • Product Environmental

              • Certificates (MSDS)

              Frequently Asked Questions

              hide show

              Is A9A27006 suitable to use on A9S66463?

              Yes, A9A27006 is suitable to use on A9S66463

               

              What is the IP Rating of A9A27006?

              IP55

              What is the difference between A9D32620 and A9D33620 RCBO Acti 9 devices?

               
               

              A9D33620 = SI (Super Immunised)
              A9D32620 = Type A (AC or pulsating DC)

              Type A RCBO = Tripping is ensured for residual sinusoidal alternating currents and residual pulsating direct currents, whether suddenly applied or slowly rising.
              Type Si RCBO = With all the features of a Type A device, “Si” type Super Immunised earth leakage protection range has been specially developed to be used with loads or in environments causing disturbances. Examples are lightning or switching surges, harmonics generated by increasing number of loads and constant load leakage current from electronic ballasts, speed drives, computers, etc. The Si increases safety and allows improved continuity of supply.